Modbus Register Map
143
PEM735_D00084_00_M_XXEN/02.2015
Waveform recorder data structure (WFR log)
The waveform recorder data contains the values of the secondary side. The voltage
data returned is 10 times of the actual secondary voltage and the current data is
1,000 times of the actual secondary current. The voltage and current values of the
primary side are calculated as follows:
U
primary
=
U
secondary
x voltage transformer transformation ratio/10
I
primary
=
I
secondary
x CT transformation ratio/1,000
Tab. 10.36: Waveform recorder data structure
N
#
= number of sample (1…N)
Offset
Property
Description
Format Range/options
+ 0
RO
Trigger mode
UINT16
0*= disabled
1 = manual
2 = Setpoint
3 = Sag/swell
+ 1
RO
HiWord: Year
UINT16
0…99 (year- 2000)
RO
LoWord: month
1…12
+ 2
RO
HiWord: Date: Day
UINT16
1…31
RO
LoWord: Hour
1…23
+ 3
RO
HiWord: Minute
UINT16
0…59
RO
LoWord: Second
0…59
+ 4
RO
Millisecond
UINT16
0…999
+ 5…N+4
RO
U
L1
of sample N
#
UINT16
x 10, V
N+5…2N+4
RO
U
L2
of sample N
#
UINT16
x 10, V
2N+5…3N+4
RO
U
L3
of sample N
#
UINT16
x 10, V
3N+5…4N+4
RO
I
1
of sample N
#
UINT16
x 1,000, A
4N+5…5N+4
RO
I
2
of sample N
#
UINT16
x 1,000, A
5N+5…6N+4
RO
I
3
of sample N
#
UINT16
x 1,000, A
Summary of Contents for LINETRAXX PEM575 Series
Page 8: ......
Page 12: ...Making effective use of this document 12 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 28: ...Installation and connection 28 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 62: ...Application inputs and outputs 62 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 82: ...Logging 82 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 88: ...Power Quality 88 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 162: ...Modbus Register Map 162 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 166: ...Technical data 166 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 170: ...INDEX 170 PEM575_D00016_00_M_XXEN 04 2015 ...
Page 171: ......