Fire alarm systems
Enclosed
addressable manual
call point
3339
Attractive design compliant with EN54-11. IP rating IP56
Test key for routine testing without breaking the glass element
Protection against accidental operation
General
The call point has an attractive design
compliant with EN54-11, and is surface
mounted in the supplied red back box. It has
a clip retained front cover that makes it easy
to replace the glass element and adds
security since the clips are concealed. The
frangible element is a glass element with a
protective plastic film. To operate the call
point, the glass element is pressed until it is
broken. This will activate the built-in micro
switch, which will generate a fire alarm in
the c.i.e.
Test / cover removal key
Routine testing is made with a supplied test
key, without breaking the glass element.
Inserting the test key simulates the breaking
of the glass element. The call point will be
reset when the test key is pulled out. The
test key is also used to release the security
clips for the front cover removal.
Protective cover
To protect the call point against accidental
operation, a transparent polycarbonate flap
has to be lifted to get access to the glass
element.
Encapsulated circuit
All electronics are encapsulated. Only the
terminal block is accessible from the rear.
Mounted in the supplied red back box with
the tightening gasket on place (see the
opposite page), the IP rating is IP56.
LED indicator
An LED on the front cover indicates fire
alarm generated by the call point.
Furthermore it can via Win512 / Win128 be
set to be flashing or non-flashing:
Flashing LED
: Is indicating that the c.i.e. is
communicating with the call point. When
the call point is operated the LED will be
turned on continuously.
Non-flashing LED
: The LED is turned off
until the call point is operated and the LED
will be turned on continuously.
Connections / Settings
The COM loop is connected directly to the
call point via a 4-way terminal block. For
COM loop address setting is the address
setting tool 3314 used. 3314 is also used to
set the call point type and the LED mode:
NORMAL
mode: (EBL512 SW
version >2.0 / EBL128). M.c.p. type
3339. (Flashing or non-flashing LED is
set via Win512 / Win128.)
2330
mode: M.c.p. type 2339, flashing
LED.
NOTE!
This mode is only used
for backwards compatibility.
2312
mode: M.c.p. type 2339, non-
flashing LED.
NOTE!
This mode is
only used for backwards compatibility.
Two flying leads (wires) are connected to
the terminal block and shall be used for the
address setting tool's connection cable. The
wires shall be disconnected before the COM
loop wires are connected.
Product applications
Used in the systems EBL512 / 128 / 1000 /
2000 and is intended for indoor use in
premises where IP56 rating is required.