15

When the required number of break-points have
been entered, return to the linearisation sub-menu
by pressing 

E

.  

The indicator will display the 'Add'

or 'dEL' prompt depending upon the last function
used.

Now that the number of break-points has been
entered, the input current at which each occurs
and the corresponding indicator display can be
defined by the ‘Pts’ sub-function.

Using the 

 or 

 button select  'PtS' from the sub-

menu and press 

P

 which will select the first break-

point '0 : n', where n is the total number of break-
points entered.  The selected break-point can be
changed using the 

 and 

 buttons.  When the

required break-point has been selected, set the
indicator input current to the exact value at which
the break-point is required and press 

P

.   Then

using the 

 and 

 buttons and the 

P

 button to

move between digits, enter the required indicator
display at this break-point.

When set as required, press the 

E

 

push-button

 

to

enter the required indicator display at this break-
point and return to the sub-menu from which the
next beak-point can be selected.

When all the break-points have been calibrated
pressing 

E

 

twice will return the indicator to the

‘CAL’ function in the configuration menu.

Note:  

The indicator input current must be adjusted

to the required value before the 

button is

operated to enter the required indicator display.

6.2  Lineariser calibration using the internal
       reference.

The ‘SEt’ function enables the lineariser to be
calibrated without the need for an accurate
external current source.  Throughout the
calibration the indicator input current may be any
value between 4 and 20mA.

The ‘SEt’ functions contains four sub-functions.

Display      Description of function

'Add'

Add a break-point

Adds a new break-point before the
displayed break-point.  The calibration
of existing break-points is not changed,
but the identification number of all
subsequent break-points is increased
by one.

'dEL'

Remove a break-point

Removes the displayed break-point and
joins the preceding break-point to the
following break-point with a straight
line.   The identification number of all
subsequent break-points is decreased
by one.

'in' 

Defines the current at which break-
point occurs

Enables the required current at each
break-point to be defined without
having to input an accurate input
current to the indicator.

'diSP'

Defines indicator display at break-
point

Enables the indicator display at each
break-point to be defined.

The number of break-points required should first
be entered using the 'Add' and 'dEL'  sub-
functions.  In both these sub-functions the indicator
initially displays the current break-point and the
total number of break-point being used as shown
below.

To add a break-point, using the 

 or 

 button

select 'SEt' from the configuration menu and press

P

 

which will result in the

 

'Add' sub-function prompt

being displayed. To enter the sub-function press 

P

which will reveal the current break-point and the
total number of break-points which have already
been entered.    Each subsequent operation of the

P

  push-button will introduce an additional break-

point up to the maximum of 17.  When adding a
break-point to a calibrated indicator, the insertion
position for the new break-point can be selected
using the 

 and 

 push-buttons.

The delete segment sub-function 'dEL' operates in
exactly the same way as the 'Add' sub-function
described above.   Once within the ‘dEL’ function
each time the 

P

 button is pressed a break-point is

removed. When deleting a break-point from a
calibrated indicator, the break-point to be deleted
can be selected using the 

 and 

 push-buttons.

The minimum number of  break-points is 2, break-
points 0 and 1.

Summary of Contents for BA507E

Page 1: ...Supplied by Call us on 44 0 118 916 9420 Email info 247able com com Installation Maintenance Instructions BA507E BA508E BA527E BA528E...

Page 2: ...rk Danehill Lower Earley Reading Berkshire RG6 4UT UK Tel 44 0 118 9311188 Email info able co uk Aberdeen Office Unit 6 Airside Business Park Kirkhill Industrial Estate Dyce Aberdeen AB21 0GT UK Tel 4...

Page 3: ...Issue 3 1st December 2012 BA507E BA527E BA508E BA528E General Purpose loop powered panel mounting indicators issue 3...

Page 4: ...error message 6 4 Lineariser under and over range 6 5 Lineariser default configuration 7 Maintenance 7 1 Fault finding during commissioning 7 2 Fault finding after commissioning 7 3 Servicing 7 4 Rout...

Page 5: ...splay any variable represented by the 4 20mA current e g temperature flow pressure or level The BA507E BA527E BA508E and the BA528E are not certified for use in explosive atmospheres For hazardous are...

Page 6: ...in display mode function has been enabled P E Access to configuration menu via optional security code Note BA527E and BA528E only If the indicator has been calibrated using the CAL function calibratio...

Page 7: ...el providing that the operating temperature is between 40 C and 70 C Figs 4A and 4B show the overall dimensions of the 96 x 48mm and the 144 x 72mm instruments together with the recommended panel cut...

Page 8: ...dovetail as shown in Fig 5 Push the knurled screw slightly forward to engage the thread and tighten by turning clockwise until it is just finger tight When both clamps are fitted ensure that the gaske...

Page 9: ...rd unclip the protruding end of the flexible strip by gently pushing it upwards and pulling it out of the enclosure Peel the existing scale card from the flexible strip and replace it with a new print...

Page 10: ...00 0000 Function FunC Std Std Display at 4mA Zero 0 0 0 00 Display at 20mA SPAn 100 0 100 00 Resolution rESn 1 digit 1 digit Bargraph start BarLo 0 00 Bargraph finish BarHi 100 00 P button in display...

Page 11: ...value Using ZEro function set required display at 4mA by pressing pressing and to move to the next digit Similarly using SPAn function set required display at 20mA E P P E P E P E E Select type of ba...

Page 12: ...ble lineariser To reveal the existing indicator function select FunC from the configuration menu and press P If the function is set as required press E to return to the menu or press the or button to...

Page 13: ...ese conditions are not complied with the indicator displays FaiL and aborts the calibration c If the zero current is greater than the span current the instrument will be reverse acting i e an increasi...

Page 14: ...between on and oFF When set as required press E to return to the tARE prompt in the configuration menu 5 10 Security code CodE Access to the instrument configuration menu may be protected by a four di...

Page 15: ...lling the tank with known incremental volumes and calibrating the indicator to display the sum of the increments at each break point The number of break points required should first be entered using t...

Page 16: ...14...

Page 17: ...a new break point before the displayed break point The calibration of existing break points is not changed but the identification number of all subsequent break points is increased by one dEL Remove a...

Page 18: ...ired press E to return to the 0 n prompt from which the the next break point can be selected using the or buttons When the required break point has been selected press P and set the required indicator...

Page 19: ...s does not reveal the cause of the fault it is recommended that the instrument is replaced This can be done without disconnecting power but while the indicator is disconnected the 4 20mA loop will be...

Page 20: ...output may be independently conditioned as a high or low alarm with a normally open or normally closed output in the non alarm condition When the 4 20mA current powering the indicator is removed both...

Page 21: ...19...

Page 22: ...section 8 3 3 SP1 Alarm setpoint 1 Adjusts the alarm setpoint The alarm is activated when the indicator display equals the setpoint See section 8 3 4 Hi Lo Alarm function Defines the alarm function a...

Page 23: ...or fail safe operation both alarm outputs should be conditioned to be open in the alarm condition nC To check or change the alarm output status select no nC from the alarm configuration menu and press...

Page 24: ...ving access to the indicator configuration menu Protection against accidental adjustment of the setpoints when the indicator is in the display mode is provided by a separate security code This direct...

Page 25: ...plus the displayed value to be represented or a low and a high setpoint plus the displayed value to be represented by the bargraph as shown in Fig 15 Fig 15 Displayed value and setpoints on bargraph T...

Page 26: ...backlight 8 4 1 Loop powering the backlight The backlight is loop powered by connecting it in series with the indicator 4 20mA input as shown in Fig 17 which increases the maximum indicator voltage dr...

Reviews: