26
MACH 1040
Release 02 03/2013
Figure 8: Power supply unit “M”
(see page 41 „General technical data“)
:
AC voltage (pictured on right) or DC voltage (pictured on left)
Connecting
1 - Supply voltage
2 - Signal contact
For every supply voltage to be connected, perform the following steps:
Ensure the required conditions for connecting the supply voltage
(see
page 4 „Supply voltage“)
.
Pull the terminal block off the device.
Connect the protective conductor to the protective conductor terminal.
Connect the lines for the supply voltage to the ter/L and -/N.
Mount the terminal block on the device using screws.
Connection
Type “L”
Type “M” VDC
Type “M” VAC
, pin 1
Protective conductor
Protective conductor
Protective conductor
-/N, pin 2
Minus terminal of the
supply voltage
Minus terminal of the
supply voltage
Neutral conductor
+/L, pin 3
Plus terminal of the
supply voltage
Plus terminal of the
supply voltage
Line conductor
Table 3:
Pin assignment of terminal block for voltage supply
WARNING
ELECTRIC SHOCK
Only start connecting the supply voltage if
all
the above mentioned
requirements are fulfilled.
(see page 4 „Supply voltage“)
Failure to follow these instructions can result in death, serious injury,
or equipment damage.
1
2
Relay
-/N +/L
-/N +/L
G
Relay
1
2
Summary of Contents for HIRSCHMANN MACH 1040 Series
Page 51: ...MACH 1040 Release 02 03 2013 51...