Basic programs
49
VMD460-NA_D00001_05_M_XXEN/01.2020
6. Basic programs
The following standards are implemented in the factory settings of the VMD460-NA:
Response values for NS protection may only be changed in consultation
with the system operator!
Standard/application guide
Basic pro-
gram
Profiles
VDE-AR-N 4105:2018-09
4105_2
1:
Synchronous and asynchronous generators coupled directly
or via a converter with P
n
≤ 50 kW
2:
Synchronous and asynchronous generators coupled directly
with P
n
≥ 50 kW
3:
Converter
VDE-AR-N 4105:2011-08
4105_1
VDE-AR-N 4110:2018-11
4110
1 (MV-busbar; higher-level generating plant)
Protection of a generating plant at the network connection
point when connected to the busbar *
2 (MV-busbar; generating unit)
Protection at the generating unit when connecting the gener-
ating plant to the busbar of a substation
3 (MV-network; higher-level generating plant)
Protection of a generating plant at the network connection
point when connected to the medium-voltage network *
4 (MV-network; generating unit)
Protection at the generating unit when connecting the gener-
ating plant to a medium-voltage network
*) For profiles 1 and 3, the separate instructions for the
intended use in Chapter 2.4 and the wiring diagram in
Chapter 4.8.3 must be observed.
BDEW technical guideline 2008 with amend-
ments until 01.2013
BDEW
DIN V VDE V 0126-1-1:2006-02/A1:2012-02
0126
CEI 0-21(:2012-06, :V1:2012-12, :V2:2013-12,
:2014-09, :V1:2014-12, 2016-07, V1:2017-07)
CEI 021
C10/11:2012-06
C10/11
G98/1-4:2019
G98
G83/2:2012 and G59/3:2013
G83/2
G99/1-4:2019
G99
Type A, type B and type C power generation modules
1:
Low-voltage protection (LV Protection)
2:
High-voltage protection (HV Protection)
Type D ...
3:
Type D power generation modules and power plants with a
registered capacitance of > 50 MW