10

5.3.3  Scan fieldbus segment  ‘SCAn’

If the Device Address and Variable Identity of a
process variable are not known, the ‘SCAn’
function provides a simple way to identify them.
This function scans the fieldbus segment to which
the BA644DF-F indicator is connected and
identifies all the publishers.  To aid identification it
enables the value of each process variable to be
pre-viewed and, if required, allocated to one of the
eight BA644DF-F Fieldbus indicator inputs.

The BA644DF-F indicator only supports DS-65
formatted data (float + status) which is the usual
format for analogue process variables.   The
‘SCAn’ function will identify all publishers on the
segment irrespective of format, but when pre-
viewed, non DS-65 formatted data will produce a
‘no dAt’ error message.

‘SCAn’ is the first function displayed when entering
the listener configuration menu, or it may be
selected from within the menu by operating the 

or 

 button.   To scan the fieldbus segment to

which the indicator is connected for all published
data press 

P

 which will reveal the hexadecimal

Device Address and Variable Identity of the first
publisher found as shown in Fig 5.    If there is
more than one publisher operating the 

 or 

button will scroll though all of them.

If no cyclic data is being published on the fieldbus
segment the BA644DF-F indicator will display
‘noPub’.

When the Device Address and Variable Identity of
a process variable is being displayed, pressing 

P

will preview the value of the process variable
displayed with maximum resolution on the five digit
display.   If this confirms that it is one of the
process variables to be displayed, it may be
allocated to one of the eight BA644DF-F listener
inputs in-1 to in-8.

To select the required indicator input press 

P

 to

display the first input in-1, operating the 

 or 

button will scroll the display through the other
inputs.  When the required input is displayed
pressing 

E

 will allocate the selected process

variable to the selected input and return the display
to the Device Address and Variable Identity from
which another process variable may be selected.

When a process variable is allocated to a indicator
input any previous allocation will be overwritten.

5.3.4 List configured input parameters   ‘LiSt’

The ‘LiSt’ function enables the Device Address and
Variable Identity allocated to each lindicator input
to be viewed without danger of it being accidentally
changed.

The ‘LiSt’ function may be selected from within the
menu by operating 

 or 

 button. To enter the

function press 

P

 which will display the indicator

input currently selected in the display mode, other
inputs may be selected using the 

 or 

 button.

Operating the 

P

 button will cause the following

parameters for the selected input to be displayed
sequentially:

           

Display                    Explanation

‘Enb: Y or N’

Input Enabled yes or no

‘Adr:   00’

Device Address

   ‘id:   00’

Variable Identity

The display then automatically returns to the
selected BA644DF-F indicator input from where
another input may be selected.

If one of the eight BA644DF-F indicator’s inputs in-
1 to in-8 has not had a Device Address and
Variable Identity allocated to it, ‘LiSt’ will show both
as invalid address FF.

5.3.5  Enter address & display parameters
          ‘Edit’

The ‘Edit’ function may be selected from within the
menu by operating 

 or 

 button. To enter the

function press 

P

 which will display the indicator

input currently selected in the display mode, other
listener inputs may be selected using the 

 or 

button.  When the required input has been
selected operating the 

P

 button will enter the edit

sub-menu at ‘Enb’ for the selected input.

5.3.6  Enable selected input    ‘Enb’

‘Enb’ turns the indicator input selected in the Edit
function on or off without affecting the conditioning.
To enter the function press 

P

 which will reveal

whether the selected input is ‘on’ or ‘oFF’.
Operating the 

 or 

 buttons will toggle between

the two conditions.  When set as required
operating the 

E

 button will enter the selection and

return to the edit sub-menu.

Summary of Contents for FOUNDATION BA644DF-F

Page 1: ...Issue 4 4th March 2014 BA644DF F FOUNDATION fieldbus Field mounting 8 variable Fieldbus Indicator Issue 4...

Page 2: ...display parameters 5 3 6 Enable selected input 5 3 7 Enter Device Address 5 3 8 Enter Variable Identity 5 3 9 Decimal point position 5 3 10 Configuration of bargraph 5 3 11 Scale numeric display 5 3...

Page 3: ...protocol is shown on a label inside the terminal cover The F order code suffix also indicates the protocol but is not shown on the instrument identification label There is an alternative version of t...

Page 4: ...arth terminal should be connected to the potential equalising network The BA644DF F enclosure is supplied with a bonding plate to ensure electrical continuity between the three conduit cable entries 4...

Page 5: ...5 Fig 3 Dimensions and terminal connections...

Page 6: ...nditioned as a fieldbus listener see section 5 3 13 to change it to a fieldbus node 5 2 1 Reset the indicator to node factory defaults rESEt The BA644DF F may be reset to the factory defaults that are...

Page 7: ...the P button causes the BA644DF F indicator to search the fieldbus segment to which it is connected for all publishers Fig 5 shows how the indicator displays the hexadecimal Device Address and Variabl...

Page 8: ...vice Address and Variable Identity Parameters can not be changed from within this function See section 5 3 4 Edit Enter addresses and display parameters Contains six sub functions that enable known fi...

Page 9: ...9...

Page 10: ...isplayed pressing E will allocate the selected process variable to the selected input and return the display to the Device Address and Variable Identity from which another process variable may be sele...

Page 11: ...function pressing P again will reveal the existing bargraph justification The or button will scroll through the four options when the required justification is displayed pressing E will enter the sele...

Page 12: ...ration menu using the or button To enter the function press P which will show that the instrument is configured as a fieldbus listener to change to a fieldbus node press the or button which will toggl...

Page 13: ...nfiguration All display segments activated Display is initialising This is normal operation after a few seconds the model number followed by the firmware version will be displayed prior to entering th...

Page 14: ...After adding the required legends or fitting a new pre printed self adhesive escutcheon ensure that the gasket is correctly positioned before reassembling the instrument enclosure 7 2 Tag plate The BA...

Reviews: