PEM735_D00084_00_M_XXEN/02.2015
Tab. 8.4: Setup energy log
The energy log will only become active when the values of the Setup settings 1…5
are all non-zero.
For details refer to Modbus registers 7700…7712.
8.5 Waveform recording (WFR)
The PEM575 provides two waveform recorders capable of recording waveforms in-
dependently from one another. The total capacity of WFR 1 and WFR 2 is 32. Each
waveform recorder can simultaneously record 3-phase voltage and current signals
at a maximum resolution of 256 samples per cycle.
Waveform recorders can be triggered by
Setpoints
Undervoltage/overvoltage (sag/swell)
Transient events
Communications interface (manual)
During this process the
control via communications interface has the highest
priority
. Other WFR triggers will be ignored until recording is completed.
Each WFR log has a capacity of 32 entries. If there are more than 32 entries, the ne-
west entry will replace the oldest entry on a first-in-first-out basis: Der 33
rd
entry
overwrites the 1
st
entry, the 34
th
the 2
nd
etc.
WFR data is stored in a non-volatile memory and will not suffer any loss in the event
of power failure.
The programming of the waveform recorder log is only supported by the commu-
nications interface. For details about the applied
registers
and their data structure
refer to
.
5
Number of parame-
ters
0…5
6
Parameters 1…5
0 = Import
P
1 = Export
P
2 = Import
Q
3 = Export
Q
4 =
S
No.
Parameters
Setting
Summary of Contents for LINETRAXX PEM575 Series
Page 8: ......
Page 12: ...Making effective use of this document 12 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 28: ...Installation and connection 28 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 62: ...Application inputs and outputs 62 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 82: ...Logging 82 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 88: ...Power Quality 88 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 162: ...Modbus Register Map 162 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 166: ...Technical data 166 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 170: ...INDEX 170 PEM575_D00016_00_M_XXEN 04 2015 ...
Page 171: ......