background image

20

Fig 13  Typical alarm application

(Shown without recommended screened cables)

8.3.2  Configuration and adjustment

When optional alarms are fitted to a loop powered
indicator the configuration menu is extended as
shown in Fig 12.   The additional functions appear
between the ‘SEt’ and  the ‘C- - P’ functions for the
BA507E and BA508E indicators, and between
‘bAr’ and ‘C- -P’ for the BA527E and BA528E
indicators.  For simplicity, Fig 12 only shows the
additional functions for alarm 1, but alarm 2 has
identical functions.

The following table summaries each of the alarm
configuration functions and includes a cross
reference to more detailed information.   Again
only the functions on alarm 1 are listed, but alarm
2 has identical facilities

Summary of alarm configuration functions

   

Display

      Description of function

'EnbL’

Alarm enable

Enables or disables the alarm without
changing the alarm parameters.
See section  8.3.3

'SP1'

Alarm setpoint 1

Adjusts the alarm setpoint.  The alarm
is activated when the indicator display
equals the setpoint.
See section 8.3.4

'Hi.Lo'

Alarm function

Defines the alarm function as High or
Low.
See section 8.3.5

'no.nC' Normally open or normally closed

output

Sets the alarm output open or closed in
the non-alarm condition.
See section 8.3.6

'HStr'

Hysteresis

Adjusts the alarm hysteresis.
See section 8.3.7

'dELA'

Alarm delay

 

time

Introduces adjustable delay between
the display equalling the setpoint and
the alarm output being activated.
See section 8.3.8

'SiL'

Alarm silence time

Defines the time that the alarm output
remains in the non-alarm condition
following acceptance of an alarm.
See section 8.3.9

‘FLSH’

Flash display when alarm occurs

When enabled, alternates the
numerical display between process
value and alarm reference, ‘ALr1’ or
‘ALr2’, when an alarm output is
activated.
See section 8.3.10

'ACSP' Access setpoint

Sub-menu which enables direct access
to the alarm setpoints from the indicator
display mode, and defines a separate
security code.
See section 8.3.11

Summary of Contents for BA507E

Page 1: ...Supplied by Call us on 44 0 118 916 9420 Email info 247able com com Installation Maintenance Instructions BA507E BA508E BA527E BA528E...

Page 2: ...rk Danehill Lower Earley Reading Berkshire RG6 4UT UK Tel 44 0 118 9311188 Email info able co uk Aberdeen Office Unit 6 Airside Business Park Kirkhill Industrial Estate Dyce Aberdeen AB21 0GT UK Tel 4...

Page 3: ...Issue 3 1st December 2012 BA507E BA527E BA508E BA528E General Purpose loop powered panel mounting indicators issue 3...

Page 4: ...error message 6 4 Lineariser under and over range 6 5 Lineariser default configuration 7 Maintenance 7 1 Fault finding during commissioning 7 2 Fault finding after commissioning 7 3 Servicing 7 4 Rout...

Page 5: ...splay any variable represented by the 4 20mA current e g temperature flow pressure or level The BA507E BA527E BA508E and the BA528E are not certified for use in explosive atmospheres For hazardous are...

Page 6: ...in display mode function has been enabled P E Access to configuration menu via optional security code Note BA527E and BA528E only If the indicator has been calibrated using the CAL function calibratio...

Page 7: ...el providing that the operating temperature is between 40 C and 70 C Figs 4A and 4B show the overall dimensions of the 96 x 48mm and the 144 x 72mm instruments together with the recommended panel cut...

Page 8: ...dovetail as shown in Fig 5 Push the knurled screw slightly forward to engage the thread and tighten by turning clockwise until it is just finger tight When both clamps are fitted ensure that the gaske...

Page 9: ...rd unclip the protruding end of the flexible strip by gently pushing it upwards and pulling it out of the enclosure Peel the existing scale card from the flexible strip and replace it with a new print...

Page 10: ...00 0000 Function FunC Std Std Display at 4mA Zero 0 0 0 00 Display at 20mA SPAn 100 0 100 00 Resolution rESn 1 digit 1 digit Bargraph start BarLo 0 00 Bargraph finish BarHi 100 00 P button in display...

Page 11: ...value Using ZEro function set required display at 4mA by pressing pressing and to move to the next digit Similarly using SPAn function set required display at 20mA E P P E P E P E E Select type of ba...

Page 12: ...ble lineariser To reveal the existing indicator function select FunC from the configuration menu and press P If the function is set as required press E to return to the menu or press the or button to...

Page 13: ...ese conditions are not complied with the indicator displays FaiL and aborts the calibration c If the zero current is greater than the span current the instrument will be reverse acting i e an increasi...

Page 14: ...between on and oFF When set as required press E to return to the tARE prompt in the configuration menu 5 10 Security code CodE Access to the instrument configuration menu may be protected by a four di...

Page 15: ...lling the tank with known incremental volumes and calibrating the indicator to display the sum of the increments at each break point The number of break points required should first be entered using t...

Page 16: ...14...

Page 17: ...a new break point before the displayed break point The calibration of existing break points is not changed but the identification number of all subsequent break points is increased by one dEL Remove a...

Page 18: ...ired press E to return to the 0 n prompt from which the the next break point can be selected using the or buttons When the required break point has been selected press P and set the required indicator...

Page 19: ...s does not reveal the cause of the fault it is recommended that the instrument is replaced This can be done without disconnecting power but while the indicator is disconnected the 4 20mA loop will be...

Page 20: ...output may be independently conditioned as a high or low alarm with a normally open or normally closed output in the non alarm condition When the 4 20mA current powering the indicator is removed both...

Page 21: ...19...

Page 22: ...section 8 3 3 SP1 Alarm setpoint 1 Adjusts the alarm setpoint The alarm is activated when the indicator display equals the setpoint See section 8 3 4 Hi Lo Alarm function Defines the alarm function a...

Page 23: ...or fail safe operation both alarm outputs should be conditioned to be open in the alarm condition nC To check or change the alarm output status select no nC from the alarm configuration menu and press...

Page 24: ...ving access to the indicator configuration menu Protection against accidental adjustment of the setpoints when the indicator is in the display mode is provided by a separate security code This direct...

Page 25: ...plus the displayed value to be represented or a low and a high setpoint plus the displayed value to be represented by the bargraph as shown in Fig 15 Fig 15 Displayed value and setpoints on bargraph T...

Page 26: ...backlight 8 4 1 Loop powering the backlight The backlight is loop powered by connecting it in series with the indicator 4 20mA input as shown in Fig 17 which increases the maximum indicator voltage dr...

Reviews: