Function
49
FTC470XDP_D00111_00_M_XXEN/02.2015
6.7.19 Requesting the maximum number of measurements
In EDS systems, the maximum number of measurements can be set in the menu item "Peak". Setting
a higher peak value allows increased measuring reliability in systems where interferences occur, for
example caused by converters.
Writing to FTC470XDP (= output of the PROFIBUS Master)
Table 6.51: Master request: the maximum number of measurements
Reading from FTC470XDP (= input data of the PROFIBUS Master)
Table 6.52: FTC reply to: the maximum number of measurements
6.7.20 Setting the maximum number of measurements
Writing to FTC470XDP (= output of the PROFIBUS Master)
Table 6.53: Master request: setting of the maximum number of measurements
Reading from FTC470XDP (= input data of the PROFIBUS Master)
Table 6.54: FTC reply to: setting of the maximum number of measurements
Function
Devices
Channel
No.
BMS
comma
nd
Data
Type
Data
Value
Request for the maximum number of measurements
EDS…,
PRC470
1… 12
1… 12
41
0
0
Preset max. number of measurements
EDS…,
PRC470
1… 12
1… 12
41
1
quan-
tity
Function
Devices
Channel
No.
BMS
comma
nd
Data
Type
Data
Value
Setting of the max. number of measurement
EDS…,
PRC470
1… 12
1… 12
40
1
quan-
tity
Acknowledgement
EDS…,
PRC470
1… 12
1… 12
40
1
quan-
tity
Invalid value
EDS…,
PRC470
1… 12
1… 12
40
255
255