6 720 611 443 GB (05.04)
36
Maintenance
B
Clean out the condensate collector and trap connec-
tion (with other end of brush).
Fig. 55
B
Refit the clean-out cover using a new seal and
tighten screws to torque of approx. 5 Nm.
Burner
B
Check that the gas cock is turned off and the master
switch is in the OFF position.
B
Remove the clips (1.) and unscrew the two bolts (2.).
Refer to fig. 56.
B
Unscrew and remove the two hexagon screws secur-
ing the fan (3.).
B
Slacken fully the rear securing bolt (4.).
B
Remove the burner coverplate.
Fig. 56
B
Remove the burner skin and clean components. Do
not use a wire brush. Refer to fig. 57.
Fig. 57
B
Re-assemble burner in reverse order inspect seal for
damage and replace if necessary.
B
Adjust gas/air ratio. Refer to section 7.2.
Condensation trap
In order to prevent spillage of condensate, the conden-
sation trap should be completely removed, (see
page 35, fig. 52).
B
Unscrew condensation trap and check connection to
heat exchanger is clear.
B
Remove condensation trap cover and clean.
B
Fill condensation trap with approx. 1/4 l of water and
refit.
Electrode assembly
B
Switch off the master switch.
B
Pull off the leads from the electrodes. Refer to fig. 2.
B
Unscrew the two fixing screws and carefully remove
the electrode assembly. Refer to fig. 51.
B
Clean the electrodes with a non-metallic brush. (The
spark gap should be 4 mm ± 1 mm.)
B
Replace and re-connect the assembly taking care not
to mislay the inspection window.
6 720 610 332-75.2R
1.
2.
4.
7 181 465 330-04.1R
3.
7 181 465 330-08.2R