25
TGH 1360E
Setting and operation
Selecting the last sub menu 10.ABOUT opens a screen with information about
the manufacturer (BENDER), designation of the device and the software version
(identical with the welcome screen).
If problems arise or information about IR5002 is required, the first thing the
user wants to know is the software version. Information can be interrogated
from this sub menu.
*******BENDER*******
*A-ISOMETER IR500
2
*
*VERSION L2.0/05.96*
ENTER
Software version
Factory settings
The settings described in this chapter allow for optimal adaptation to the
individual application of the system. Before starting operation please check if
the factory settings suit your needs. If necessary make the respective changes.
The following parameters are pre-set:
Response values
(Menu 2 RESPONSE VALUES)
1 k
Ω
/ 1 k
Ω
Response times
(Menu 3 ALARM TIMING)
Delay-time: 0 s, Window-time: 50 s
Relay mode
(Menu 4 RELAY MODE)
K1 and K2: N/O operation; K3: N/C
operation (fixed setting)
Alarm indication voltage
(Menu 5 ALARM SYST. VOLT.)
DC 350 V
Serial interfaces
(Menu 6 SERIAL INTERFACE)
9600 baud. Further parameters are 8N1 (not
adjustable).
Digital input 1
(Menu ENABLE MEASUREM.)
NOT ACTIVE