.3.1  Access

Access to the listener configuration menu is
obtained by operating the 

P

 and 

E

 buttons

simultaneously.  If the BA644DF-F is not protected
by an access code the first parameter 'SCAn’ will
be displayed.

*

   If the indicator is protected by an

access code, ‘CodE’ will be displayed first.
Pressing 

P

 will allow the four digit security code to

be entered digit by digit using the 

 or 

 button to

adjust the flashing digit and 

P

 to move control to

the next digit.  When the correct code has been
entered, pressing 

E

 will cause the first parameter

‘SCAn’ to be displayed.

*

    If an incorrect code is

entered, or no button is pressed for ten seconds,
the indicator will automatically return to the display
mode.

If the indicator displays ‘rESEt’ it is conditioned

as a fieldbus node, see section 5.2.2 to change it
to a fieldbus listener.

5.3.2  Summary of listener configuration
           functions.

This section contains a summary of all the listener
configuration functions including a reference to
more detailed information.  It should be read in
conjunction with Fig 6.

  

Indicator              Summary

   

display               of function

‘SCAn’

Scan fieldbus segment 

Identifies

 

all publishers on the fieldbus

segment to which the listener is
connected and enables selected data to
be allocated to one of the eight listener
inputs.
See section 5.3.3

‘LiSt’

List configured input parameters

For each of the eight BA644DF-F
listener input, in-1 to in-8 shows if the
input is enabled and the allocated
Device Address and Variable Identity.
Parameters can not be changed from
within this function.
See section 5.3.4

‘Edit’

Enter addresses and display
parameters

Contains six sub-functions that enable
known fieldbus Device Address and
Variable Identity to be entered and all
display parameters adjusted for each of
the eight fieldbus listener inputs.
See section 5.3.5 

‘Enb’

Enable listener input

Each of the eight listener inputs in-1
to in-8 may be enabled or disabled
without affecting any parameters.
See section 5.3.6

‘Adr’

Enter fieldbus Device Address

Allows hexadecimal fieldbus device
address for each of the eight listener
inputs in-1 to in-8 to be entered.
See section 5.3.7

‘id’

Enter Variable Identity

Allows hexadecimal Variable Identity
for each listener input in-1 to in-8 to
be entered.
See section 5.3.8

‘dP’

Decimal point position

Defines position of displayed decimal
point for each listener input in-1 to
in-8.
See section 5.3.9

‘bAr’

Configuration of bargraph display.

Defines bargraph type, plus digital
display at which bargraph is zero and
full scale for each listener input in-1 to
in-8.
See section 5.3.10

‘SCALE’

Scale numeric display

Applies zero offset and scale factor to
the numeric display for each listener
input in-1 to in-8.
See section 5.3.11

‘CodE’

Access code for listener
configuration menu

Enters a four digit security access
code for configuration menu.  Default
code 0000 disables this function.
See section 5.3.12

‘tYPE’

Change from listener to node

Changes the function of the fieldbus
indicator from a listener to a node.
See section 5.3.13

‘rESEt’

Reset

Returns the BA644DF-F listener to
factory defaults.
See section 5.3.14

Summary of Contents for FOUNDATION BA644DF-F

Page 1: ...Issue 4 4th March 2014 BA644DF F FOUNDATION fieldbus Field mounting 8 variable Fieldbus Indicator Issue 4...

Page 2: ...display parameters 5 3 6 Enable selected input 5 3 7 Enter Device Address 5 3 8 Enter Variable Identity 5 3 9 Decimal point position 5 3 10 Configuration of bargraph 5 3 11 Scale numeric display 5 3...

Page 3: ...protocol is shown on a label inside the terminal cover The F order code suffix also indicates the protocol but is not shown on the instrument identification label There is an alternative version of t...

Page 4: ...arth terminal should be connected to the potential equalising network The BA644DF F enclosure is supplied with a bonding plate to ensure electrical continuity between the three conduit cable entries 4...

Page 5: ...5 Fig 3 Dimensions and terminal connections...

Page 6: ...nditioned as a fieldbus listener see section 5 3 13 to change it to a fieldbus node 5 2 1 Reset the indicator to node factory defaults rESEt The BA644DF F may be reset to the factory defaults that are...

Page 7: ...the P button causes the BA644DF F indicator to search the fieldbus segment to which it is connected for all publishers Fig 5 shows how the indicator displays the hexadecimal Device Address and Variabl...

Page 8: ...vice Address and Variable Identity Parameters can not be changed from within this function See section 5 3 4 Edit Enter addresses and display parameters Contains six sub functions that enable known fi...

Page 9: ...9...

Page 10: ...isplayed pressing E will allocate the selected process variable to the selected input and return the display to the Device Address and Variable Identity from which another process variable may be sele...

Page 11: ...function pressing P again will reveal the existing bargraph justification The or button will scroll through the four options when the required justification is displayed pressing E will enter the sele...

Page 12: ...ration menu using the or button To enter the function press P which will show that the instrument is configured as a fieldbus listener to change to a fieldbus node press the or button which will toggl...

Page 13: ...nfiguration All display segments activated Display is initialising This is normal operation after a few seconds the model number followed by the firmware version will be displayed prior to entering th...

Page 14: ...After adding the required legends or fitting a new pre printed self adhesive escutcheon ensure that the gasket is correctly positioned before reassembling the instrument enclosure 7 2 Tag plate The BA...