Function
46
FTC470XDP_D00111_00_M_XXEN/02.2015
6.7.13 Requesting the operating mode of the alarm relay
Writing to FTC470XDP (= output of the PROFIBUS Master)
Table 6.39: Master request: operating mode of the collective alarm relay
Reading from FTC470XDP (= input data of the PROFIBUS Master)
Table 6.40: FTC reply to: operating mode of the collective alarm relay
6.7.14 Setting the operating mode of the alarm relay
Writing to FTC470XDP (= output of the PROFIBUS Master)
Table 6.41: Master request: setting the operating mode of the alarm relay
Reading from FTC470XDP (= input data of the PROFIBUS Master)
Table 6.42: FTC reply to: setting the operating mode of the alarm relay
Function
Devices
Channel
No.
BMS
comma
nd
Data
Type
Data
Value
Request for the operating mode of the collective
alarm relay
EDS.., RCMS..,
PRC470…
0
27
0
0
N/O operation
EDS.., RCMS..,
PRC470…
0
27
1
0
N/C operation
"
0
27
1
1
Invalid value
"
0
27
255
255
Function
Devices
Channel
No.
BMS
comma
nd
Data
Type
Data
Value
Setting the alarm relays to N/O operation
107TD47
EDS…,
RCMS…,
PRC470
0
25
1
0
Setting the alarm relays to N/C operation
"
0
25
1
1
Acknowledgement
EDS…,
RCMS…,
PRC470
0
25
1
value
Invalid value
"
0
25
255
255