Downloading
Once the operating parameters have been set up, they
must be downloaded to the respective Control Panel,
as follows.
1.
Remove the screws
4
and open the Control panel.
2.
Connect the jumper
65
to the
first and second ter-
minal
pins on the 3-pin terminal strip marked
PRG
on the Main Board. All the Control panel LEDs will
go OFF except for the
Disab./Fault Telecom
LED
which will blink — to indicate that the system is re-
ady for programming via computer.
3.
Connect the Control Panel serial port (
67
) to one of
the PC serial ports, as follows:
– using a
CVSER/9F9F
link (accessory item), or a
cable similar to the one in Figure 27a;, connect the
Control Panel to the PC;
– if the PC serial port has 25 pins, use an
ADSER/9M25F
adapter (accessory item), or a ca-
ble similar to the one in Figure 27b.
4.
Select the PC serial port used for connection with
the Control panel, as follows:
– select
Serial Ports
from the
Setup
menu;
– select the serial port (
Control Panel
section);
– click or
OK
.
5.
Select the parameters to be downloaded, as fol-
lows:
– select
Control panel
from the
Setup
menu;
– select the Control panel type from the
Panel
menu;
– select the respective firmware release from the
Firmware
menu;
– click
OK
.
6. To download a specific page:
click the
DWLoad
button on the page in question.
To Download several pages:
– select the required page from the
Pages
menu,
right click,
Select
(a
ü
on the page Icon indicates
that it will be downloaded);
– repeat the procedure for all the required Pages;
– right click again then select
DWLoad
.
+
To download a group of pages, select the root.
For example: to download all the Configuration related
pages, select
Configuration
from the
Pages
menu; to
download
All
the Pages, select
J400
from the
Pages
menu.
7.
To view the Control panel parameters —
work care-
fully through point
6
then select
UPLoad
instead of
DWLoad
.
8.
To exit the Programming session
— connect the
jumper
65
to the
second and third terminals
on
the 3-pin terminal strip marked
PRG
on the Main
Board. The Control panel will Reset automatically.
PROGRAMMING FROM A PC
43
5
4
6
5
4
3
2
1
9
18
8
19
17
16
15
14
7
20
21
22
23
24
25
6
3
7
2
8
9
10
11
12
13
1
DB9 Female
connector
a)
b)
7-wire cable
shield
DB25 Female
connector
5
5
4
4
9
9
8
8
7
7
6
6
3
3
2
2
1
1
DB9 Female
connector
7-wire cable
shield
DB9 Female
connector
Figure 27
Wiring diagram for the serial link between the Control panel and PC
Summary of Contents for J408
Page 1: ...INSTALLATION MANUAL CONVENTIONAL F I R E PA N E L S 424 408...
Page 17: ...IDENTIFICATION OF PARTS 17 C N O N C 36 35 b...
Page 29: ...USER S INSTRUCTIONS CONVENTIONAL F I R E PA N E L S 424 408...
Page 52: ...44 Conventional Fire Panels J424 J408...
Page 61: ...QUICK GUIDE 53...
Page 62: ...54 Conventional Fire Panels J424 J408...
Page 63: ...QUICK GUIDE 55...