5

subtracted from the maximum cable
capacitance and inductance permitted by the
system certificate of the loop into which the
BA358C is connected.

3.3  Reset terminals

The BA358C total display may be reset to
zero by connecting the reset terminals RS1
and RS2 together.  These two terminals
have the following safety parameters:

Uo

5V dc

Io

1.3mA dc

Po

1.6mW

Ui

28V dc

Ii

98mA

Pi

0.65W

The maximum equivalent capacitance and
inductance between them is:

Ci

=

1.2nF

Li

= 0

µ

H

The total display may be reset from within
the hazardous area by any mechanically
operated switch having 500V rms insulation.
This may be connected directly to terminals
RS1 and RS2, no Zener barrier or isolator is
required.    Alternatively, the BA358C may
be programmed so that the total display is
reset to zero when the Up and Down push-
buttons are operated simultaneously.

To reset the total display from the safe area
a Zener barrier or intrinsically safe relay  is
required to transfer the contact closure into
the hazardous area.    Acceptable interface
devices and the maximum permissible cable
parameters are defined by the BA358C
system certificates.  Almost any intrinsically
safe relay with certification permitting the
contacts to be connected into the hazardous
area may be used.  Alternatively, one of the
positive diode return Zener barriers listed in
the system certificate may be used  - see Fig
3A.

3.4  Zones, gas groups and T rating

The BA358C has been certified to show
compliance with the requirements for Group
II Category 1G equipment, EEx ia IIC T5.
When connected to a suitable system the
instrument may be installed in:

Zone 

0

explosive gas air mixture
continuously present.

Zone 

1

explosive gas air mixture
likely to occur in normal
operation.

Zone 2

explosive gas air mixture not
likely to occur, and if it does
will only exist for a short
time.

Be used with gases in groups:

Group   A

propane

Group   B

ethylene

Group   C 

hydrogen

Having a temperature classification of:

T1

450

o

C

T2

300

o

C

T3

200

o

C

T4

350

o

C

T5

100

o

C  

At an ambient temperature between –40 and
+60

o

C.

Note:

 the guaranteed operating temperature

is –20 to +60

o

C

This allows the BA358C to be installed in all
Zones and to be used with most common
industrial gases.

WARNING installation in Zone 0

When installed in a Zone 0 potentially
explosive atmosphere requiring
apparatus of Category 1G, the rate
totaliser shall be installed such that
even in the event of rare incidents, an
ignition source due to impact or
friction between the aluminium
enclosure at the rear of the instrument
mounting panel and iron/steel is
excluded.

3.5 Certification Label Information

The certification label is fitted in a recess on
the side of the enclosure.  It shows the
ATEX certification information, the date of
manufacture, serial number plus BEKA
associates’ name and address.   Non
European certification information may also
be included.   The instrument serial number
is also shown on a separate label adjacent
to the field terminals.

Summary of Contents for BA358C

Page 1: ...October 2010 BA358C Intrinsically safe 4 20mA loop powered panel mounting rate totaliser Issue 4 Certification information label Rate display Annunciators for optional alarms Rotating flow indicator T...

Page 2: ...1 Timebase 6 12 Function of the P push button 6 13 Total scale factor 6 14 Percentage clip off 6 15 Local reset of total display 6 16 Security code 6 17 Over and under range 7 Calibration Examples 7 1...

Page 3: ...sed diode D1 The voltage developed across D1 which is relatively constant is multiplied by a switch mode power supply and used to power the instrument The voltage developed across R1 which is proporti...

Page 4: ...eds 4mA 3 INTRINSIC SAFETY CERTIFICATION 3 1 ATEX certificate The BA358C has been issued with an EC Type Examination Certificate by Notified Body Intertek Testing Services ITS formerly ERA Technology...

Page 5: ...Zones gas groups and T rating The BA358C has been certified to show compliance with the requirements for Group II Category 1G equipment EEx ia IIC T5 When connected to a suitable system the instrumen...

Page 6: ...dication of rate and total flow within a hazardous area The type of interface is not critical either a Zener barrier or a galvanic isolator may be used providing that Uo Io and Po are not exceeded If...

Page 7: ...esetting from the safe area via a single channel diode return Zener barrier A certified intrinsically safe relay or certified opto isolator may also be used Fig 3B shows how the total display may be r...

Page 8: ...lective displays there is little degradation of contrast when viewed from above the centre line but slight degradation may be noticeable when the instrument is fitted with a backlight Fig 4 BA358C dim...

Page 9: ...in the rate display is defined by the d p function To simplify calibration the BA358C uses floating point arithmetic moving the rate display decimal point position will therefore affect totalisation T...

Page 10: ...of 0 00 with 4mA input and 100 00 with 20mA input The total scale factor will be set to 1 0000 with a timebase of flow per second The instrument can easily be recalibrated on site 6 3 Summary of progr...

Page 11: ...input current in milliamps or the input as a percentage when the P push button is operated in the display mode Select PC for of span and 4 20 to display current See section 6 12 Display Description o...

Page 12: ...cimal point clip off to adjust value Press or between 0 and 10 or and pressing Define Security Enter by Code to move to next digit Local reset or Fig 7B Programme Structure CLr Gtot E E E E E E E E P...

Page 13: ...or and Similarly set the required full scale display accurate 20mA input current scale display using an Similarly set the required full to move to next digit pressing or and set required zero display...

Page 14: ...s Operating the P push button will toggle control between the two displays When both decimal points have been correctly positioned press E to return to the main menu If the application requires flow r...

Page 15: ...ay 0000 Using the Up and Down buttons and the P button to move to the next digit enter the password SurE S is entered as 5 Pressing E will then give access to the sub menu 6 9 1 AC rejection FrE WARNI...

Page 16: ...our Tb 3600 3600 Select the required divisor and press E to return to the main menu 6 12 Function of the P push button C P This parameter defines the function of the P push button when the BA358C is i...

Page 17: ...lect CLIP OFF from the main menu and press P to reveal the current setting This clip off threshold is shown as a percentage of total flow and may be adjusted in one percent increments using the Up or...

Page 18: ...ction 7 1 describes the preferred method of calibration using an external traceable 4 20mA calibrator Section 7 2 contains an example of calibration using the BA358C internal 4 and 20mA references whi...

Page 19: ...git of the total display flashing Press the Up or Down push button until the second least significant digit and following decimal point of the total display flash This gives the required total display...

Page 20: ...to the main menu by pressing E Step 12 Reset the grand total to zero To reset the grand total to zero select CLr Gtot from the main menu and press P which will cause the instrument to display Clr no T...

Page 21: ...multaneously pressing P and E Assuming a security code has not already been entered the instrument will respond by displaying root which is the first function in the main menu Steps Perform as describ...

Page 22: ...terminals 1 3 No power supply Confirm that a 4 20mA current is flowing in the loop Unstable rate display 4 20mA current is noisy or the flow signal is unstable Eliminate source of electrical noise Red...

Page 23: ...ons available for a rate alarm and shows which are fail safe i e output is in the alarm condition open when the 4 20mA input current is zero Similarly when programmed as a total alarm the output shoul...

Page 24: ...nt capacitance and inductance of each BA358C alarm output is Ci 40nF Li 20 H The maximum permissible cable parameters for the alarm circuit will be the figures specified for the barrier or isolator le...

Page 25: ...veal the current setting The function can be changed by pressing the Up or Down button followed by the E button to return to the alarm menu 9 3 5 Type of alarm tYPE This function conditions the alarm...

Page 26: ...Down button followed by the E button to return to the alarm menu 9 3 9 Hysteresis HStr Hysteresis is only available on rate alarms During programming hysteresis is shown in the units of rate the BA358...

Page 27: ...This direct access menu is enabled and a separate security code entered from the AcSP function in the main programme menu To change the menu parameters select AcSP from the programme menu and press P...

Page 28: ...is segregated from the measuring circuit and has been certified as a separate intrinsically safe circuit but it does not comply with the requirements for simple apparatus Systems certificates for use...

Page 29: ...ere the instrument is likely to be damaged by impact an additional front cover is available The BA398 is a robust transparent cover which is secured to the panel by six screws and sealed with a neopre...

Page 30: ...missioning 8 1 after commissioning 8 2 Flow indicator 2 2 Flow transmitter loops 4 1 Galvanic isolators 4 0 Gas groups 3 4 Grand total 2 1 clear 6 3 6 10 Guarantee 8 5 HI LO 9 3 3 9 3 7 HStr 9 3 3 9 3...

Reviews: