background image

17

7.  MAINTENANCE

7.1 Fault finding during commissioning

If an indicator fails to function during
commissioning the following procedure should be
followed:

Symptom

Cause

Solution

No display

Incorrect wiring

Check wiring

There should be
0.6 to 1.2V
between terminals
1 & 3 with terminal
1 positive.

With an optional
loop powered
backlight, there
should be 3.4 to
5V between
terminals 3 & 12
with terminal 12
positive.

No display
0V between
terminals 1 & 3.

Incorrect wiring
or no power
supply

Check supply
voltage and
voltage drop
caused by all the
instruments in the
loop.

All decimal points
flashing.

Underrange  if
 –ve sign
displayed or
overrange.

Recalibrate the
numerical display.

Unstable display

4/20mA input is
noisy.

Eliminate ripple on
4/20mA power
supply and/or
decrease indicator
resolution.

Unable to enter
configuration
menu.

Incorrect
security code
entered.

Enter correct
security code, or
contact BEKA if
the code has been
lost.

7.2  Fault finding after commissioning

ENSURE PLANT SAFETY BEFORE

STARTING MAINTENANCE

If an indicator fails after it has been functioning
correctly follow the procedure shown in section
7.1.  If this does not reveal the cause of the fault, it
is recommended that the instrument is replaced.
This can be done without disconnecting power, but
while the indicator is disconnected the 4/20mA
loop will be open circuit.

7.3  Servicing

All BA507E, BA527E, BA508E and BA528E loop
powered indicators are interchangeable if the
required optional backlight and alarms are fitted.  A
single spare instrument may quickly be
recalibrated to replace any instrument that is
damaged or fails.   No attempt should be made to
repair instruments at component level.

We recommend that faulty instruments
are returned to BEKA associates or to
your local BEKA agent for repair.

7.4 Routine maintenance

The mechanical condition of the instrument and
electrical calibration should be regularly checked.
The interval between inspections depends upon
environmental conditions.  We recommend that
initially instrument calibration should be checked
annually.

7.5  Guarantee

Indicators which fail within the guarantee period
should be returned to BEKA associates or our local
agent.  It is helpful if a brief description of the fault
symptoms is provided.

7.6  Customer comments

BEKA associates is always pleased to receive
comments from customers about our products and
services.  All communications are acknowledged
and whenever possible, suggestions are
implemented.

Summary of Contents for BA507E

Page 1: ...Supplied by Call us on 44 0 118 916 9420 Email info 247able com com Installation Maintenance Instructions BA507E BA508E BA527E BA528E...

Page 2: ...rk Danehill Lower Earley Reading Berkshire RG6 4UT UK Tel 44 0 118 9311188 Email info able co uk Aberdeen Office Unit 6 Airside Business Park Kirkhill Industrial Estate Dyce Aberdeen AB21 0GT UK Tel 4...

Page 3: ...Issue 3 1st December 2012 BA507E BA527E BA508E BA528E General Purpose loop powered panel mounting indicators issue 3...

Page 4: ...error message 6 4 Lineariser under and over range 6 5 Lineariser default configuration 7 Maintenance 7 1 Fault finding during commissioning 7 2 Fault finding after commissioning 7 3 Servicing 7 4 Rout...

Page 5: ...splay any variable represented by the 4 20mA current e g temperature flow pressure or level The BA507E BA527E BA508E and the BA528E are not certified for use in explosive atmospheres For hazardous are...

Page 6: ...in display mode function has been enabled P E Access to configuration menu via optional security code Note BA527E and BA528E only If the indicator has been calibrated using the CAL function calibratio...

Page 7: ...el providing that the operating temperature is between 40 C and 70 C Figs 4A and 4B show the overall dimensions of the 96 x 48mm and the 144 x 72mm instruments together with the recommended panel cut...

Page 8: ...dovetail as shown in Fig 5 Push the knurled screw slightly forward to engage the thread and tighten by turning clockwise until it is just finger tight When both clamps are fitted ensure that the gaske...

Page 9: ...rd unclip the protruding end of the flexible strip by gently pushing it upwards and pulling it out of the enclosure Peel the existing scale card from the flexible strip and replace it with a new print...

Page 10: ...00 0000 Function FunC Std Std Display at 4mA Zero 0 0 0 00 Display at 20mA SPAn 100 0 100 00 Resolution rESn 1 digit 1 digit Bargraph start BarLo 0 00 Bargraph finish BarHi 100 00 P button in display...

Page 11: ...value Using ZEro function set required display at 4mA by pressing pressing and to move to the next digit Similarly using SPAn function set required display at 20mA E P P E P E P E E Select type of ba...

Page 12: ...ble lineariser To reveal the existing indicator function select FunC from the configuration menu and press P If the function is set as required press E to return to the menu or press the or button to...

Page 13: ...ese conditions are not complied with the indicator displays FaiL and aborts the calibration c If the zero current is greater than the span current the instrument will be reverse acting i e an increasi...

Page 14: ...between on and oFF When set as required press E to return to the tARE prompt in the configuration menu 5 10 Security code CodE Access to the instrument configuration menu may be protected by a four di...

Page 15: ...lling the tank with known incremental volumes and calibrating the indicator to display the sum of the increments at each break point The number of break points required should first be entered using t...

Page 16: ...14...

Page 17: ...a new break point before the displayed break point The calibration of existing break points is not changed but the identification number of all subsequent break points is increased by one dEL Remove a...

Page 18: ...ired press E to return to the 0 n prompt from which the the next break point can be selected using the or buttons When the required break point has been selected press P and set the required indicator...

Page 19: ...s does not reveal the cause of the fault it is recommended that the instrument is replaced This can be done without disconnecting power but while the indicator is disconnected the 4 20mA loop will be...

Page 20: ...output may be independently conditioned as a high or low alarm with a normally open or normally closed output in the non alarm condition When the 4 20mA current powering the indicator is removed both...

Page 21: ...19...

Page 22: ...section 8 3 3 SP1 Alarm setpoint 1 Adjusts the alarm setpoint The alarm is activated when the indicator display equals the setpoint See section 8 3 4 Hi Lo Alarm function Defines the alarm function a...

Page 23: ...or fail safe operation both alarm outputs should be conditioned to be open in the alarm condition nC To check or change the alarm output status select no nC from the alarm configuration menu and press...

Page 24: ...ving access to the indicator configuration menu Protection against accidental adjustment of the setpoints when the indicator is in the display mode is provided by a separate security code This direct...

Page 25: ...plus the displayed value to be represented or a low and a high setpoint plus the displayed value to be represented by the bargraph as shown in Fig 15 Fig 15 Displayed value and setpoints on bargraph T...

Page 26: ...backlight 8 4 1 Loop powering the backlight The backlight is loop powered by connecting it in series with the indicator 4 20mA input as shown in Fig 17 which increases the maximum indicator voltage dr...

Reviews: