background image

 

All technical features and data are subject to changes without notice, resulting from continuous development and improvement. 

Product Leaflet 

Date of issue 

Revision / Date of revision  

MEW00098 

2005-04-14 

3 / 2010-03-03 

 

Type numbers 

3339 

Enclosed addressable manual call point 

2347 

Replacement glass (10 pcs.) 

2348 

Replacement polycarbonate flap (10 pcs.) 

    

 

 

 

Left:  The supplied back box.  Mounting lug hole  
Ø = 5 mm.    Right:  The call point backside view  
(note the black tightening gasket). 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Technical data 

Voltage (V DC) 

 

  allowed  
  nominal 

 

 

12-30 

 

24 

Current  consumption  at  nom.  volt. 
from COM loop (mA) 

  quiescent / active 

 
 

2 / 5 

Ambient temperature (

C) 

  operating / storage 

 

-10 to +55 / -40 to +85 

Ingress Protection rating 

IP56 

Weight (g) 

242  

Construction / Colour 

ABS / Red (ISO 3864) 

Approvals 

  10  EC Certificate no. 0786-CPD-20918, EN54-11 

 

Flying leads to be 
connected to the 
Address setting tool 
3314 during mode and 
address setting 

59mm 

1) 

1)

 66mm with the 

polycarbonate flap.

 

How to perform routine testing 

 Insert the test key into the hole in the front cover. 

    The glass position will change, indicating  
    that the call point is operated. 
    Wait until the LED is turned on, i.e. fire alarm 
    is activated in the c.i.e. 

 Pull out the test key and the glass position will 

    return to normal. 
    The LED will be turned off when the fire alarm 
    is reset in the c.i.e. 

How to replace the glass element 

Lift the polycarbonate flap. 

 Release the front cover security clips with the test key.   

 Lift and remove the front cover. 

    Remove the broken glass element. 
    Place the top edge of the replacement glass element 
    against the micro switch plunger and push it upwards 
    until the glass element is in correct position. 

Put back the front cover and lower the polycarbonate flap. 
Perform a routine test (see left). 