8 Integrated Web Server
8.3 System Page
14.
Reset into delivery status by setting the address switch to 979 and by
running a power restart of the module. A period of 10 seconds should be
waited (during the restart procedure the red BF/MS LED flashes on and
off cyclically three times until the restart is completed)
15.
Set the address switch to 000.
16.
The firmware update is completed and the module was reset to the delivery
condition.
8.3 System Page
When the
System
menu item in the Web server menu bar is selected, the
System page opens. On this page in the
Connection Status
area, the current
status of both Ethernet ports is displayed with regard to the connection,
transfer rate and transfer mode as well as the network parameters and the
PROFINET status of the LioN-P module.
The
General Information
area contains the system-related information on the
runtime, the Firmware version used and the LioN-P module's manufacturing
details.
In User Management passwords of created users can be changed using the
Edit
button. The
Create User
area can be used to add users with
Write
or
Admin
permissions. Only access with
Admin
permission enables new users to be
created or passwords to be changed.
The status information on this page is updated in a web browser only after
reopening or refreshing of the page.
Technical Manual LioN-P PROFINET
Version 2.0 10/2017
63