TGH 1360E
7 Technical data
Insulation coordination acc. to IEC 60664-1:
Rated insulation voltage
DC 800 V
Rated impulse withstand voltage/contamination level
8 kV/3
Dielectric test acc. to IEC 60255
4 kV
System being monitored:
Rated mains voltage U
N
DC 350...800 V
Operating range U
N
DC 100...1100 V
Supply voltage:
Supply voltage U
S
AC
AC 50...60 Hz 100...240 V
Operating range U
S
AC
0.9...1.1 U
S
Supply voltage U
S
DC
d.c. 110 V
Operating range U
S
DC
0.8...1.2 U
S
Max. power consumption
30 W max.
Response values:
Response value R
ALARM
5
Ω
....100 k
Ω
For response values <1000
Ω
a coupling device AG5002 must be used.
Alarm indication threshold voltage exceeded
350 or 100 V
Max. system leakage capacitance
10
µ
F
Response times:
Delay time
0...100 s
Window time
0...300 s
Measuring circuit:
Internal resistance DC
R
i
500 kOhm
Internal resistance DC R
i with AG5002
5 kOhm
Relay outputs
Contact circuit
Switching components
3 change-over contact
Contact class acc. to DIN IEC 60255 Teil 0-20
IIB
Rated contact voltage
AC 250 V/DC 300 V
Admissible number of operations
12000 cycles
Limited making capacity
UC 5 A
Limited breaking capacity
at AC 230 V and cos phi = 0.4
AC 2 A
at DC 220 V and L/R = 0.04 s
DC 0.2 A
Operating principle, K1 and K2, selectable
N/O / N/C operation
Pre-set by factory, K1 and K2
N/O operation
Operating principle K3
N/C operation
Serial interfaces
RS 232 and RS 485
Outputs
*analog output M+/M-
0...20 mA, linear
Inputs
Digital input 1 (E1/EG)
selectable, DC 24 V or DC 5 V
Digital input 2 (E2/EG)
without function at the moment
* )
see diagram on page 35
Supplementary information on switching elements:
The insulation condition between the relays is:
basic insulation 230 V, protective separation < 150 V