Par
.
no.
Parameter
Number of
elements
T
ype
Edit
V
alue range
Min Max
Resolution
Default
setting
Password
level
125
Mains frequency
0 = 50 Hz
1 = 60 Hz
1
Selection
edit
0
1
1
LMV37.400...: 0
LMV37.420...: 1
SO
126
Display brightness
1
Std_u8
edit
0%
100%
1%
LMV37.400...: 75 %
LMV37.420...: 100
%
SO
128
Fuel meter: Pulse valency [pulses / volume unit]
1
Std_u16
edit
0
400
0.01
0
SO
130
Delete display of error history
To delete the display: Set parameter to 1, then to 2
Return value 0: Job successfully completed
Return value -1: Timeout of 1_2 sequence
1
Std_s8
edit
-5
2
1
0
SO
133
Default output for TÜV test
Invalid = TÜV test when output is active
2.000...10.000 = low-fire...high-fire or stage 1 / stage 2 /
stage 3
1
Output
edit / clear
20 %
100 %
0.1 %
undefined
SO
141
Operating mode BACS
0 = off
1 = Modbus
2 = reserved
1
Selection
edit
0
2
1
0
SO
142
Setback time in the event of communication breakdown
Setting values
0 = inactive
1….7200 s
1
Std_u16
edit
0 s
7200 s
1 s
120 s
SO (BA)
143
Reserved
1
Std_u8
edit
1
8
1
1
Info / Service
144
Reserved
1
Std_u16
edit
10 s
60 s
1 s
30 s
SO
145
Device address for Modbus of basic unit
Setting values
1…247
1
Std_u8
edit
1
247
1
1
SO
146
Setting of Baud rate for Modbus communication
Setting values
0 = 9600
1 = 19200
1
Selection
edit
0
1
1
1
SO
147
Parity for Modbus
0 = none
1 = odd
2 = even
1
Selection
edit
0
2
1
0
SO