background image

4

2.1  Controls

The indicators are controlled and calibrated via
four front panel push-buttons located below the
display.    In the display mode i.e. when the
indicator is displaying a process variable, these
push-buttons have the following functions:

P

While this button is pushed the
indicator will display the input current in
mA, or as a percentage of the
instrument span depending upon how
the indicator has been conditioned.
When the button is released the normal
display in engineering units will return.
The function of this push-button is
modified when optional alarms are
fitted to the indicator.

While this button is pushed the
indicator will display the numerical
value and analogue bargraph* the
indicator has been calibrated to display
with a 4mA

Φ

 

input.  When released the

normal display in engineering units will
return.

While this button is pushed the
indicator will display the numerical
value and analogue bargraph* the
indicator has been calibrated to display
with a 20mA

Φ

 input.  When released

the normal display in engineering units
will return.

E

No function in the display mode unless
the tare function is being used.

P +

 

Firmware number followed by version.

P + 

Direct access to the alarm setpoints
when optional alarms are fitted to the
indicator and the ‘ACSP’ access
setpoints in display mode function has
been enabled.

P + E

Access to configuration menu via
optional security code.

Note:

*

  BA527E and BA528E only

Φ

 

If the indicator has been calibrated
using the CAL function, calibration
points may not be 4 and 20mA.

3. APPLICATIONS

3.1  Transmitter loops

All the models may be connected in series with
any 4/20mA current loop and calibrated to display
the measured variable or control signal in
engineering units.

Figs 2 illustrate a typical application in which an
indicator is connected in series with a 2-wire
transmitter.

Fig 2  Indicator in a transmitter loop

Considering the example shown in Fig 2, the sum
of the maximum voltage drops of all the
components in the loop must be less than the
minimum power supply voltage.

Minimum operating voltage of 2-wire Tx

10.0

Maximum voltage drop caused by controller

5.0

Maximum voltage drop caused by BA507E

1.3

Maximum voltage caused by cables

0.4

                                                                              _____

16.7V

Therefore at 20mA in this example the power
supply must have a minimum output of 16.7V

3.2  Remote indication

All the indicators may be driven from a 4/20mA
signal to provide a remote indication.   Fig 3 shows
a typical application in which the 4/20mA output
from a gas analyser is connected to a BA507E
loop powered indicator to provide a remote
indication of the analyser’s output. Again it is
necessary to ensure that the voltage capability of
the 4/20mA source is greater than the sum of the
voltage drops introduced by the indicator and the
cable resistance.

Summary of Contents for BA507E

Page 1: ...Supplied by Call us on 44 0 118 916 9420 Email info 247able com com Installation Maintenance Instructions BA507E BA508E BA527E BA528E...

Page 2: ...rk Danehill Lower Earley Reading Berkshire RG6 4UT UK Tel 44 0 118 9311188 Email info able co uk Aberdeen Office Unit 6 Airside Business Park Kirkhill Industrial Estate Dyce Aberdeen AB21 0GT UK Tel 4...

Page 3: ...Issue 3 1st December 2012 BA507E BA527E BA508E BA528E General Purpose loop powered panel mounting indicators issue 3...

Page 4: ...error message 6 4 Lineariser under and over range 6 5 Lineariser default configuration 7 Maintenance 7 1 Fault finding during commissioning 7 2 Fault finding after commissioning 7 3 Servicing 7 4 Rout...

Page 5: ...splay any variable represented by the 4 20mA current e g temperature flow pressure or level The BA507E BA527E BA508E and the BA528E are not certified for use in explosive atmospheres For hazardous are...

Page 6: ...in display mode function has been enabled P E Access to configuration menu via optional security code Note BA527E and BA528E only If the indicator has been calibrated using the CAL function calibratio...

Page 7: ...el providing that the operating temperature is between 40 C and 70 C Figs 4A and 4B show the overall dimensions of the 96 x 48mm and the 144 x 72mm instruments together with the recommended panel cut...

Page 8: ...dovetail as shown in Fig 5 Push the knurled screw slightly forward to engage the thread and tighten by turning clockwise until it is just finger tight When both clamps are fitted ensure that the gaske...

Page 9: ...rd unclip the protruding end of the flexible strip by gently pushing it upwards and pulling it out of the enclosure Peel the existing scale card from the flexible strip and replace it with a new print...

Page 10: ...00 0000 Function FunC Std Std Display at 4mA Zero 0 0 0 00 Display at 20mA SPAn 100 0 100 00 Resolution rESn 1 digit 1 digit Bargraph start BarLo 0 00 Bargraph finish BarHi 100 00 P button in display...

Page 11: ...value Using ZEro function set required display at 4mA by pressing pressing and to move to the next digit Similarly using SPAn function set required display at 20mA E P P E P E P E E Select type of ba...

Page 12: ...ble lineariser To reveal the existing indicator function select FunC from the configuration menu and press P If the function is set as required press E to return to the menu or press the or button to...

Page 13: ...ese conditions are not complied with the indicator displays FaiL and aborts the calibration c If the zero current is greater than the span current the instrument will be reverse acting i e an increasi...

Page 14: ...between on and oFF When set as required press E to return to the tARE prompt in the configuration menu 5 10 Security code CodE Access to the instrument configuration menu may be protected by a four di...

Page 15: ...lling the tank with known incremental volumes and calibrating the indicator to display the sum of the increments at each break point The number of break points required should first be entered using t...

Page 16: ...14...

Page 17: ...a new break point before the displayed break point The calibration of existing break points is not changed but the identification number of all subsequent break points is increased by one dEL Remove a...

Page 18: ...ired press E to return to the 0 n prompt from which the the next break point can be selected using the or buttons When the required break point has been selected press P and set the required indicator...

Page 19: ...s does not reveal the cause of the fault it is recommended that the instrument is replaced This can be done without disconnecting power but while the indicator is disconnected the 4 20mA loop will be...

Page 20: ...output may be independently conditioned as a high or low alarm with a normally open or normally closed output in the non alarm condition When the 4 20mA current powering the indicator is removed both...

Page 21: ...19...

Page 22: ...section 8 3 3 SP1 Alarm setpoint 1 Adjusts the alarm setpoint The alarm is activated when the indicator display equals the setpoint See section 8 3 4 Hi Lo Alarm function Defines the alarm function a...

Page 23: ...or fail safe operation both alarm outputs should be conditioned to be open in the alarm condition nC To check or change the alarm output status select no nC from the alarm configuration menu and press...

Page 24: ...ving access to the indicator configuration menu Protection against accidental adjustment of the setpoints when the indicator is in the display mode is provided by a separate security code This direct...

Page 25: ...plus the displayed value to be represented or a low and a high setpoint plus the displayed value to be represented by the bargraph as shown in Fig 15 Fig 15 Displayed value and setpoints on bargraph T...

Page 26: ...backlight 8 4 1 Loop powering the backlight The backlight is loop powered by connecting it in series with the indicator 4 20mA input as shown in Fig 17 which increases the maximum indicator voltage dr...

Reviews: