9.5.3 4/20mA output:
4-20 oP
Access the Counter's configuration menu as
described in section 6.2. Using the
&
or
*
push
buttons scroll though the menu until
4-20 oP
is
displayed, pressing
(
will then access the 4/20mA
output sub-menu which is shown in Fig 20.
9.5.4 Enable 4/20mA output:
EnbL
This function allows the 4/20mA output to be
disabled or enabled without altering any of the
4/20mA output parameters. Using the
&
or
*
push button select
EnbL
in the
4-20 oP
sub-menu
and press
(
to reveal the existing setting
on
or
oFF
.
The function can be changed by pressing the
&
or
*
push button followed by the
)
button to return
to
EnbL
prompt.
Note:
When the 4/20mA output is disabled by
selecting
oFF
, the output is a constant
3.5mA irrespective of the instrument
display.
9.5.5 Select rate or total source:
4-20tYPE
The 4/20mA output current can represent the
Counter's rate or total display, this should be defined
before any other current output functions are
adjusted.
Using the
&
or
*
push button select
4-20tYPE
in
the 4/20mA output sub-menu and press
(
to reveal
the existing setting
totAL
or
rAtE
. The function can
be changed by pressing the
&
or
*
push button
followed by the
)
button to return to the
4-20tYPE
prompt in the sub-menu.
9.5.6 Display which corresponds to 4mA
output:
4
.
000
The Counter display which corresponds to a
4.000mA output current is defined by this function.
Using the
&
or
*
push button select
4.000
in the
4/20mA output sub-menu and press
(
which will
reveal the existing rate or total display with one digit
flashing. The required display can be entered using
the
&
or
*
push button to adjust the flashing digit
and the
(
button to transfer control to the next
digit. When set as required press
)
to enter the
value and return to the
4
.
000
prompt in the 4/20mA
output sub-menu.
9.5.7 Display which corresponds to 20mA
output:
20
.
000
The Counter display which corresponds to a
20.000mA output current is defined by this function.
Using the
&
or
*
push button select
20
.
000
in the
4/20mA output sub-menu and press
(
which will
reveal the existing rate or total display with one digit
flashing. The required display can be entered using
the
&
or
*
push button to adjust the flashing digit
and the
(
button to transfer control to the next digit.
37