Product Leaflet
Date of issue
Revision / Date of revision
MEW00098
2005-04-14
3 / 2010-03-03
Type numbers
3339
Enclosed addressable manual call point
2347
Replacement glass (10 pcs.)
2348
Replacement polycarbonate flap (10 pcs.)
Left: The supplied back box. Mounting lug hole
Ø = 5 mm. Right: The call point backside view
(note the black tightening gasket).
Technical data
Voltage (V DC)
allowed
nominal
12-30
24
Current consumption at nom. volt.
from COM loop (mA)
quiescent / active
2 / 5
Ambient temperature (
C)
operating / storage
-10 to +55 / -40 to +85
Ingress Protection rating
IP56
Weight (g)
242
Construction / Colour
ABS / Red (ISO 3864)
Approvals
10 EC Certificate no. 0786-CPD-20918, EN54-11
Flying leads to be
connected to the
Address setting tool
3314 during mode and
address setting
59mm
1)
1)
66mm with the
polycarbonate flap.
How to perform routine testing
Insert the test key into the hole in the front cover.
The glass position will change, indicating
that the call point is operated.
Wait until the LED is turned on, i.e. fire alarm
is activated in the c.i.e.
Pull out the test key and the glass position will
return to normal.
The LED will be turned off when the fire alarm
is reset in the c.i.e.
How to replace the glass element
Lift the polycarbonate flap.
Release the front cover security clips with the test key.
Lift and remove the front cover.
Remove the broken glass element.
Place the top edge of the replacement glass element
against the micro switch plunger and push it upwards
until the glass element is in correct position.
Put back the front cover and lower the polycarbonate flap.
Perform a routine test (see left).