Modbus Register Map
98
PEM735_D00084_00_M_XXEN/02.2015
10.3 Pulse counter
The value stored in the registers
0350…0360
is 1000 times the actual value, i.e. the
register value must be divided by 1000 for an accurate measuring value.
Tab. 10.5: Pulse counter
10.4 Fundamental measurements (Power quality)
The registers
0400…0456
contain measured values which relate to the fundamen-
tal
f
0
.
Register
Property
Description
Format
0350
RW
Pulse counter DI1
UINT32
0352
RW
Pulse counter DI2
UINT32
0354
RW
Pulse counter DI3
UINT32
0356
RW
Pulse counter DI4
UINT32
0358
RW
Pulse counter DI5
UINT32
0360
RW
Pulse counter DI6
UINT32
Register Property
Description
Format
Unit
0400
RO
U
L1(f0)
1)
Float
V
0402
RO
U
L2 (f0)
1)
Float
V
0404
RO
U
L3 (f0)
1)
Float
V
0406
RO
Ø
U
LN (f0)
1)
Float
V
0408
RO
U
L1L2 (f0)
2)
Float
V
0410
RO
U
L2L3 (f0)
2)
Float
V
0412
RO
U
L3L1 (f0)
2)
Float
V
0414
RO
Ø
U
LL (f0)
2)
Float
V
0416
RO
I
1(f0)
Float
A
0418
RO
I
2 (f0)
Float
A
0420
RO
I
3( f0)
Float
A
0422
RO
Ø
I
(f0)
Float
A
Summary of Contents for LINETRAXX PEM575 Series
Page 8: ......
Page 12: ...Making effective use of this document 12 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 28: ...Installation and connection 28 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 62: ...Application inputs and outputs 62 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 82: ...Logging 82 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 88: ...Power Quality 88 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 162: ...Modbus Register Map 162 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 166: ...Technical data 166 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 170: ...INDEX 170 PEM575_D00016_00_M_XXEN 04 2015 ...
Page 171: ......