Operation and settings
41
VMD460-NA_D00001_05_M_XXEN/01.2020
5.2 Display indications
5.2.1
Standard display
In the standard display, line-to-line voltages, phase voltages, the highest 10-minute-
phase voltage mean value U10LN (depending on the standard) and the frequency are
indicated on the display.
Fig. 5.1: Standard display
5.2.2
Info display
Device-specific information is indicated on the info display.
Fig. 5.2: Info display
For detailed information, refer to Refer to "INFO button" on page 43.
5.2.3
Alarm display
Type and source of alarms are indicated on the alarm display in clear text format.
Fig. 5.3: Alarm display
Explanation: In the example above, the second message of three is being indicated (2/
3). The address "Addr.:" shows the BMS-bus address of the device sending the alarm.
The alarm is output on measuring channel 1 and can be accessed via channel number
1 in the "Alarm/meas. values" menu.
L1-N 229.9V
L1-L2
397.2V
L2-N 229.5V
L2-L3
VMD460-NA
22.02.14 12:34
Address: xx
ALARM
2/3
Undervoltage
U
(N-1)
: 180.3 V