Pre-extinguishment Phase
If the programmed extinguishment conditions occur
(programmed by your Installer), the Extinguishment
Module will generate the Pre-extinguishment phase
which will be signalled by:
Ø
the devices set up by the installer;
Ø
the
ON Pre Ext
. LED (On).
The Extinguishment Module will activate the Fire Extin-
guishment devices when the Pre-extinguishment Time
expires.
The Pre-extinguishment phase will allow you to check
whether use of these devices and Evacuation of the
premises are really necessary.
The Pre-extinguishment phase can be terminated by
means of the:
Ø
Disable Extinguish.
button;
Ø
duly set up manual buttons.
+
The
Disable Extinguish.
button can be used du-
ring Access Level 2 only.
n
Extinguishment Phase
The Extinguishment Module will activate the Fire Extin-
guishment devices when the Pre-extinguishment Pha-
se expires.
The Extinguishment Phase will be signalled by.
Ø
the
ON Electrovalve
LED (On).
The
AV ACTIVATED
event, and the respective details
will be recorded in the logger (
EXTING.MODULE 1
or
EXTING.MODULE 1
).
The Extinguishment Phase will run for the pre-set
Extinguishment Time or, until the Control panel Resets.
The Extinguishment Phase can be interrupted by the:
Ø
Disable Extinguish.
button;
Ø
duly set up
Inhibit Extinguishment
call points.
+
The
Disable Extinguish.
button can be used du-
ring Access Level 2 only.
If you re-enable the Extinguishment phase, it will not
start until the pre-set Pre-extinguishment Time ends.
If you restore the
Inhibit Extinguishment
call points to
standby status, the Extinguishment phase will restart
immediately.
n
Manual Extinguishment
The Extinguishment Module can be activated from ma-
nual call-points (ask your Installer for details).
Manual activation of the Extinguishment Module is si-
gnalled by:
Ø
the
ON Manual Ext.
LED (On);
Ø
a message on the display similar to the following:
EXTING.MODULE.1
MANUAL ACTIVATE
+
If you activate the Extinguishment Module ma-
nually, the Control panel will generate an Alarm.
n
Disable Extinguish. button
This button will allow you to inhibit the Fire Extingui-
shment devices.
+
The
Disable Extinguish.
button can be used du-
ring Access Level 2 only.
This operation will be signalled by:
Ø
the
Disable Extinguish.
LED (On);
Ø
the
Disab.
LED (On).
The
OUTS BYPASS
event, and respective details will
be recorded in the logger (
EXTING.MODULE 1
or
EXTING.MODULE 1
).
If you disable the Extinguishment Module during
Standby status, it will be unable to operate in the event
of an Alarm.
If you disable the Extinguishment Module during the
Pre-extinguishment Phase, the Pre-extinguishment
Phase will be interrupted until the Extinguishment Mo-
dule is re-enabled. The Pre-extinguishment Phase will
re-start from the point of interruption.
If you disable the Extinguishment Module during the
Extinguishment Phase, the latter will be interrupted.
n
Disable Manual Extinguish. button
This button will allow you to Disable/Enable manual ac-
tivation of the Extinguishment Module.
+
The
Disable Manual Extinguish.
button can be
used during Access Level 2 only.
This operation will be signalled by:
Ø
the
Disable Manual Extinguish.
LED (On);
Ø
the
Disab.
LED (On).
USER’S INSTRUCTIONS
5
Summary of Contents for J408
Page 1: ...INSTALLATION MANUAL CONVENTIONAL F I R E PA N E L S 424 408...
Page 17: ...IDENTIFICATION OF PARTS 17 C N O N C 36 35 b...
Page 29: ...USER S INSTRUCTIONS CONVENTIONAL F I R E PA N E L S 424 408...
Page 52: ...44 Conventional Fire Panels J424 J408...
Page 61: ...QUICK GUIDE 53...
Page 62: ...54 Conventional Fire Panels J424 J408...
Page 63: ...QUICK GUIDE 55...