1.  DESCRIPTION

The BA344D is an intrinsically safe, battery
powered pulse input rate totaliser primarily
intended for use with flowmeters.  The
instrument simultaneously displays the rate of
flow and the total flow in engineering units on
two separate displays.

The BA344D complies with the European
ATEX Directive 94/9/EC and has been certified
intrinsically safe for use in explosive gas and
combustible dust atmospheres by Notified
Body Intertek Testing Services (ITS).

ATEX dust certification is an option -  See
Appendix 1.

Housed in a robust IP66 glass reinforced
polyester (GRP) enclosure with an armoured
glass window, the BA344D is surface
mounting, or may be pipe mounted using one
of the accessory kits.  A stem mounting kit is
also available allowing direct mounting onto a
flowmeter conduit entry.

2.  OPERATION

Fig 1 shows a simplified block diagram of a
BA344D.  The instrument accepts pulses
which, after scaling, are shown on two
separate displays as the total number of pulses
received and their rate. When connected to a
pulse output flowmeter the BA344D will provide
an accurate display of total flow and the rate of
flow.    The BA344D has two sets of input
terminals allowing connection to high or low
level voltage pulses, switch contacts or to an
open collector output, it may therefore be used
with most flowmeters.     The total display may
be reset to zero by a remote switch contact,
the internal switches or via the optional
external keypad.

Optional alarms, which may be programmed to
function on the rate or total displays, further
extend the applications of this instrument.

The BA344D contains an internal replaceable
battery that will power the instrument for up to
five years. Battery life depends upon how the
BA344D is programmed, and the pulse input
frequency.   A replacement BA491 battery may
be installed without removing the BA344D from
the hazardous area.

Fig 1  Simplified block diagram of BA344D

2.1  Controls

The BA344D is controlled and calibrated via
four push-button switches which are located
behind the instrument control cover, or as an
option on the outside of the control cover.    In
the operating mode, i.e. when the instrument is
displaying rate and total flow, the switch
functions are:

Description of Switch Functions

E+ Down

While these buttons are pushed the
total display will show the least
significant eight digits of the grand
total, and the grand total
annunciator will be activated.

E+Up

While these two buttons are pushed
the total display will show the most
significant eight digits of the grand
total and the grand total annunciator
will be activated.

Down

The   total   display is reset  to  zero

+Up

when  these  two  push-buttons  are
operated simultaneously for two
seconds.
This function may be turned on or
off from within the programme
menu.
See section  6.13

P

While these buttons are pushed the

+Down

instrument will display the firmware
part number and version number.

Note

:  When optional alarms are fitted the

push-buttons may be programmed to have
alternative functions – see section 9.2

Summary of Contents for BA344D

Page 1: ...Issue 5 7th April 2009 BA344D Intrinsically safe Battery powered pulse input field mounting rate totaliser Issue 5...

Page 2: ...0 Rate filter 6 11 Total scale factor 6 12 Clip off 6 13 Local reset 6 14 Resetting grand total 6 15 Security code 7 Calibration Example 7 1 Calibration procedure 8 Maintenance 8 1 Fault finding durin...

Page 3: ...es or via the optional external keypad Optional alarms which may be programmed to function on the rate or total displays further extend the applications of this instrument The BA344D contains an inter...

Page 4: ...mospheres which conform with BS EN60079 Part14 2003 Electrical Installation in Hazardous Areas When designing systems for installation outside the UK the local Code of Practice should be consulted For...

Page 5: ...and 4 is Ci 30nF Li 10 H To determine the maximum permissible cable parameters these figures should be subtracted from the maximum permitted cable parameters specified for the device connected to ter...

Page 6: ...perated simultaneously See 6 13 Each time the total display is reset to zero the grand total is transferred to permanent memory 3 5 Zones gas groups and T rating The BA344D has been issued with an EC...

Page 7: ...onnected to terminals 5 6 The maximum input counting frequency is 10kHz 4 1 System certificates When the input signal is derived from the safe area or the total display is to be reset from within the...

Page 8: ...rconnected within the BA344D see Fig 1 4 3 Use with Galvanic Isolators Galvanic isolators are probably the simplest intrinsically safe interface as they provide isolation and do not require a high int...

Page 9: ...nstallation procedure a Remove the instrument terminal cover by unscrewing the two captive A screws b Mount the instrument on a flat surface and secure with two M6 screws through the B holes Alternati...

Page 10: ...ssembly The discharged battery may be removed and the replacement fitted while the BA344D rate totalisers is installed in the hazardous area Fig 7 illustrates the replacement sequence a If the instrum...

Page 11: ...the instrument enclosure Before replacing the terminal cover turn the instrument ON by moving the slide switch to the right Fig 7 Replacement of internal battery 5 5 Disposal of used batteries The BEK...

Page 12: ...ond minute or hour Similarly to calculate the total flow in the required units of measurement the number of input pulses is divided by the total scale factor SCALE t Total flow is continuously added t...

Page 13: ...13...

Page 14: ...section 6 6 dISPLAY 2 Lower display Turns the lower display which normally shows rate on or off See section 6 7 Display Description of function SCALE r Rate Scale Factor Defines the arithmetic relatio...

Page 15: ...ype select InPut from the menu and press P which will reveal the current input type Pressing Up or Down will scroll through the four options UOLts Voltage pulse input Threshold 1V and 3V 10kHz max Inp...

Page 16: ...int position and simultaneously press the Up and Down buttons When the required rate scale factor has been entered press E to store the number and return to the main menu 6 9 Timebase t bASE The timeb...

Page 17: ...ecimal point in the scale factor move the flashing digit to the left hand side of the required decimal point position and simultaneously press the Up and Down buttons When the required total scale fac...

Page 18: ...d before access to the programme menu is granted New instruments are programmed with the default security code 0000 which allows unrestricted access to all programming functions without entering a sec...

Page 19: ...3 Select the type of input Using the Up or Down button scroll through the main menu until InPut is displayed then press P to reveal the existing setting Select COIL the input for a magnetic pick off u...

Page 20: ...A344D is required to display 1 cubic metre for every 105 x 1 000 pulses received SCALE t should therefore be set to 105 000 Select SCALE t from the main menu and press P which will reveal the current...

Page 21: ...rument to the CLr Gtot prompt in the main menu Step 12 Define the security code Defining a security code prevents unauthorised access to the programme functions Select COdE from the main menu and pres...

Page 22: ...equipment should be used unless a gas clearance certificate is available If a BA344D fails after it has been functioning correctly the following table may help Symptom Cause Check No display Instrume...

Page 23: ...larm annunciators on the instrument display indicate the status of both alarms If an alarm delay or silence time has been selected the annunciator will flash during the delay or silence period Program...

Page 24: ...lay Description of function EnbL Alarm enable Enables or disables the alarm function without changing the alarm parameters See section 9 2 4 tYPE Type of alarm Defines whether the alarm operates on th...

Page 25: ...rn to the alarm menu 9 2 5 Type of alarm tYPE Alarm 1 and Alarm 2 may both be rate or total alarms or one may be conditioned for rate and the other for total To check or change the type of alarm selec...

Page 26: ...select HStr from the alarm menu and press P which will reveal the existing figure Each digit can be adjusted using the Up and Down push buttons and the P button to move to the next digit When the req...

Page 27: ...o the setpoints in the display mode by pressing the P and Up buttons simultaneously New instruments with alarms are supplied with the security code set to 0000 9 2 13 Adjusting alarm setpoints from th...

Page 28: ...mounting kits are available for securing the BA344D to a horizontal or vertical pipe BA392D Stainless steel bracket secured by two worm drive hose clips for 60 to 80mm outside diameter pipes BA393 He...

Page 29: ...ertification Appendix 1 EnbL 9 2 3 9 2 4 Fault finding during commissioning 8 1 after commissioning 8 2 FILtEr 6 10 Flow indicator 2 2 Galvanic isolators 4 3 Gas groups 3 5 Grand total 2 2 clear 6 14...

Page 30: ...ve atmosphere in the form of a cloud of combustible dust in air is likely to occur occasionally in normal operation Zone 22 explosive atmosphere in the form of a cloud of combustible dust in air is no...

Page 31: ...ctioning immediately it is switched on When a replacement battery is fitted or when the rate totaliser is turned on after not being used for an extended period the battery should be conditioned by dra...

Reviews: