EMC and immunity
IEC/EN 61850-
3:2002 EMI TYPE
tests, test in
comp. with
Description
Certification C
Test level
Certification H
Test level
IEC/EN 61000-4-2 ESD
Contact discharge
Air discharge
+/- 8 kV
+/- 15 kV
+/- 8 kV
+/- 15 kV
IEC/EN 61000-4-3 Electromagnetic field
80 - 2700MHz
20 V/m
20 V/m
IEC/EN 61000-4-4 Burst
DC Power line
AC Power line
Data line
+/- 4 kV
+/- 4 kV
+/- 4 kV
+/- 4 kV
+/- 4 kV
+/- 4 kV
IEC/EN 61000-4-5 Surge
DC Power line
AC Power line
Data line
+/- 2 kV line/ground
+/- 1 kV line/line
+/- 4 kV line/ground
+/- 2 kV line/line
+/- 4 kV line/ground
+/- 2 kV line/ground
+/- 1 kV line/line
+/- 4 kV line/ground
+/- 2 kV line/line
+/- 4 kV line/ground
IEC/EN 61000-4-6 Conducted interference
voltage
50kHz - 80MHz
10 V
10 V
IEC/EN 61000-4-12 Damped oscillation
DC Power line
AC Power line
Data line
+/- 2.5kV line/ground
+/- 1kV line/line
+/- 2.5kV line/ground
+/- 1kV line/line
+/- 2.5kV line/ground
+/- 1kV line/line
+/- 2.5kV line/ground
+/- 1kV line/line
+/- 2.5kV line/ground
+/- 1kV line/line
+/- 2.5kV line/ground
+/- 1kV line/line
IEC 60255-5
Electrical strength
DC Power line power supply
unit type C
Signal contact
500 VAC
a
2000 VAC
a. Protective elements limit this voltage to 60 VDC (1 mA)
500 VAC
a
2000 VAC
IEEE 1613:2009
EMI TYPE tests,
test in comp. with
Description
Certification C
Test level
Certification H
Test level
IEEE C37.90.3
ESD
Contact discharge
Air discharge
+/- 8 kV
+/- 15 kV
+/- 8 kV
+/- 15 kV
IEEE C37.90.2
Electromagnetic field
80 - 2700MHz
35 V/m (peak)
35 V/m (peak)
IEEE C37.90.1
Burst
DC Power line
AC Power line
Data line
+/- 4 kV
+/- 4 kV
+/- 4 kV
+/- 4 kV
+/- 4 kV
+/- 4 kV
Summary of Contents for HIRSCHMANN RSR20 Series