STEP ONE
( Selecting Site )
Before installing your new lift, check the following.
1. LIFT LOCATION: Always use architects plans when
available. Check layout dimension against floorplan
requirements making sure that adequate space is
available.
2. OVERHEAD OBSTRUCTIONS: The area where the lift
will be located should be free of overhead obstructions
such as heaters, building supports, electrical lines etc.
3. DEFECTIVE CONCRETE: Visually inspect the site
where the lift is to be installed and check for cracked or
defective concrete.
4.
OPERATING TEMPERATURE.
Operate lift only
between temperatures of 41° -104° F.
5. Lift is designed for
INDOOR INSTALLATION ONLY.
STEP TWO
( Floor Requirements )
This lift must be installed on a solid level concrete
floor with no more than 3-degrees of slope. Failure
to do so could cause personal injury or death.
A level floor is suggested for proper installation.
I
f a floor
is of questionable slope, consider a survey of the site
and/or the possibility of pouring a new level concrete slab.
DO NOT install this lift on any asphalt surface or any
surface other than concrete.
DO NOT install this lift on expansion seams or on
cracked or defective concrete.
DO NOT install this lift on a second /elevated floor
without first consulting building architect.
DO NOT install this lift outdoors unless special
consideration has been made to protect the
power unit from inclimate weather conditions.
CONCRETE SPECIFICATIONS
LIFT
CONCRETE
MODEL
REQUIREMENT
7,000 Lb. Models
4” Min. Thickness / 3000 PSI
10,000 Lb. Models
4” Min. Thickness / 3000 PSI
12,000 Lb. Models
6” Min. Thickness / 3000 PSI
15,000 Lb. Models
6” Min. Thickness / 3000 PSI
18,000 Lb. Models
8” Min. Thickness / 3000 PSI
Rotary Hammer Drill Or Similar
3/4" Masonry Bit
Hammer
4 Foot Level
Open-End Wrench Set: 7/16" - 1-1/8"
Socket And Ratchet Set: 7/16" - 1-1/8"
Hex-Key / Allen Wrench Set
Medium Crescent Wrench
Medium Pipe Wrench
Crow Bar For Shim Installation
Chalk Line
Medium Flat Screwdriver
Tape Measure: 25 Foot Minimum
Needle Nose Pliers
IMPORTANT NOTICE
These instructions must be followed to insure proper installation and operation of your lift. Failure to
comply with these instructions can result in serious bodily harm and void product warranty.
Manufacturer will assume no liability for loss or damage of any kind, expressed or implied resulting
from improper installation or use of this product.
PLEASE READ ENTIRE MANUAL PRIOR TO INSTALLATION.
NOTE
All models MUST be installed on 3000 PSI
concrete only conformIng to the minimum
requirements shown above. New concrete must be
adequately cured by at least 28 days minimum.