1. DESCRIPTION

The BA358C is an intrinsically safe 4/20mA
loop-powered rate totaliser primarily
intended for use with flowmeters.   The
instrument simultaneously displays the rate
of flow and the total flow in engineering units
on two separate displays.  The BA358C only
introduces a 1.1V drop which allows it to be
installed into almost any 4/20mA flow loop.
No additional power supply or battery is
required.

The BA358C has been certified intrinsically
safe by European Notified Body Intertek
Testing Sevices (ITS) to the ATEX Directive
94/9/EC.  The EC-Type Examination
Certificate specifies that under fault
conditions the voltage, current and power at
input terminals 1 and 3 will not exceed those
specified for simple apparatus in Clause 5.4
of EN50020:1994.

Safety approvals from authorities outside
Europe are being obtained, please contact
BEKA associates for the latest information.

Housed in a robust 72 x 144 panel mounting
DIN enclosure, the BA358C has an IP65
front panel which will not support a static
charge, and is supplied with a gasket to seal
the joint between the instrument and the
panel.

2.  OPERATION

Fig 1 shows a simplified block diagram of a
BA358C.  The 4/20mA input current flows
through resistor R1 and forward biased
diode D1.  The voltage developed across
D1, which is relatively constant, is multiplied
by a switch mode power supply and used to
power the instrument.  The voltage
developed across R1, which is proportional
to the 4/20mA input current, provides the
input signal for the analogue to digital
converter.

Each time a 4/20mA current is applied to the
instrument, initialisation is performed.  After
a short delay the following display sequence
occurs:

All segments of the display are activated
for about 3 seconds.

Decimal points on large display are
sequentially activated for about 3
seconds.

Rate display and totaliser start to function
using calibration information stored in the
instrument's permanent memory.

If the 4/20mA current is disconnected during
operation the latest total and grand total are
stored in permanent memory.

Fig 1  Simplified block diagram of BA358C

2.1  Controls

The BA358C is controlled and calibrated via
four front panel push-button switches.  In the
display mode i.e. when the instrument is
displaying rate of flow and total flow, these
switches have the following functions:

Summary of Switch Functions

P

Displays input current in mA or
as a percentage of span.

Down

Shows rate display calibration at
4mA input

Up

Shows rate display calibration at
20mA input

E+Down

Grand total –
displays least significant 8 digits

E+Up

Grand total –
displays most significant 8
digits.

Down 

Resets total display

+Up

programmable function

Summary of Contents for BA358C

Page 1: ...October 2010 BA358C Intrinsically safe 4 20mA loop powered panel mounting rate totaliser Issue 4 Certification information label Rate display Annunciators for optional alarms Rotating flow indicator T...

Page 2: ...1 Timebase 6 12 Function of the P push button 6 13 Total scale factor 6 14 Percentage clip off 6 15 Local reset of total display 6 16 Security code 6 17 Over and under range 7 Calibration Examples 7 1...

Page 3: ...sed diode D1 The voltage developed across D1 which is relatively constant is multiplied by a switch mode power supply and used to power the instrument The voltage developed across R1 which is proporti...

Page 4: ...eds 4mA 3 INTRINSIC SAFETY CERTIFICATION 3 1 ATEX certificate The BA358C has been issued with an EC Type Examination Certificate by Notified Body Intertek Testing Services ITS formerly ERA Technology...

Page 5: ...Zones gas groups and T rating The BA358C has been certified to show compliance with the requirements for Group II Category 1G equipment EEx ia IIC T5 When connected to a suitable system the instrumen...

Page 6: ...dication of rate and total flow within a hazardous area The type of interface is not critical either a Zener barrier or a galvanic isolator may be used providing that Uo Io and Po are not exceeded If...

Page 7: ...esetting from the safe area via a single channel diode return Zener barrier A certified intrinsically safe relay or certified opto isolator may also be used Fig 3B shows how the total display may be r...

Page 8: ...lective displays there is little degradation of contrast when viewed from above the centre line but slight degradation may be noticeable when the instrument is fitted with a backlight Fig 4 BA358C dim...

Page 9: ...in the rate display is defined by the d p function To simplify calibration the BA358C uses floating point arithmetic moving the rate display decimal point position will therefore affect totalisation T...

Page 10: ...of 0 00 with 4mA input and 100 00 with 20mA input The total scale factor will be set to 1 0000 with a timebase of flow per second The instrument can easily be recalibrated on site 6 3 Summary of progr...

Page 11: ...input current in milliamps or the input as a percentage when the P push button is operated in the display mode Select PC for of span and 4 20 to display current See section 6 12 Display Description o...

Page 12: ...cimal point clip off to adjust value Press or between 0 and 10 or and pressing Define Security Enter by Code to move to next digit Local reset or Fig 7B Programme Structure CLr Gtot E E E E E E E E P...

Page 13: ...or and Similarly set the required full scale display accurate 20mA input current scale display using an Similarly set the required full to move to next digit pressing or and set required zero display...

Page 14: ...s Operating the P push button will toggle control between the two displays When both decimal points have been correctly positioned press E to return to the main menu If the application requires flow r...

Page 15: ...ay 0000 Using the Up and Down buttons and the P button to move to the next digit enter the password SurE S is entered as 5 Pressing E will then give access to the sub menu 6 9 1 AC rejection FrE WARNI...

Page 16: ...our Tb 3600 3600 Select the required divisor and press E to return to the main menu 6 12 Function of the P push button C P This parameter defines the function of the P push button when the BA358C is i...

Page 17: ...lect CLIP OFF from the main menu and press P to reveal the current setting This clip off threshold is shown as a percentage of total flow and may be adjusted in one percent increments using the Up or...

Page 18: ...ction 7 1 describes the preferred method of calibration using an external traceable 4 20mA calibrator Section 7 2 contains an example of calibration using the BA358C internal 4 and 20mA references whi...

Page 19: ...git of the total display flashing Press the Up or Down push button until the second least significant digit and following decimal point of the total display flash This gives the required total display...

Page 20: ...to the main menu by pressing E Step 12 Reset the grand total to zero To reset the grand total to zero select CLr Gtot from the main menu and press P which will cause the instrument to display Clr no T...

Page 21: ...multaneously pressing P and E Assuming a security code has not already been entered the instrument will respond by displaying root which is the first function in the main menu Steps Perform as describ...

Page 22: ...terminals 1 3 No power supply Confirm that a 4 20mA current is flowing in the loop Unstable rate display 4 20mA current is noisy or the flow signal is unstable Eliminate source of electrical noise Red...

Page 23: ...ons available for a rate alarm and shows which are fail safe i e output is in the alarm condition open when the 4 20mA input current is zero Similarly when programmed as a total alarm the output shoul...

Page 24: ...nt capacitance and inductance of each BA358C alarm output is Ci 40nF Li 20 H The maximum permissible cable parameters for the alarm circuit will be the figures specified for the barrier or isolator le...

Page 25: ...veal the current setting The function can be changed by pressing the Up or Down button followed by the E button to return to the alarm menu 9 3 5 Type of alarm tYPE This function conditions the alarm...

Page 26: ...Down button followed by the E button to return to the alarm menu 9 3 9 Hysteresis HStr Hysteresis is only available on rate alarms During programming hysteresis is shown in the units of rate the BA358...

Page 27: ...This direct access menu is enabled and a separate security code entered from the AcSP function in the main programme menu To change the menu parameters select AcSP from the programme menu and press P...

Page 28: ...is segregated from the measuring circuit and has been certified as a separate intrinsically safe circuit but it does not comply with the requirements for simple apparatus Systems certificates for use...

Page 29: ...ere the instrument is likely to be damaged by impact an additional front cover is available The BA398 is a robust transparent cover which is secured to the panel by six screws and sealed with a neopre...

Page 30: ...missioning 8 1 after commissioning 8 2 Flow indicator 2 2 Flow transmitter loops 4 1 Galvanic isolators 4 0 Gas groups 3 4 Grand total 2 1 clear 6 3 6 10 Guarantee 8 5 HI LO 9 3 3 9 3 7 HStr 9 3 3 9 3...

Reviews: