![Bender FTC470XDP Manual Download Page 53](http://html1.mh-extra.com/html/bender/ftc470xdp/ftc470xdp_manual_2731752053.webp)
Function
53
FTC470XDP_D00111_00_M_XXEN/02.2015
6.9.3
Starting the self test of an EDS system
Writing to FTC470XDP (= output of the PROFIBUS Master):
Table 6.65: Master request: starting the self test of an EDS system
Reading from FTC470XDP (= input data of the PROFIBUS Master):
Table 6.66: FTC reply to: starting the self test of an EDS system
6.9.4
Buzzer mute
Writing to FTC470XDP (= output of the PROFIBUS Master):
Table 6.67: Master request: buzzer mute
Reading from FTC470XDP (= input data of the PROFIBUS Master):
Table 6.68: FTC reply to: buzzer mute
Function
Devices
Channel
No.
BMS
comma
nd
Data
Type
Data
Value
Starting the self test of an EDS system
EDS.., RCMS..
0
7
0
0
No answer
EDS…,
RCMS…
0
7
255
255
Self test is being confirmed
EDS… effec-
tive from ver-
sion 2.0
0
7
0
0
Function
Devices
Channel
No.
BMS
comma
nd
Data
Type
Data
Value
Buzzer mute
MK2418..,
SMI470…
0
14
0
address
No answer
MK2418..,
SMI470…
0
14
255
255
Acknowledgement of the buzzer mute
version 2.0 or higher
"
0
14
0
0