background image

6

4. 

SYSTEM DESIGN FOR HAZARDOUS

    AREAS     ATEX Certification

4.1 Flow transmitter loops

A BA358C rate totaliser may be connected
in series with almost any intrinsically safe
4/20mA flow loop and calibrated to display
the rate of flow and total flow.   There are
two basic design requirements:

1. The intrinsic safety output parameters

of the 4/20mA loop, which are defined
by the Zener barrier or galvanic isolator,
must be less than:

Uo

30V dc

Io

200mA

Po

0.85W

2. The loop must be able to tolerate the

additional 1.1V required to operate the
indicator

increases to 1.2V at -20ºC.

Fig 2 illustrates an application in which a
BA358C indicator is connected in series with
a 2-wire flow transmitter protected by a two
channel Zener barrier.

Fig 2  BA358C in a flow loop

4.2  Remote indication

A BA358C may be driven via an intrinsically
safe interface from a 4/20mA safe area
signal to provide a remote indication of rate
and total flow within a hazardous area.   The
type of interface is not critical, either a Zener
barrier or a galvanic isolator may be used,
providing that Uo,  Io and Po are not
exceeded.

If one side of the 4/20mA current loop may
be earthed, a single channel Zener barrier
provides the lowest cost protection.  If the
4/20mA signal is not isolated, then two
Zener barriers, a two channel Zener barrier
or a galvanic isolator must be used.

When the hazard is a IIC gas, and two single
channel Zener barriers or a two channel
Zener barrier are used, only one barrier or
channel may be a 28V 300ohm device.    A
10V 50ohm or diode return barrier may be
used for the second channel to form a safe
combination.

Again it is necessary to ensure that the
voltage capability of the 4/20mA signal is
sufficient to drive the rate totaliser plus the
voltage drop introduced by the intrinsically
safe interface.

Figs 3A, 3B and 3C show the alternative
circuits which may be used.

Fig 

3A Simplest circuit with one side of

4/20mA current loop connected to
earth. Also shows optional resetting
from safe area.

Summary of Contents for BA358C

Page 1: ...October 2010 BA358C Intrinsically safe 4 20mA loop powered panel mounting rate totaliser Issue 4 Certification information label Rate display Annunciators for optional alarms Rotating flow indicator T...

Page 2: ...1 Timebase 6 12 Function of the P push button 6 13 Total scale factor 6 14 Percentage clip off 6 15 Local reset of total display 6 16 Security code 6 17 Over and under range 7 Calibration Examples 7 1...

Page 3: ...sed diode D1 The voltage developed across D1 which is relatively constant is multiplied by a switch mode power supply and used to power the instrument The voltage developed across R1 which is proporti...

Page 4: ...eds 4mA 3 INTRINSIC SAFETY CERTIFICATION 3 1 ATEX certificate The BA358C has been issued with an EC Type Examination Certificate by Notified Body Intertek Testing Services ITS formerly ERA Technology...

Page 5: ...Zones gas groups and T rating The BA358C has been certified to show compliance with the requirements for Group II Category 1G equipment EEx ia IIC T5 When connected to a suitable system the instrumen...

Page 6: ...dication of rate and total flow within a hazardous area The type of interface is not critical either a Zener barrier or a galvanic isolator may be used providing that Uo Io and Po are not exceeded If...

Page 7: ...esetting from the safe area via a single channel diode return Zener barrier A certified intrinsically safe relay or certified opto isolator may also be used Fig 3B shows how the total display may be r...

Page 8: ...lective displays there is little degradation of contrast when viewed from above the centre line but slight degradation may be noticeable when the instrument is fitted with a backlight Fig 4 BA358C dim...

Page 9: ...in the rate display is defined by the d p function To simplify calibration the BA358C uses floating point arithmetic moving the rate display decimal point position will therefore affect totalisation T...

Page 10: ...of 0 00 with 4mA input and 100 00 with 20mA input The total scale factor will be set to 1 0000 with a timebase of flow per second The instrument can easily be recalibrated on site 6 3 Summary of progr...

Page 11: ...input current in milliamps or the input as a percentage when the P push button is operated in the display mode Select PC for of span and 4 20 to display current See section 6 12 Display Description o...

Page 12: ...cimal point clip off to adjust value Press or between 0 and 10 or and pressing Define Security Enter by Code to move to next digit Local reset or Fig 7B Programme Structure CLr Gtot E E E E E E E E P...

Page 13: ...or and Similarly set the required full scale display accurate 20mA input current scale display using an Similarly set the required full to move to next digit pressing or and set required zero display...

Page 14: ...s Operating the P push button will toggle control between the two displays When both decimal points have been correctly positioned press E to return to the main menu If the application requires flow r...

Page 15: ...ay 0000 Using the Up and Down buttons and the P button to move to the next digit enter the password SurE S is entered as 5 Pressing E will then give access to the sub menu 6 9 1 AC rejection FrE WARNI...

Page 16: ...our Tb 3600 3600 Select the required divisor and press E to return to the main menu 6 12 Function of the P push button C P This parameter defines the function of the P push button when the BA358C is i...

Page 17: ...lect CLIP OFF from the main menu and press P to reveal the current setting This clip off threshold is shown as a percentage of total flow and may be adjusted in one percent increments using the Up or...

Page 18: ...ction 7 1 describes the preferred method of calibration using an external traceable 4 20mA calibrator Section 7 2 contains an example of calibration using the BA358C internal 4 and 20mA references whi...

Page 19: ...git of the total display flashing Press the Up or Down push button until the second least significant digit and following decimal point of the total display flash This gives the required total display...

Page 20: ...to the main menu by pressing E Step 12 Reset the grand total to zero To reset the grand total to zero select CLr Gtot from the main menu and press P which will cause the instrument to display Clr no T...

Page 21: ...multaneously pressing P and E Assuming a security code has not already been entered the instrument will respond by displaying root which is the first function in the main menu Steps Perform as describ...

Page 22: ...terminals 1 3 No power supply Confirm that a 4 20mA current is flowing in the loop Unstable rate display 4 20mA current is noisy or the flow signal is unstable Eliminate source of electrical noise Red...

Page 23: ...ons available for a rate alarm and shows which are fail safe i e output is in the alarm condition open when the 4 20mA input current is zero Similarly when programmed as a total alarm the output shoul...

Page 24: ...nt capacitance and inductance of each BA358C alarm output is Ci 40nF Li 20 H The maximum permissible cable parameters for the alarm circuit will be the figures specified for the barrier or isolator le...

Page 25: ...veal the current setting The function can be changed by pressing the Up or Down button followed by the E button to return to the alarm menu 9 3 5 Type of alarm tYPE This function conditions the alarm...

Page 26: ...Down button followed by the E button to return to the alarm menu 9 3 9 Hysteresis HStr Hysteresis is only available on rate alarms During programming hysteresis is shown in the units of rate the BA358...

Page 27: ...This direct access menu is enabled and a separate security code entered from the AcSP function in the main programme menu To change the menu parameters select AcSP from the programme menu and press P...

Page 28: ...is segregated from the measuring circuit and has been certified as a separate intrinsically safe circuit but it does not comply with the requirements for simple apparatus Systems certificates for use...

Page 29: ...ere the instrument is likely to be damaged by impact an additional front cover is available The BA398 is a robust transparent cover which is secured to the panel by six screws and sealed with a neopre...

Page 30: ...missioning 8 1 after commissioning 8 2 Flow indicator 2 2 Flow transmitter loops 4 1 Galvanic isolators 4 0 Gas groups 3 4 Grand total 2 1 clear 6 3 6 10 Guarantee 8 5 HI LO 9 3 3 9 3 7 HStr 9 3 3 9 3...

Reviews: