Modbus Register Map
93
PEM735_D00084_00_M_XXEN/02.2015
Tab. 10.2: Basic measurements
Notes on table 10.2:
1)
Only in the case of wye connection (WYE).
2)
"x 1000" indicates the value returned in the register is 1000 times the measured value (the
value of the register must be divided by 1000 for an accurate measuring value).
3)
Status register 0085:
Represents the
status of the six digital inputs
B0 B5 for DI1 DI6 (1 = active/closed; 0 = inactive/open)
4)
Status register 0086:
Represents the
status of the three digital outputs
B0 for DO1 (1 = active/closed; 0 = inactive/open)
B1 for DO2 (1 = active/closed; 0 = inactive/open)
B2 for DO3 (1 = active/closed; 0 = inactive/open)
0099
RO
DR1 Pointer (highspeed)
10)
UINT32
0101
RO
DR2 Pointer (highspeed)
10)
UINT32
0103
RO
DR3 Pointer (highspeed)
10)
UINT32
0105
RO
DR4 Pointer (highspeed)
10)
UINT32
0107
RO
DR5 pointer (standard)
10)
UINT32
…
0129
RO
DR16 pointer (standard)
10)
UINT32
0131
RO
Total memory
11)
UINT32
0133
RO
Available memory
11)
UINT32
Register
Property
Description
Format
Scale/unit
Summary of Contents for LINETRAXX PEM575 Series
Page 8: ......
Page 12: ...Making effective use of this document 12 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 28: ...Installation and connection 28 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 62: ...Application inputs and outputs 62 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 82: ...Logging 82 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 88: ...Power Quality 88 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 162: ...Modbus Register Map 162 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 166: ...Technical data 166 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 170: ...INDEX 170 PEM575_D00016_00_M_XXEN 04 2015 ...
Page 171: ......