29
TGH 1360E
Error messages
Various error messages may occur during operation. Error messages are
indications of internal or external faults of the IR5002 excluding the response of
the device when the pre-set response value of the insulation resistance has been
exceeded.
CRITICAL ERRORS are signalled when certain internal errors occur. CRITICAL
ERROR means, for example, that the system voltage has fallen below the pre-set
minimum value (<350 V resp. < 100 V DC).
*******************
*******************
*
CRITICAL ERROR
*
*
Un < 350 V
*
As shown in the picture above, IR5002 provides detailed descriptions about the
nature of error. In this case, it is recommended to measure the system voltage.
From the display CRITICAL ERROR you have the possibility to get to the
setting menu by activating the RIGHT key.
**** MEASURING ****
*** SUPPRESSION ***
****** ACTIVE ******
Menue:
08:37
The indication MEASURING SUPPRESSION ACTIVE shows that the
measuring suppression has been activated via the digital input 1 (E1/EG).
Wiring and commissioning