background image

5

3.3   Pulse input terminals

The BA344D rate totaliser has two alternative
pairs of input terminals enabling the instrument
to count pulses from a wide variety of sources.

Note:

 Only one pair of input terminals may be

used at one time.

3.3.1  Voltage pulse input

Terminals 3 and 4 are intended for connection
to a voltage pulse source.  In Europe, sources
of energy which do not generate more than
1.5V; 100mA and 25mW are, for intrinsic safety
purposes, considered to be 

simple apparatus

(Clause 5.4 of EN50 020:1994).

Although the BA344D indicator does not itself
comply with the requirements for 

simple

apparatus

, the EC-Type Examination

Certificate specifies that under fault conditions
the voltage, current and power at terminals 3 &
4 will not exceed those specified for 

simple

apparatus

.   This allows these input terminals

to be connected to any certified intrinsically
safe apparatus or circuit providing that the
output parameters of the apparatus or circuit
do not exceed:

Uo

=

28V dc

Io

=

100mA dc

Po

=

0.7W

The certified intrinsically safe voltage pulse
output of a flowmeter mounted in a hazardous
area, or the output of a certified magnetic pick-
off mounted in a hazardous area may be
directly connected to these terminals providing:

The output parameters of the device do
not exceed  the figures shown above.

The device can withstand a 500V rms
insulation test to earth for one minute.

The BA344D EC-Type Examination Certificate
specifies that the maximum equivalent
capacitance and inductance between the two
pulse input terminals 3 and 4 is:

Ci

=     30nF

Li

=      10

µ

H

To determine the maximum permissible cable
parameters these figures should be subtracted
from the maximum permitted cable parameters
specified for the device connected to terminals
3 and 4.

The BA344D system certificates specify the
maximum permitted cable parameters when a
28V 300

 Zener barrier or galvanic isolator is

connected to these terminals.

3.3.2  Contact or open collector input

Terminals 5 and 6 are intended for connection
to a switch contact or a certified open collector
output.   Terminals 5 & 6 output safety
parameters are:

Uo

=

3.7V dc

Io

=

2mA dc

Po

=

2mW

and the maximum permitted external
capacitance and inductance is:

Co

=

99µF

Lo

=

999mH

Mechanically operated switch contacts comply
with the requirements for 

simple apparatus.

Providing the switch and the BA344D are both
located in the same hazardous area, the switch
may be connected directly to terminals 5 & 6.
This also applies to most magnetically
operated reed switches used in turbine
flowmeters.

Similarly, certified intrinsically safe open
collector outputs may be directly connected to
terminals 5 and 6

In all cases the device and circuit connected to
terminals 5 & 6 must be capable of
withstanding a 500V rms insulation test to
earth for one minute and have IP20 protection

The maximum input safety parameters for
terminals 5 & 6 are:

Ui

=

28V dc

Ii

=

100mA dc

Pi

=

0.7W

and the equivalent internal capacitance and
inductance are:

Ci

=

30nF

Li

=

10µH

This allows Zener barriers and galvanic
isolators to be connected to these terminals.
The BA344D system certificates specify the
maximum permitted cable parameters when a
28V 300

 Zener barrier or galvanic isolator is

used to transfer a pulse from the safe area to
the BA344D in a hazardous area.

Summary of Contents for BA344D

Page 1: ...Issue 5 7th April 2009 BA344D Intrinsically safe Battery powered pulse input field mounting rate totaliser Issue 5...

Page 2: ...0 Rate filter 6 11 Total scale factor 6 12 Clip off 6 13 Local reset 6 14 Resetting grand total 6 15 Security code 7 Calibration Example 7 1 Calibration procedure 8 Maintenance 8 1 Fault finding durin...

Page 3: ...es or via the optional external keypad Optional alarms which may be programmed to function on the rate or total displays further extend the applications of this instrument The BA344D contains an inter...

Page 4: ...mospheres which conform with BS EN60079 Part14 2003 Electrical Installation in Hazardous Areas When designing systems for installation outside the UK the local Code of Practice should be consulted For...

Page 5: ...and 4 is Ci 30nF Li 10 H To determine the maximum permissible cable parameters these figures should be subtracted from the maximum permitted cable parameters specified for the device connected to ter...

Page 6: ...perated simultaneously See 6 13 Each time the total display is reset to zero the grand total is transferred to permanent memory 3 5 Zones gas groups and T rating The BA344D has been issued with an EC...

Page 7: ...onnected to terminals 5 6 The maximum input counting frequency is 10kHz 4 1 System certificates When the input signal is derived from the safe area or the total display is to be reset from within the...

Page 8: ...rconnected within the BA344D see Fig 1 4 3 Use with Galvanic Isolators Galvanic isolators are probably the simplest intrinsically safe interface as they provide isolation and do not require a high int...

Page 9: ...nstallation procedure a Remove the instrument terminal cover by unscrewing the two captive A screws b Mount the instrument on a flat surface and secure with two M6 screws through the B holes Alternati...

Page 10: ...ssembly The discharged battery may be removed and the replacement fitted while the BA344D rate totalisers is installed in the hazardous area Fig 7 illustrates the replacement sequence a If the instrum...

Page 11: ...the instrument enclosure Before replacing the terminal cover turn the instrument ON by moving the slide switch to the right Fig 7 Replacement of internal battery 5 5 Disposal of used batteries The BEK...

Page 12: ...ond minute or hour Similarly to calculate the total flow in the required units of measurement the number of input pulses is divided by the total scale factor SCALE t Total flow is continuously added t...

Page 13: ...13...

Page 14: ...section 6 6 dISPLAY 2 Lower display Turns the lower display which normally shows rate on or off See section 6 7 Display Description of function SCALE r Rate Scale Factor Defines the arithmetic relatio...

Page 15: ...ype select InPut from the menu and press P which will reveal the current input type Pressing Up or Down will scroll through the four options UOLts Voltage pulse input Threshold 1V and 3V 10kHz max Inp...

Page 16: ...int position and simultaneously press the Up and Down buttons When the required rate scale factor has been entered press E to store the number and return to the main menu 6 9 Timebase t bASE The timeb...

Page 17: ...ecimal point in the scale factor move the flashing digit to the left hand side of the required decimal point position and simultaneously press the Up and Down buttons When the required total scale fac...

Page 18: ...d before access to the programme menu is granted New instruments are programmed with the default security code 0000 which allows unrestricted access to all programming functions without entering a sec...

Page 19: ...3 Select the type of input Using the Up or Down button scroll through the main menu until InPut is displayed then press P to reveal the existing setting Select COIL the input for a magnetic pick off u...

Page 20: ...A344D is required to display 1 cubic metre for every 105 x 1 000 pulses received SCALE t should therefore be set to 105 000 Select SCALE t from the main menu and press P which will reveal the current...

Page 21: ...rument to the CLr Gtot prompt in the main menu Step 12 Define the security code Defining a security code prevents unauthorised access to the programme functions Select COdE from the main menu and pres...

Page 22: ...equipment should be used unless a gas clearance certificate is available If a BA344D fails after it has been functioning correctly the following table may help Symptom Cause Check No display Instrume...

Page 23: ...larm annunciators on the instrument display indicate the status of both alarms If an alarm delay or silence time has been selected the annunciator will flash during the delay or silence period Program...

Page 24: ...lay Description of function EnbL Alarm enable Enables or disables the alarm function without changing the alarm parameters See section 9 2 4 tYPE Type of alarm Defines whether the alarm operates on th...

Page 25: ...rn to the alarm menu 9 2 5 Type of alarm tYPE Alarm 1 and Alarm 2 may both be rate or total alarms or one may be conditioned for rate and the other for total To check or change the type of alarm selec...

Page 26: ...select HStr from the alarm menu and press P which will reveal the existing figure Each digit can be adjusted using the Up and Down push buttons and the P button to move to the next digit When the req...

Page 27: ...o the setpoints in the display mode by pressing the P and Up buttons simultaneously New instruments with alarms are supplied with the security code set to 0000 9 2 13 Adjusting alarm setpoints from th...

Page 28: ...mounting kits are available for securing the BA344D to a horizontal or vertical pipe BA392D Stainless steel bracket secured by two worm drive hose clips for 60 to 80mm outside diameter pipes BA393 He...

Page 29: ...ertification Appendix 1 EnbL 9 2 3 9 2 4 Fault finding during commissioning 8 1 after commissioning 8 2 FILtEr 6 10 Flow indicator 2 2 Galvanic isolators 4 3 Gas groups 3 5 Grand total 2 2 clear 6 14...

Page 30: ...ve atmosphere in the form of a cloud of combustible dust in air is likely to occur occasionally in normal operation Zone 22 explosive atmosphere in the form of a cloud of combustible dust in air is no...

Page 31: ...ctioning immediately it is switched on When a replacement battery is fitted or when the rate totaliser is turned on after not being used for an extended period the battery should be conditioned by dra...

Reviews: