10

instrument will display 'COdE'.  Press P to
clear this prompt and enter the security code
for the instrument using the Up or Down
push-button to adjust each digit, and the P
push-button to move control to the next digit.
If the correct code has been entered
pressing  E will cause the first parameter
'root' to be displayed.  If an incorrect code is
entered, or a push-button is not operated,
the instrument will timeout after ten seconds
and automatically return to the display
mode.

Apart from defining the position of the
decimal point in the rate display all
programme functions and prompts are
shown on the large eight digit display.

Once within the main programme menu the
required parameter can be reached by
scrolling through the menu using the Up and
Down push-buttons as shown by the
programme structure in Figs 7A and 7B.
When returning to the operating mode
following recalibration or changes to any
parameters, the total display will show
circulating decimal points for a few seconds
while the new information is stored in
permanent memory.

All new BA358C rate totalisers are supplied
calibrated as requested at the time of
ordering.  If calibration information is not
supplied, the BA358C will be set to display a
rate of 0.00 with 4mA input and 100.00 with
20mA input.  The total scale factor will be set
to 1.0000 with a timebase of flow per
second.    The instrument can easily be
recalibrated on-site.

6.3  Summary of programmable functions

This section summarises all of the BA358C
programmable functions. When read with
Figs 7A and 7B it provides a quick aid for
calibrating the instrument.  If more detail is
required, each section contains a reference
to a full description of the function.

SUMMARY

Display

Description of function

  'root' 

Square root extractor

Enables the square root
extractor for linearising the
output from differential
flowmeters.
Percentage CLIP-OFF, below
which the instrument does not
totalise, is automatically set to
5% of rate when the 'root'
function is turned 'On'.
See section 6.4

'rESn'

         

Display resolution

Selects the resolution of the
least significant digit of the rate
display.  May be set to 1, 2, 5 or
10 digits.
See section 6.5

'd.P.'          Decimal points

Defines the position of the
decimal point in both the rate
and total displays.
See section 6.6

'CAL'         Calibration of rate display
                  using external current source.

Enables the zero and span of
the rate display to be adjusted
using an external current source
such as a calibrator.   Also
enables a complete loop to be
calibrated from primary element
to the indicator display.
When used with an accurate
traceable current source this is
the preferred method of
calibration.
See section 6.7

Summary of Contents for BA358C

Page 1: ...October 2010 BA358C Intrinsically safe 4 20mA loop powered panel mounting rate totaliser Issue 4 Certification information label Rate display Annunciators for optional alarms Rotating flow indicator T...

Page 2: ...1 Timebase 6 12 Function of the P push button 6 13 Total scale factor 6 14 Percentage clip off 6 15 Local reset of total display 6 16 Security code 6 17 Over and under range 7 Calibration Examples 7 1...

Page 3: ...sed diode D1 The voltage developed across D1 which is relatively constant is multiplied by a switch mode power supply and used to power the instrument The voltage developed across R1 which is proporti...

Page 4: ...eds 4mA 3 INTRINSIC SAFETY CERTIFICATION 3 1 ATEX certificate The BA358C has been issued with an EC Type Examination Certificate by Notified Body Intertek Testing Services ITS formerly ERA Technology...

Page 5: ...Zones gas groups and T rating The BA358C has been certified to show compliance with the requirements for Group II Category 1G equipment EEx ia IIC T5 When connected to a suitable system the instrumen...

Page 6: ...dication of rate and total flow within a hazardous area The type of interface is not critical either a Zener barrier or a galvanic isolator may be used providing that Uo Io and Po are not exceeded If...

Page 7: ...esetting from the safe area via a single channel diode return Zener barrier A certified intrinsically safe relay or certified opto isolator may also be used Fig 3B shows how the total display may be r...

Page 8: ...lective displays there is little degradation of contrast when viewed from above the centre line but slight degradation may be noticeable when the instrument is fitted with a backlight Fig 4 BA358C dim...

Page 9: ...in the rate display is defined by the d p function To simplify calibration the BA358C uses floating point arithmetic moving the rate display decimal point position will therefore affect totalisation T...

Page 10: ...of 0 00 with 4mA input and 100 00 with 20mA input The total scale factor will be set to 1 0000 with a timebase of flow per second The instrument can easily be recalibrated on site 6 3 Summary of progr...

Page 11: ...input current in milliamps or the input as a percentage when the P push button is operated in the display mode Select PC for of span and 4 20 to display current See section 6 12 Display Description o...

Page 12: ...cimal point clip off to adjust value Press or between 0 and 10 or and pressing Define Security Enter by Code to move to next digit Local reset or Fig 7B Programme Structure CLr Gtot E E E E E E E E P...

Page 13: ...or and Similarly set the required full scale display accurate 20mA input current scale display using an Similarly set the required full to move to next digit pressing or and set required zero display...

Page 14: ...s Operating the P push button will toggle control between the two displays When both decimal points have been correctly positioned press E to return to the main menu If the application requires flow r...

Page 15: ...ay 0000 Using the Up and Down buttons and the P button to move to the next digit enter the password SurE S is entered as 5 Pressing E will then give access to the sub menu 6 9 1 AC rejection FrE WARNI...

Page 16: ...our Tb 3600 3600 Select the required divisor and press E to return to the main menu 6 12 Function of the P push button C P This parameter defines the function of the P push button when the BA358C is i...

Page 17: ...lect CLIP OFF from the main menu and press P to reveal the current setting This clip off threshold is shown as a percentage of total flow and may be adjusted in one percent increments using the Up or...

Page 18: ...ction 7 1 describes the preferred method of calibration using an external traceable 4 20mA calibrator Section 7 2 contains an example of calibration using the BA358C internal 4 and 20mA references whi...

Page 19: ...git of the total display flashing Press the Up or Down push button until the second least significant digit and following decimal point of the total display flash This gives the required total display...

Page 20: ...to the main menu by pressing E Step 12 Reset the grand total to zero To reset the grand total to zero select CLr Gtot from the main menu and press P which will cause the instrument to display Clr no T...

Page 21: ...multaneously pressing P and E Assuming a security code has not already been entered the instrument will respond by displaying root which is the first function in the main menu Steps Perform as describ...

Page 22: ...terminals 1 3 No power supply Confirm that a 4 20mA current is flowing in the loop Unstable rate display 4 20mA current is noisy or the flow signal is unstable Eliminate source of electrical noise Red...

Page 23: ...ons available for a rate alarm and shows which are fail safe i e output is in the alarm condition open when the 4 20mA input current is zero Similarly when programmed as a total alarm the output shoul...

Page 24: ...nt capacitance and inductance of each BA358C alarm output is Ci 40nF Li 20 H The maximum permissible cable parameters for the alarm circuit will be the figures specified for the barrier or isolator le...

Page 25: ...veal the current setting The function can be changed by pressing the Up or Down button followed by the E button to return to the alarm menu 9 3 5 Type of alarm tYPE This function conditions the alarm...

Page 26: ...Down button followed by the E button to return to the alarm menu 9 3 9 Hysteresis HStr Hysteresis is only available on rate alarms During programming hysteresis is shown in the units of rate the BA358...

Page 27: ...This direct access menu is enabled and a separate security code entered from the AcSP function in the main programme menu To change the menu parameters select AcSP from the programme menu and press P...