Power Quality
86
PEM735_D00084_00_M_XXEN/02.2015
The following set-up parameters are supported:
1. Enable undervoltage/overvoltage
disabled/enabled
2. Overvoltage limit
1.05…2 x
U
nom
3. Undervoltage limit
0.11…0.95
U
nom
4. Trigger 1/Trigger 2 for undervoltage/overvoltageDO1…3 /DR 1…16/
WFR1…2/alarm e-mail
9.5 Transient events setpoint
The universal measuring device can detect transient events in the event of voltage
disturbances. The programming of the transient setpoints is only supported by the
communications interface (
registers 6178… 6181
). The following set-up parame-
ters are supported:
1. Enable transient events
disabled/enabled
2. Transient events limit
0.05…1.00 x
U
n
3. Trigger 1/Trigger 2 for transient events
DO1…3/DR 1…16/
WFR1…2/alarm e-mail
9.6 Time synchronisation
The universal measuring device provides timestamps for all recorded data. The
clock needs to be configured properly to achieve precise events and power quality
analysis. The PEM575 features a clock that has a maximum error of 0.5 s per day. The
internal battery keeps the real-time clock running in case of voltage interruption.
There are two methods to synchronise the clock:
SNTP server
GPS via external device
Summary of Contents for LINETRAXX PEM575 Series
Page 8: ......
Page 12: ...Making effective use of this document 12 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 28: ...Installation and connection 28 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 62: ...Application inputs and outputs 62 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 82: ...Logging 82 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 88: ...Power Quality 88 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 162: ...Modbus Register Map 162 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 166: ...Technical data 166 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 170: ...INDEX 170 PEM575_D00016_00_M_XXEN 04 2015 ...
Page 171: ......