Function
38
FTC470XDP_D00111_00_M_XXEN/02.2015
Table 6.16: FTC reply to: requesting the device response values
Function
Devices
Channel
No.
BMS
comma
nd
Data
Type
Data
Value
EDS mode:
0 = off 1 = on 2 = auto 3 = 1 cycle
4 = position
IRDH..
14
30
91
value
EDS operation,
system: 0 = DC 1 = AC 2 = 3AC
IRDH..
15
30
92
"
EDS pulse:
0 = 1mA 1 = 2,5 mA 2 = 10 mA
3 = 25 mA 4 = 50 mA
IRDH..
16
30
93
"
EDS position mode:
indication of the BMS address
IRDH..
17
30
94
"
EDS position mode:
indication of the channel number
IRDH..
18
30
95
"
Value = alarm address * 100 + channel No. (of the alarm
giving device; reference to the subsequent pages)
SMO482-12
1… 12
30
96
"
Test address:
0 = all connected devices will be tested,
Value = BMS address of the addressed device
MK2418..
13
30
97
"
Buzzer, collective alarm reset:
1 = on 2 = off
MK2418..
14
30
98
"
Personnel:
0 = medical 1 = technical
MK2418..
15
30
99
"
LSD470 mode
Display language
EDS mode
107TD47
16
17
18
30
181
"
Response value insulation monitoring in k
Ω
107TD47
5
30
182
"
Response value load current in A
107TD47
6
30
183
"
Time delay of the alarm relay in s
107TD47
7
30
184
"
No further channels
all
channel
No.
30
254
254
Invalid value
RCMS….,
MK2418..-11
1… 12
30
255
255