![Bender LINETRAXX PEM575 Series Manual Download Page 109](http://html.mh-extra.com/html/bender/linetraxx-pem575-series/linetraxx-pem575-series_manual_2731698109.webp)
Modbus Register Map
109
PEM735_D00084_00_M_XXEN/02.2015
Tab. 10.11: Maximum values per demand period
1)
Register 1424
is valid only if the device is equipped with the I
4
input, otherwise it is
reserved.
1450
RO
λ
1 max
INT32
x 1,000
1452
RO
λ
2 max
INT32
x 1,000
1454
RO
λ
3 max
INT32
x 1,000
1456
RO
λ
ges max
INT32
x 1,000
1458
RO
f
max
INT32
x 100, Hz
1460
RO
max. voltage unbalance
INT32
x 1,000
1462
RO
max. current unbalance
INT32
x 1,000
1464
RO
THD
UL1 max
INT32
x 10,000
1466
RO
THD
UL2 max
INT32
x 10,000
1468
RO
THD
UL3 max
INT32
x 10,000
1470
RO
THD
I1 max
INT32
x 10,000
1472
RO
THD
I2 max
INT32
x 10,000
1474
RO
THD
I3 max
INT32
x 10,000
Register Property
Description
Format Unit
Summary of Contents for LINETRAXX PEM575 Series
Page 8: ......
Page 12: ...Making effective use of this document 12 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 28: ...Installation and connection 28 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 62: ...Application inputs and outputs 62 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 82: ...Logging 82 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 88: ...Power Quality 88 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 162: ...Modbus Register Map 162 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 166: ...Technical data 166 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 170: ...INDEX 170 PEM575_D00016_00_M_XXEN 04 2015 ...
Page 171: ......