Automatic measurement (Vo/c, Is/c, R
ISO
)
Attention:
Maximum DC power: P ≤ 10 kW, Vo/c ≤ 1000 V, Is/c ≤ 15 A
Do not make measurements at PV strings which are connected in parallel!
1. Connect the BENNING PV 1-1 to the PV generator as shown, by means of
the enclosed PV safety measuring leads and the red 4 mm safety test lead.
2. The open-circuit voltage (Vo/c) is automatically displayed.
3. In case of reversed polarity of the DC voltage, the symbol
is displayed and
the measurement will be blocked.
4. Use the
V
ISO
-key to select 250 V, 500 V or 1000 V insulation test voltage.
5. Press the
Auto
-key to automatically measure short-circuit current (I
S/C
) and
insulatio
n resistance (R
ISO
).
Note:
The red 4 mm safety measuring lead is required for the insulation resistance
measurement.
500V
250V
1000V
PV 1-1
DIN EN 62446 (VDE 0126-23), ÖVE/ÖNORM EN 62446
Auto
Ω
NULL
R
PE
V
ISO
ON/OFF
press 2 sec.
NULL
red
red
black
Null balance of the measuring leads, resistance (R
PE
)
1. Connect the safety measuring leads to the red and black 4 mm test sockets of
the BENNING PV 1-1.
2. Hold the test probe tips together or connect together using the supplied
crocodile clips.
3. Press and hold the
Ω
NULL
-key until an acoustic signal sounds and the
Ω
NULL
-symbol
is displayed.
4. The Null-value is stored when unit is switched off.
5. To disable, press
Ω
NULL
-key until the
Ω
NULL
-symbol is removed from LC display.
Note:
Max. measuring lead resistance: 10 Ohm
500V
250V
1000V
PV 1-1
DIN EN 62446 (VDE 0126-23), ÖVE/ÖNORM EN 62446
Auto
Ω
NULL
R
PE
V
ISO
ON/OFF
press 2 sec.
NULL
red
black
Protective conductor resistance (R
PE
)
1. Connect the 4 mm safety measuring leads as shown.
2. To make a single measurement (2 sec.), press and release the
R
PE
-key.
3. To make a continuous measurement, press and hold the
R
PE
-key until the symbol
is displayed continuously.
4. Press the
R
PE
-key to terminate the continuous measurement.
500V
250V
1000V
PV 1-1
DIN EN 62446 (VDE 0126-23), ÖVE/ÖNORM EN 62446
Auto
Ω
NULL
R
PE
V
ISO
ON/OFF
press 2 sec.
NULL
R
PE
red
black
AC/DC current measurement
1. Disconnect all safety measuring leads from the BENNING PV 1-1.
2. Connect the BENNING CC 3 (option) current clamp adapter to the 4 mm test
sockets.
3. Select the 40 A range on the BENNING CC 3.
4. Press the null balance key (ZERO) of the BENNING CC 3 for approx. 2
seconds.
5. Press the
V
ISO
-key on the BENNING PV 1-1 until the symbol
is
displayed.
6. The AC/DC current can be measured in single-wire live conductor.
500V
250V
1000V
PV 1-1
DIN EN 62446 (VDE 0126-23), ÖVE/ÖNORM EN 62446
Auto
Ω
NULL
R
PE
V
ISO
ON/OFF
press 2 sec.
+
40A
: 10mV/
A
300A
: 1mV/
A
BA
TT
LO
W
PW
R
ON
BENNING CC
3
ZERO A
OFF
40A
300A
CAT. III 600V
300A
NULL
AC/DC voltage measurement
1. Disconnect the PV safety measuring leads from the BENNING PV 1-1.
2. Connect the red and black safety measuring lead as pictured.
3. The BENNING PV 1-1 automatically measures the AC/DC voltage at the
measuring probes.
4. The polarity of the DC voltage is displayed by “+/-“. In case of AC voltage,
“+/-“ will be displayed alternately.
500V
250V
1000V
PV 1-1
DIN EN 62446 (VDE 0126-23), ÖVE/ÖNORM EN 62446
Auto
Ω
NULL
R
PE
V
ISO
ON/OFF
press 2 sec.
NULL
c
Max.
P ≤ 10 kW
Vo/c ≤ 1000 V
Is/c ≤ 15 A
Max.
CAT III 400 V
Option:
40 m measuring leads
BENNING TA 5
part no. 044039
Option:
BENNING CC 3
part no. 044038
PV-module/ -string