8.2 Configuration Page (Config)
8 Integrated Web Server
8.2.1 Firmware Update for PROFINET
Requirements
D
PC with network interface
D
Performing Update
1.
Reset into delivery status by setting the address switch to 979 and by
running a power restart of the module. A period of 10 seconds should be
waited (during the restart procedure the red BF/MS LED flashes on and
off cyclically three times until the restart is completed / The 1st step is only
necessary if the module was already operated on a PLC).
2.
Set the IP address on the PC network interface (e.g. 192.168.001.050,
different from the IO module).
3.
Set the IP address on the IO module using a configuration tool (e.g.
Hilscher Config Tool) over DCP to 192.168.001.001 and run a power
restart of the module.
4.
in the browser.
5.
Select
Config
tab on WEB page.
6.
Select and click the
Firmware Update
button.