.2.3  Access code for node configuration

          menu   ‘CodE’

Access to the node configuration menu may be
protected by a four digit security code which must
be entered to gain access.  New instruments are
supplied configured with the default code 0000
which disables this protection and allows
unrestricted access to the configuration menu.

To enter a new access code select ‘CodE’ in the
configuration menu by operating the 

 or 

button.   To enter the function press 

P

 which will

reveal the current access code with one digit
flashing. The code may be changed using the 

 or

 button to adjust the flashing digit and the 

P

button to move control to the next digit.  When the
required code has been selected, press 

E

 to enter

the selection and return to the ‘CodE’ prompt in the
configuration menu.    The revised access code will
be activated when the indicator is returned to the
display mode.

If the access code is lost please contact BEKA
associates.

Fig 4 Node configuration menu

5.3  Listener configuration menu

The listener configuration menu is separated into
three sections, ‘SCAn’, ‘LISt’ and ‘Edit’, plus three
housekeeping functions ‘CodE’, ‘tYPE’ and ‘rESEt’
as shown in Fig 6.

‘SCAn’ is the simplest method of configuration if
the fieldbus Device Address and Variable Identity
of the data to be displayed by the BA644DF-F
listener are not known.

In the ‘SCAn’ function pressing the 

P

 button

causes the BA644DF-F indicator to search the
fieldbus segment to which it is connected for all
publishers.  Fig 5 shows how the indicator displays
the hexadecimal Device Address and Variable
Identity associated with each publisher.

Publisher

 is a device that places it's output

data onto the bus as part of a cyclical pre-
determined data exchange schedule.

The 

Device Address

 is a unique address that

identifies each fieldbus instrument connected to
the bus.

The 

Variable Identity

 is the fieldbus device

Data Link Connection End Point (DLCEP)
which identifies each Function Block output
(process variable) transmitted by a fieldbus
device such as flow and temperature
transmitted by a fieldbus flowmeter.

The 

 and 

 push buttons scroll the display

through all the publishers on the segment showing
the Device Address and Variable Identity for each
one - see Fig 5.   To aid identification, operating
the 

P

 button will preview the value of the data at

each selected address, if required it may then be
allocated to one of the eight BA644DF-F listener
inputs in-1, to in-8 by operating the 

P

 button again.

If the format of the data at the selected Device
Address and Variable Identity is not DS-65 (float +
status) ‘no dAt’ will be displayed.

Fig 5  Device Address and Variable Identity

If the Device Address and Variable Identity of the
process variable to be displayed by the BA644DF-
F indixator are known, they may be directly
entered via the edit sub-menu.  This sub-menu
also provides full control of both the numeric and
bargraph display parameters.

Summary of Contents for FOUNDATION BA644DF-F

Page 1: ...Issue 4 4th March 2014 BA644DF F FOUNDATION fieldbus Field mounting 8 variable Fieldbus Indicator Issue 4...

Page 2: ...display parameters 5 3 6 Enable selected input 5 3 7 Enter Device Address 5 3 8 Enter Variable Identity 5 3 9 Decimal point position 5 3 10 Configuration of bargraph 5 3 11 Scale numeric display 5 3...

Page 3: ...protocol is shown on a label inside the terminal cover The F order code suffix also indicates the protocol but is not shown on the instrument identification label There is an alternative version of t...

Page 4: ...arth terminal should be connected to the potential equalising network The BA644DF F enclosure is supplied with a bonding plate to ensure electrical continuity between the three conduit cable entries 4...

Page 5: ...5 Fig 3 Dimensions and terminal connections...

Page 6: ...nditioned as a fieldbus listener see section 5 3 13 to change it to a fieldbus node 5 2 1 Reset the indicator to node factory defaults rESEt The BA644DF F may be reset to the factory defaults that are...

Page 7: ...the P button causes the BA644DF F indicator to search the fieldbus segment to which it is connected for all publishers Fig 5 shows how the indicator displays the hexadecimal Device Address and Variabl...

Page 8: ...vice Address and Variable Identity Parameters can not be changed from within this function See section 5 3 4 Edit Enter addresses and display parameters Contains six sub functions that enable known fi...

Page 9: ...9...

Page 10: ...isplayed pressing E will allocate the selected process variable to the selected input and return the display to the Device Address and Variable Identity from which another process variable may be sele...

Page 11: ...function pressing P again will reveal the existing bargraph justification The or button will scroll through the four options when the required justification is displayed pressing E will enter the sele...

Page 12: ...ration menu using the or button To enter the function press P which will show that the instrument is configured as a fieldbus listener to change to a fieldbus node press the or button which will toggl...

Page 13: ...nfiguration All display segments activated Display is initialising This is normal operation after a few seconds the model number followed by the firmware version will be displayed prior to entering th...

Page 14: ...After adding the required legends or fitting a new pre printed self adhesive escutcheon ensure that the gasket is correctly positioned before reassembling the instrument enclosure 7 2 Tag plate The BA...

Reviews: