Programming examples
63
FTC470XDP_D00111_00_M_XXEN/02.2015
The PROFIBUS Master addresses BMS address 20, the insulation monitoring device 107TD47, for the
actual measuring value. This information is available at channel 1 of the 107TD47.
PROFIBUS Master output data:
The 107TD47 signals an insulation resistance of 100 k
Ω
as measuring value.
PROFIBUS Master input data:
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
Consecutive
PROFIBUS ID
No.
always
"0"
BMS address of
the addressed
device
BMS channel
number
BMS
Com-
mand
BMS data
type
High byte
BMS data
value
Low byte
BMS data
value
12
0
20
1
105
0
0
0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
12
0
20
1
105
61
0
100