background image

n

Extinguishment Module Terminals

EM Supervised/Bypassable

Manual

Extingui-

shment Input

This Input is for manual activation of the Extingui-

shment devices.

Standby status of this Input can be either

Normally

Open

(at default) or

Normally Closed

(refer to “Manual

Extinguishment Input” under “Enrolling: Extinguishment

Modules” in the “PROGRAMMING FROM PC”)

Operating principles:

Ø

the Control panel will consider the EM Input OPEN

when a 3.900 ohm resistance is applied to its [+] and

[–] terminals;

Ø

the Control panel will consider the EM Input CLOSED

when one or more (up to 10) 680 ohm resistor is/are

applied in parallel to the 3.900 ohm resistance.

The EM Input will activate when inverse conditions to its

standby conditions occur.

Activation of the EM Input will start the Pre-Extingui-

shment Time.

Activation of the EM Input will be indicated by Glowing

on the

ON Manual Ext.

LED.

Short-circuit or power supply interruption on the EM

Input will be indicated by fast blinking on the

Fault Ma-

nual Ext.

LED.

The EM input can be disabled by means of the

Disable

Manual Extinguish.

key.

Disablement of this Input will be indicated by Glowing

on the

Disable Manual Extinguish.

LED.

IE Supervised Inhibit Extinguishment Input

This Input is for the inhibition of Extinguishment devices.

The standby status of this Input can be either

Normally

Open

(at default) or

Normally Closed

(refer to “Disable

Extinguishment Input” under “Enrolling: Extinguishment

Modules” in the “PROGRAMMING FROM A PC”).

Operating principles:

Ø

the Control panel will consider the IE Input OPEN

when a 3.900 ohm resistor is applied between its [+]

and [–] terminals;

Ø

the Control panel will consider the IE Input CLOSED

when one or more (up to 10) 680 ohm resistor is/are

applied in parallel to the 3.900 ohm resistor.

The IE Input will activate when the inverse conditions to

its programmed standby conditions occur.

Activation of the IE Input will start the Pre-Extingui-

shment Time.

If the IE Input is active when Extinguishment conditions

occur, the Control panel will activate the PR Output

(Pre-Extinguishment) but WILL NOT START the

Pre-Extinguishment Time.

If the IE Input activates during the Pre-Extinguishment

phase, the Control panel will stop Pre-Extinguishment

Time. The Control panel will restart the Pre-Extingui-

shment Time when the IE Input restores to standby.

If the IE Input is activated during the Extinguishment

phase, the Control panel will reset the EV Output (Elec-

trovalve). The Control panel will re-activate the EV Out-

put when the IE Input restores to standby.

Activation of the IE Input will be indicated by Glowing on

the

ON Disab. Ext.

LED.

Short-circuit or power supply interruption on the IE Input will

be indicated by fast blinking on the

Fault Disab. Ext.

LED.

PS Supervised Pressure Switch Input

This Input is for the Pressure Switch connection.

Standby status of this Input can be either

Normally

Open

(at default) or

Normally Closed

(refer to “Pres-

sure Switch Input” under “Enrolling: Extinguishment

Modules” in the “PROGRAMMING FROM A PC”).

Ø

the Control panel will consider the PS Input OPEN

when a 3.900 ohm resistor is applied across its [+]

and [–] terminals;

Ø

the Control panel will consider the PS Input CLOSED

when one or more (up to 10) 680 ohm resistor is/are

applied in parallel to the 3.900 ohm resistor.

The PS Input will activate when the inverse conditions

to its programmed standby conditions occur.

Activation of the PS Input will be indicated by Glowing

on the

ON Pres. Switch

LED.

Short-circuit or power supply interruption on the PS

Input will be indicated by fast blinking on the

Fault Pres.

Switch

LED.

If the Pressure Switch Input of an Extinguishment Modu-

le is activated during or after the Extinguishment phase,

and the respective

Extinguishment Confirmation

op-

tion is ENABLED (refer to “Pressure Switch Input” under

“Enrolling: Extinguishment Modules” in the “PRO-

GRAMMING FROM A PC” section), the Control panel

will activate the AE Output (Activated Extinguishment).

EV Supervised Electrovalve Output

This Output is for the Electrovalve connection.

Operating principles:

Ø

in Standby status, the EV terminals will be OPEN;

Ø

during the Extinguishment phase, the EV terminals

will be CLOSED.

Activation of the EV Output will be indicated by Glowing

on the

ON Electrovalve

LED.

Short-circuit or power supply interruption on the EV

Output will be indicated by fast blinking on the

Fault

Electrovalve

LED.

Up to 5 A can circulate on the EV Output.

24P Power Boost Input

This Input is for the Power boost required by the devi-

ces connected to Outputs PR and AE.

Wiring instructions:

Connect the [+] and [–] terminals of this Input to the [+]

and [–] terminals

47

of the Switching Power Supply.

PR Supervised Pre-Extinguishment Output

This Output is for Pre-Extinguishment signalling.

Operating principles

Ø

Standby status: negative pull-down to 0 V on the [+]

terminal; positive pull-up to 27.6 V on the [–] terminal.

Ø

Pre-Extinguishment phase: positive pull-up to 27.6 V

on the [+] terminal; negative pull-down to 0 V on the

[–] terminal.

Activation of the PR Output will be indicated by Glowing

on the

ON Pre Ext.

LED.

Short-circuit or power supply interruption on the PR Input

will be indicated by fast blinking on the

Fault Pre Ext.

LED.

Up to 1 A can circulate on the PR Output.

28

Conventional Fire Panels

J424/J408

Summary of Contents for J408

Page 1: ...INSTALLATION MANUAL CONVENTIONAL F I R E PA N E L S 424 408...

Page 2: ...with the instructions described in this manual and in compliance with the local laws and bylaws in force The J424 and J408 Control panels comply with the essential requirements of standards EN54 2 EN5...

Page 3: ...dule for J424 and J400 REP ONLY 24 Installing Repeaters 25 Installing the Control panel 25 Description of the Terminals 25 Main Board and Expander Board terminals 25 Main Board Terminals 26 Extinguish...

Page 4: ...THE PANEL 45 Accessing the Programming session 45 Exiting the Programming Session 45 The ZONES Programming Phase 46 The TIMES Programming Phase 46 The OUTPUTS Programming Phase 47 The PANEL Programmin...

Page 5: ...board which will activate the fire warning and fire control devi ces and generate signalling on the Expander Control board The J424 accepts TWO J400 EXP8 Expander Modules Kits J400 EXT Extinguishment...

Page 6: ...g features Pre alarm If a zone generates an alarm during Day Mode Night Mode LED OFF the Control panel will start the Pre alarm Time This status will be signalled by a slow intermittent beep blinking...

Page 7: ...a long pause lasting 5 seconds glowing on the Silence LED Silence status will be held until the Silence key is pres sed again or if the Control panel is operating in Night Mode until the programmed Ni...

Page 8: ...shment and Pressure Switch control These Supervised inputs must pull down to 0 V negative with a 3 900 ohm resi stance during standby status In the event of interrup tion or short circuit these inputs...

Page 9: ...ound Fast blinking indicates a Voltage leakage to Earth IMPORTANT Check wiring insulation Periph Fast blinking indicates communication trouble with peripherals Red Mains Fast blinking indicates Mains...

Page 10: ...lt Test z9 z13 z12 z16 z11 z15 z10 z14 Zone Alarm Zone Alarm Disabled Fult Test Disabled Fult Test z17 z21 z20 z24 z19 z23 z18 z22 Zone Alarm Zone Alarm 424 Extinguish Automatic Extinguish Manual Exti...

Page 11: ...z6 Zone Alarm Zone Alarm 24V 24R Alarm c h M S A C M B L I J 4 0 0 R E P a 0 Esc Enter Fault Logic Unit Battery Ground Mains Periph Pre al Disab Mains Telecom Test Silence Night Mode Ack Evac Disab Fa...

Page 12: ...C N O N C 6 7 8 10 11 26 27 28 29 30 31 9 Figure 2 Maximum configuration of the J424 Control panel...

Page 13: ...M NO NC C TROUBLE NO NC C NAC1 NAC2 Z5 R5 13 14 15 Z6 R6 16 17 18 Z7 R7 19 20 21 Z8 R8 22 23 24 26 24R OC RS485 V 24 PRG B016 GAS EF R AC N FG V GND B L B GND V AC L F 3 1 5 A 2 5 V F 6 3 A 2 5 V 20 1...

Page 14: ...screws 5 Keyswitch Access Level 2 6 Display module accessory item 7 Expander Control board LEDs and keys of Expander no 2 accessory item for J424 8 Flat cable accessory item for J424 for the Expander...

Page 15: ...ain board connection 27 Flat cable accessory item for the Extingui shment Module to Main board connection 28 Extinguishment Module no 1 accessory item P Description 29 Flat cable accessory item for th...

Page 16: ...tion holes 34 Chased cable conduit entry 35 RS485 Interface 36 Soldered Earthing screw 16 Conventional Fire Panels J424 J408 a 33 33 34 33 33 Figure 4 Maximum configuration of the J400 REP Repeater a...

Page 17: ...IDENTIFICATION OF PARTS 17 C N O N C 36 35 b...

Page 18: ...408 F 2A 250V J424 F 3 15A 250V 56 Jack for Extinguishment Module nr 2 or the Display Module 57 Microprocessor 58 Jack for the Main board or Display Module 59 Reserved Jumper DO NOT REMOVE 60 Battery...

Page 19: ...Jack for the Expander Control board of zo nes 9 to 16 81 Jack for the Expander Control board of zo nes 1 to 8 82 Display Programming Jumper Programming Disabled oo Programming Enabled 83 Jack for the...

Page 20: ...used to refresh the Pre Alarm Time or trigger an Alarm For all persons on the premises If this key is pressed for over 5 seconds during Pre Alarm Time the system will generate an alarm For Key and PI...

Page 21: ...J408 The J408 can house 1 Extinguishment Module po sitioned as shown on page 14 see part no 28 To install the Extinguishment Module work through the following steps 1 Remove the screws 4 and open the...

Page 22: ...xpander Module Kit mount the Expander Module 21 and the Expander Control board 10 as per Figure 11a if you are installing TWO Expander Module Kits mount Expander Module nr 1 21 and the Expander Contro...

Page 23: ...d Install the Expan der Module as follows 1 Fit the short spacers 99 onto the soldered screws 98 as shown in Fig 10d 2 Using the nuts secure the Expander Control Board in position as per Fig 10e 3 Usi...

Page 24: ...hment Modules are installed connect the Display Module directly to the Main Board via the jacks 75 and 63 respectively as per Fig 13a J424 if ONE Extinguishment Modules is instal led connect the Displ...

Page 25: ...pipes and electrical wiring be fore drilling 3 If necessary using a hammer or similar tool remo ve the surface conduit wire knockouts 1 The cable conduit union with the case must be se cured by HB Fl...

Page 26: ...at Output of the zone concerned Repeat Outputs will hold standby status for the pro grammed Silence Time If Alarm conditions are present when the Silence Time expires the Repeat Output will re activa...

Page 27: ...when the Silence Time expires the ALARM Output will re activate Up to 5 A can circulate on the ALARM Output The ALARM Output accepts devices that operate within SELV limits ONLY TROUBLE Silenceable T...

Page 28: ...by Activation of the IE Input will be indicated by Glowing on the ON Disab Ext LED Short circuit or power supply interruption on the IE Input will be indicated by fast blinking on the Fault Disab Ext...

Page 29: ...USER S INSTRUCTIONS CONVENTIONAL F I R E PA N E L S 424 408...

Page 30: ...ignal 0 2 second beep followed by a 0 2 second pause a ALARM message similar to the following ALARM ON ZONE 01 Warehouse The top line will show the number of the zone that trig gered the ALARM the bot...

Page 31: ...he Electro valve Output is shorted or open The Extinguishment devices CANNOT be activated Fault Pre Ext Fast blink FAULT ON EXT 1 PRE EXT OUTPUT The Pre extinguishment Out put is shorted or open The P...

Page 32: ...LEAST 5 seconds To activate an Alarm when the Control panel is in Standby status 1 Enter the PIN Code or turn the key in the Keyswitch Access Level 2 2 Press the Ack Evac button for at least 5 se cond...

Page 33: ...the Inhibit Extinguishment call points to standby status the Extinguishment phase will restart immediately n Manual Extinguishment The Extinguishment Module can be activated from ma nual call points...

Page 34: ...t Mod nr shorted or open EV OUT RESTORE Extinguishment Mod nr EV Output of Extinguish Mod nr has been restored EVACUATE None Evacuation command executed GND FAULT REST None Control panel ground fault...

Page 35: ...larm by pressing the Reset button The Silence and Reset buttons can be used du ring Access Level 2 only Pre al On glowing indicates PREALARM status The Control panel will generate an ALARM when the pr...

Page 36: ...been silenced by means of the Silen ce button To re enable the devices press the Silence button again Silenced devices will be re enabled auto matically in the event of a new ALARM The Silence button...

Page 37: ...onnect when the detector is attached to its base and disconnect when it is removed terminal L the negative power terminal of the de tector EOL resistor 109 to be connected between termi nal L1 and ter...

Page 38: ...sistor in series to a Call points with zero ohm contact resistance as shown in Figu re 15 111 A IMQ SECURITY SYSTEMS certification applies ONLY when Call point priority option is ENABLED n Connecting...

Page 39: ...Outputs under PROGRAMMING FROM A PC The wiring diagram in Figure 18 shows two warning lamps and the flasher of an outdoor signalling device STROBE terminals connected to NAC2 and two fire bells and th...

Page 40: ...ventional Fire Panels J424 J408 24V RS485 24V RS485 24V RS485 24V RS485 24V RS485 Main board Repeater panel Repeater panel Repeater panel Repeater panel Connect to the earth conductor Figure 17 Wiring...

Page 41: ...Module is unable to supply the current draw of the PR and AE Outputs therefore it will be necessary to connect the 24P input to the Switching Power Supply of the Control panel or to an external Power...

Page 42: ...tery LED Memory Dynamic Test The Dynamic Test monitors the opera ting capacity of the batteries In the event of a Failed Test result batteries do not meet the Test require ments The Battery LED will t...

Page 43: ...ccordance with the battery tempera ture that the output voltage of the Switching Power Supply will be based on 5 Using the trimmer 51 adjust the voltage on the ter minal board 52 to the required value...

Page 44: ...the Probe tempe rature is 22 C the Output Voltage of the Switching Power Supply must be set at 27 4 V 10 5 0 5 10 15 20 25 30 35 40 45 50 26 0 27 0 28 0 29 0 VOLTAGE V TEMPERATURE C a 27 4 22 Figure...

Page 45: ...label will identify the Expan der Module in all the operations it is involved in Enrolling Extinguishment Modules The Extinguishment Modules page will allow you to enrol and set up Extinguishment Modu...

Page 46: ...y status of the Disable Extinguishment Input IE terminals Normally Closed If this option is DISABLED at Defa ult there must be a 3900 ohm resistance across the and terminals of the IE input during Sta...

Page 47: ...eld and the value pro grammed in the Standby Auto Alarm field Standby Auto Alarm If the Call point Priority option has been ENABLED the Control panel will consider the Zone ALARM status when the volta...

Page 48: ...that will override the Pre Alarm Time This interval will allow users time to investigate fire alerts It will be applied when the Ack Evac key is pressed for less than 5 seconds at Access Level 2 Keys...

Page 49: ...the assigned events oc curs and will Reset when ALL the assigned events end n DL Output The Dialler Output DL terminal will activate when its programmed delay expires The delay countdown will start wh...

Page 50: ...eset that the system will ignore the Zone Status Accepted values 0 through 5 seconds in steps of 1 se cond Default setting 2 seconds n User Code The 4 digit User Code will allow access to Level 2 of t...

Page 51: ...rol panel type from the Panel menu select the respective firmware release from the Firmware menu click OK 6 To download a specific page click the DWLoad button on the page in question To Download seve...

Page 52: ...44 Conventional Fire Panels J424 J408...

Page 53: ...s and insert the tabs of the Programming Overlay into the Zone la bel slots as shown in Figure 28 5 Press the Next Phase key 9 then select the group of parameters that you want to program ZONES TIMES...

Page 54: ...ALARM LCD 1 Zone 5 Zone 5 Power 1 Zone 5 Rep 1 Zone 2 Zone 2 Test Exting 2 LCD 2 Zone 6 Zone 6 Power 2 Zone 6 Rep 2 Zone 3 Zone 3 Expander 1 Zone 3 LCD 3 Zone 7 Zone 7 Power 3 Zone 7 Rep 3 Zone 4 Zone...

Page 55: ...c 640 sec MODULES VARIOUS PANEL OUTPUTS TIMES ZONES Refresh time Day mode Reset time Pre alarm Zone 1 Zone 1 Exting 1 Fault ALARM LCD 1 Zone 5 Zone 5 Power 1 Zone 5 Rep 1 Zone 2 Zone 2 Exting 2 Test L...

Page 56: ...last digit indi cating that the setting has been accepted Wrong entries will be signalled by an audible error si gnal n Mains Off Delay Key LED 8 The LED will go On to indicate that the system is rea...

Page 57: ...itten in negative type LCD 1 LCD Module nr 1 LCD 2 LCD Module nr 2 LCD 3 LCD Module nr 3 LCD 4 LCD Module nr 4 Rep 1 Repeater panel nr 1 Rep 2 Repeater panel nr 2 Rep 3 Repeater panel nr 3 Rep 4 Repea...

Page 58: ...anel LCD Module Address Zone Descriptions Strings Update Date Format To access the programming phase insert the LCD Mo dule jumper 82 the module will provide the Main menu n Programming Mode Address P...

Page 59: ...ain Board J408 4 4 Zone Control Board 0 1 0 27 Main Board J408 8 and J424 8 Zone Control Board 0 13 0 3 J400 EXT Extinguishment Module 0 04 0 21 J400 EXP8 Expander Module 0 06 0 5 J400 LCD Module 0 08...

Page 60: ...6 on terminal negative pull down to 0 V on terminal 27 6 1 4 8 ZONE MAIN BOARD RS485 RS485 Serial Port Positive pull up to 27 6 V on 24V terminal Negative pull down to 0 V on M terminal data on and te...

Page 61: ...QUICK GUIDE 53...

Page 62: ...54 Conventional Fire Panels J424 J408...

Page 63: ...QUICK GUIDE 55...

Page 64: ...BENTEL SECURITY s r l Zona Ind S Scolastica 64013 Corropoli TE ITALY Tel 39 0861 839060 Fax 39 0861 839065 e mail info bentelsecurity com http www bentelsecurity com ISTISBLEJ408 8 0 0 201204 V8...

Reviews: