33

new access code.   The Timer will display 

0000  

with

one digit flashing.  The flashing digit may be adjusted
using   the  

*

  or  

&

  push   button,   when   set   as

required operating the 

(

 button will transfer control

to   the   next   digit.       When   all   the   digits  have   been
entered   press  

)

  twice   to   return   to   the  

AC5Et   t

prompt   in   the   configuration   menu.   The   revised
access code will be activated when the BA377E-SS
is returned to the display mode.

Please contact BEKA associates sales department if
the access code is lost.

6.5.16 Direction of count:   

uP or dn

The Timer may be configured to

 time-up

 from zero to

the set time  

5Et t

  while displaying elapsed time, or

to  

time-down

  from the set time  

5Et t

  to zero while

displaying the remaining time.

When   the   repeat   timing   cycle   function  

CYCLE5

  is

enabled,   it   is   recommended   that   a   down   count   is
selected   so   that   the   progress   of   the   timer  can   be
observed with a known completion time i.e zero.   If
set as an up counter, elapsed will be displayed, but

5et t

 at which the Timer will stop is not shown.

To check the direction of count, select 

uP or dn

 from

the   configuration   menu   and   press  

(

  which   will

reveal the existing setting which can be changed by
pressing  the  

*

  or  

&

  button  followed  by  the  

)

button   to   enter   the   selection   and   return   to   the
configuration menu.

6.5.17 Power Fail:   

P-FAiL

Defines   how   the   Timer   powers-up   and   functions
when   power   is   restored   after   a   power   supply
interruption.     Three   options   are   available,  

idle

,

Pau5e

 and 

continue. 

idle

The Timer is stopped in the state it achieves

when it has timed-up to 

5et t

 or timed-down

to 

0000

,

,

with the elapsed or remaining time

when power was lost shown on the upper
display.   The Timer must be reset before it
can be restarted.   If the repeat timing cycle
is in use the number of cycles completed
will be lost when the Timer is reset.

Pau5e

The Timer is stopped in the state it achieves

following   receipt   of   a   stop   input   to   pause
timing.     The   elapsed   or   remaining   time
when power was lost is shown on the upper
display.   Timing   resumes   when   a   start
instruction is received.  If a start input exists
when   power   is   restored   timing   will   start
immediately.

Continue

When   power   is   restored   the  Timer   will

continue from where it stopped without any
manual  intervention.   To check  or  change
the   function,   select  

P-fail

  from   the

configuration menu and press 

(

 which will

reveal   the   existing   setting   which   can   be
changed by pressing the  

*

  or  

&

  button

followed   by   the  

)

  button   to   enter   the

selection   and   return   to   the   configuration
menu.

6.5.18 Local reset:     

LoC r5Et

The Local reset function contains two separate sub-
functions    

rE5Et

 

.

 

enbl

  and  

clr   Gtot

  which   when

enabled allow the Timer and the grand total to be
reset via the instrument's front panel push buttons
while the Timer is in the display mode.

6.5.19 Local total reset:   

r5Et

 

.

 

enbl

rE5Et.enbl

 is a sub-function in the 

Loc r5Et

 function

which when activated allows an operator to reset the
Timer  from  the  display  mode   by  operating  the  

*

and  

&

  push buttons simultaneously for more than

three seconds.

To check or change the local total reset select      

LoC

r5Et

 in the configuration menu and press 

(

 which

will reveal the  

LoC r5Et

  prompt, press  

(

  again to

show if the local total reset is  

on

  or  

oFF

.     If set as

required operate the 

)

 button twice to return to the

configuration   menu,   or   the  

*

  or  

&

  button   to

change the setting followed by the 

)

 button twice to

enter the change and return to the 

LoC

 

.

 

r5Et

 prompt

in the configuration menu.

Note:

The   Timer   may   also   be   reset   remotely   by
connecting   terminals  RS1   and   RS2   together
for more than one second.  See section 3.1.8
or 3.2.8

6.5.20 Local grand total reset:   

Clr Gtot

The grand total is the total run-time of the Timer that
may be viewed by operating the  

)

  and  

*

  push

buttons simultaneously in the display mode.   When
activated   

clr Gtot

  allows an operator to reset the

grand total display to zero from the display mode by
operating   the  

)

  and  

*

  push   buttons

simultaneously for more than ten seconds.

Clr Gtot

 is a sub-function in the 

LoC r5Et

 menu.  To

check or change the setting select  

LoC r5Et

  in the

configuration menu and press  

(

  which will reveal

rE5Et

 

.

 

enbl

.   Using  the  

&

  or  

 button  select

Clr Gtot

 and press 

(

 which will show if local grand

total reset is  

on

  or  

oFF

.     If set as required operate

the  

)

  button   twice   to   return   to   the   configuration

menu, or the 

&

 or 

*

 button to change the setting

followed by the 

)

 button twice to enter the change

and   return   to   the  

LoC   r5Et

  prompt   in   the

configuration menu.

Summary of Contents for BA377E-SS

Page 1: ...Issue 6 4th May 2021 BA377E SS Rugged one input intrinsically safe Timer or Clock Issue 6...

Page 2: ...ear sealing kit 6 OPERATION AS A TIMER 6 1 Initialisation 6 2 Controls when configured as a Timer 6 3 Displays when configured as a Timer 6 4 Timer structure 6 5 Configuration as a Timer 6 5 1 Accessi...

Page 3: ...YnC t 9 4 7 Control output 1 Optional oP1 9 4 8 Enable Control output 1 EnbL 9 4 9 On and off times oP 1 on 1 oP 1 off 1 oP 1 on 2 oP 1 off 2 9 4 10 Control output 2 Optional oP2 9 4 11 Enable control...

Page 4: ...plied with each instrument 2 INTRINSIC SAFETY CERTIFICATION The BA377E SS has IECEx and ATEX gas certification This section of the instruction manual describes ATEX gas certification IECEx and other a...

Page 5: ...28V dc Ii 200mA dc Pi 0 84W Any certified Zener barrier or galvanic isolator with output safety parameters equal to or less than these limits may be used to power the BA377E SS The maximum equivalent...

Page 6: ...unlikely to make a significant difference to the allowable cable parameters 2 5 2 Sensors that require energising Switch contacts proximity detectors and open collector sensors require energising whic...

Page 7: ...application Almost any intrinsically safe relay with certification permitting the contacts to be connected to equipment in the hazardous area may be used When used as a Timer the BA377E SS may also b...

Page 8: ...internally connected together as shown in Fig 15 If any of these terminals are earthed as shown in Figs 1 2 the other common terminals should only be connected to the same earth i e the barrier busbar...

Page 9: ...e input must be maintained not momentary The BA377E SS input is not used when the instrument is configured as a Clock No Zener barrier is required in series with the input if the intrinsically safe se...

Page 10: ...n Uo 28V dc Io 200mA dc Po 0 84W The BA377E SS Timer may therefore be directly connected to and controlled by most certified intrinsically safe high level voltage signals The maximum permitted cable p...

Page 11: ...requirements for simple apparatus This allows the control output terminals A1 A2 and A3 A4 to be connected to almost any intrinsically safe circuit protected by a Zener barrier having output paramete...

Page 12: ...the hazardous area although it may be difficult to find isolators for some types of sensor The BA377E SS input energising link should be fitted to suite the output of the galvanic isolator not the se...

Page 13: ...hese requirements The BA377E SS contains a configurable debounce circuit to prevent false triggering of the instrument Three levels of debounce protection are available See section 6 5 6 3 2 4 Open co...

Page 14: ...may be used but a galvanic isolator or IS relay is required to transfer the contact closure into the hazardous area Fig 5 illustrates how a BA377E SS Timer may be reset from both the safe and the haza...

Page 15: ...ections 3 1 and 3 2 When correctly installed the BA377E SS Timer or Clock does not invalidate the certification of the Ex e Ex n or Ex p panel enclosure allowing installation with higher power control...

Page 16: ...idate the Ex p panel s impact and ingress protection as the front of the Timer or Clock complies with Ex p impact and ingress requirements Although mounted in an Ex p panel enclosure the BA377E SS rem...

Page 17: ...r Clock s captive gasket and ensure that it is not damaged before inserting the Timer or Clock into the panel enclosure aperture c If the enclosure panel is less than 1 0mm thick or is non metallic an...

Page 18: ...wing the requested units of measurement if this information is not supplied when the instrument is ordered a blank card will be fitted A pack of self adhesive scale cards printed with common units of...

Page 19: ...g the units of measurement specified when the instrument was ordered if the units are not specified a blank scale card will be fitted A pack of scale cards pre printed with common units of measurement...

Page 20: ...er cycle can be accomplished via the front panel push buttons or by a remote contact A grand total time is maintained which can be viewed by operating the front panel push buttons It may be reset to z...

Page 21: ...de See 6 5 15 Shows in succession firmware version number instrument function elap5e and any output accessories that are fitted A Dual Control Outputs Access to configuration menu 6 3 Displays when co...

Page 22: ...delay time automatically returns to Running Complete Entered automatically from Running when there are no more timing cycles to perform When the CYCLE5 function is enabled the timing cycle can be rep...

Page 23: ...e instrument using the or push button to adjust the flashing digit and the push button to transfer control to the next digit If the correct code has been entered pressing will cause the first paramete...

Page 24: ...e input by linking terminals 3 4 See section 6 5 5 dEbounCE Defines the level of debounce applied to the input to prevent false functioning dEFAuLt HEAVY LiGHt See section 6 5 6 Display Summary of fun...

Page 25: ...m the display mode to 5Et t and r5t dela See section 6 5 15 Display Summary of function uP or dn Direction of count Defines whether the Timer times down from 5Et t to zero or times up from zero to the...

Page 26: ...ontrol output 1 See section 6 5 26 CLr Gtot Resets grand total to zero This function resets the grand total which represents the total Timer run time from within the configuration menu when CLr YE5 is...

Page 27: ...as required press twice to return to the configuration menu or repeatedly press the or button until the required type of input is displayed and then press twice to return to the configuration menu One...

Page 28: ...of count selected in the uP or dn function oFF Lower display disabled If the CYCLE5 function is enabled the following three options are available 5td Lower display shows the number of cycles requeste...

Page 29: ...ess which will reveal the existing setting The required units can be selected by pressing the or button followed by the button to enter the selection and return to the configuration menu The options a...

Page 30: ...30...

Page 31: ...31...

Page 32: ...o the next digit When set as required enter the selection and return to the cycl cnt prompt in the sub menu by operating the button 6 5 14 Restart delay r5t dela This sub function defines the time del...

Page 33: ...tely Continue When power is restored the Timer will continue from where it stopped without any manual intervention To check or change the function select P fail from the configuration menu and press w...

Page 34: ...figuration example in section 7 2 of this manual illustrate the use of the control outputs Further examples can be found in Application Guide AG374 which is available on the BEKA website 6 5 22 Contro...

Page 35: ...n be independently configured to turn on and off when the Timer is any of it s five states It s functions and configuration are identical to control output 1 described in sections 6 5 21 to 6 5 25 The...

Page 36: ...azardous area contact is closed The display is required in hours and minutes within the hazardous area and is to be reset to zero by a push button located in the same hazardous area not by the instrum...

Page 37: ...n is operated Fig 19 Control of valve in a hazardous area The required instrument configuration for this example are shown below Function Display Setting Access code CodE 0000 Function FunCtion ELAP5E...

Page 38: ...ct BEKA if code is lost 8 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE Live maintenance is permitted on intrinsically safe equipment installed in a hazardous are...

Page 39: ...e regularly checked Inspection frequency should be chosen to suit the environmental conditions 8 5 Guarantee Instruments which fail within the guarantee period should be returned to BEKA associates or...

Page 40: ...tialisation the instrument will display a flashing display which is a request for the local time to be entered The clock will not start to function until a display time has been entered or the remote...

Page 41: ...hroughout this manual push buttons are shown as and and legends displayed by the Clock are shown in a seven segment font as they appear on the instrument e g di5PLAY and CodE Access to the configurati...

Page 42: ...42...

Page 43: ...Optional Control output 1 can turn on output closed and off output open twice in each twenty four hour period This function contains five sub function EnbL Enables output 1 and defines if it turns on...

Page 44: ...et time is entered the Clock will display a flashing 00 00 00 or 00 00 for 24 hour formats or A12 00 00 or A12 00 for 12 hour formats To adjust the clock set time select 5Et from the configuration men...

Page 45: ...tered return to the configuration menu by pressing the button twice 9 4 10 Control output 2 Optional oP2 Control output 2 is an optional factory fitted output which can be configured to turn on output...

Page 46: ...e display mode may be protected by a four digit alphanumeric security code which must be entered to gain access Default security code 0000 allows unrestricted access With ACCd displayed press to enter...

Page 47: ...ng will then change the instrument to a Clock and return the display to FunCtion in the configuration menu Step 3 Select display format Using the or button select di5PLAY in the configuration menu and...

Page 48: ...ss to the configuration menu Using the and buttons select CodE from the configuration menu and press which will reveal 0000 with the first digit flashing This example requires the security code to be...

Page 49: ...377E SS fails after it has been functioning correctly as a Clock the following table may help to identify the cause of the failure Symptom Cause Check No display No power supply That there is between...

Page 50: ...combustible dust in air is likely to occur occasionally in normal operation Zone 22 explosive atmosphere in the form of a cloud of combustible dust in air is not likely to occur in normal operation b...

Page 51: ...ssible to mount the intrinsically safe interface in the same Ex t panel enclosure as the Timer or Clock if in normal operation the outside temperature of the enclosure is not affected The Timer or Clo...

Page 52: ...the main section of this manual and both refer to the same standards Therefore the ATEX installation requirements specified in sections 2 3 and Appendix 1 of this manual may be used for IECEx installa...

Page 53: ...y therefore also be used for US and Canadian installations subject to compliance with the local codes of practice ETL and cETL intrinsic safety codes CL I Div 1 Groups A B C D T5 US IS gas Div cert CL...

Page 54: ...54...

Page 55: ...55...

Page 56: ...56...

Page 57: ...57...

Page 58: ...58...

Page 59: ...59...

Page 60: ...60...

Page 61: ...61...

Page 62: ...62...

Page 63: ...63...

Page 64: ...64...

Page 65: ...65...

Reviews: