Beijer Electronics Frequency Inverter BFI-H3

  

  

 

KI00363D

  

2021-07

 

Start-up document 

This document is a short start-up guide describing basic functionality of the drive BFI-H3, 
firmware 2.50, manufactured from November 2020. Detailed explanations are to be read in User 
Manual BFI-H3. This manual is attached with the drive itself but also possible to download from 

www.beijerelectronics.com

 

Important Safety Information 

Please read the IMPORTANT SAFETY INFORMATION below, and all Warning and Caution 
information elsewhere. 

 

Danger : 

Indicates a risk of electric shock, which, if not 

avoided, could result in damage to the equipment and 
possible injury or death.

 

 

Danger : 

Indicates a potentially hazardous 

situation other than electrical, which if not 
avoided, could result in damage to property.

 

 

This variable speed drive product is intended for professional incorporation into complete equipment or systems as part of a fixed installation. If installed 
incorrectly it may present a safety hazard. The BFI uses high voltages and currents, carries a high level of stored electrical energy, and is used to control 
mechanical plant that may cause injury. Close attention is required to system design and electrical installation to avoid hazards in either normal operation 
or in the event of equipment malfunction. Only qualified electricians are allowed to install and maintain this product. 

System design, installation, commissioning and maintenance must be carried out only by personnel who have the necessary training and experience. 
They must carefully read this safety information and the instructions in this Guide and follow all information regarding transport, storage, installation and 
use of the BFI, including the specified environmental limitations.  
Do not perform any flash test or voltage withstand test on the BFI. Any electrical measurements required should be carried out with BFI disconnected. 
Electric shock hazard! Disconnect and ISOLATE the BFI before attempting any work on it. High voltages are present at the terminals and within the 
drive for up to 10 minutes after disconnection of the electrical supply. Always ensure by using a suitable multimeter that no voltage is present on any 
drive power terminals prior to commencing any work. 
Where supply to the drive is through a plug and socket connector, do not disconnect until 10 minutes have elapsed after turning off the supply. 
Ensure correct earthing connections.  The earth cable must be sufficient to carry the maximum supply fault current which normally will be limited by the 
fuses or MCB. Suitably rated fuses or MCB should be fitted in the mains supply to the drive, according to any local legislation or codes. 

Do not carry out any work on the drive control cables whilst power is applied to the drive or to the external control circuits.  

 

Within the European Union, all machinery in which this product is used must comply with Directive 98/37/EC, Safety of Machinery. In particular, the 
machine manufacturer is responsible for providing a main switch and ensuring the electrical equipment complies with EN60204 -1. 
The level of integrity offered by the BFI control input functions – for example stop/start, forward/reverse and maximum speed is not sufficient for use in 
safety-critical applications without independent channels of protection. All applications where malfunction could cause injury or loss of life must be 
subject to a risk assessment and further protection provided where needed. 
The driven motor can start at power up if the enable input signal is present. 
The STOP function does not remove potentially lethal high voltages. ISOLATE the drive and wait 10 minutes before starting any work on it. Never carry 
out any work on the Drive, Motor or Motor cable whilst the input power is still applied. 
The BFI can be programmed to operate the driven motor at speeds above or below the speed achieved when connecting the motor directly to the mains 
supply. Obtain confirmation from the manufacturers of the motor and the driven machine about suitability for operation over the intended speed range 
prior to machine start up. 
Do not activate the automatic fault reset function on any systems whereby this may cause a potentially dangerous situation. 
The BFI has an Ingress Protection rating of IP20, IP55 or IP66 depending on the model. IP20 units must be installed in a suitable enclosure. 
When mounting the drive, ensure that sufficient cooling is provided. Do not carry out drilling operations with the drive-in place, dust and swarf from 
drilling may lead to damage. BFI are intended for indoor use only. 
The entry of conductive or flammable foreign bodies should be prevented. Flammable material should not be placed close to the drive 
Relative humidity must be less than 95% (non-condensing). 
Ensure that the supply voltage, frequency and no. of phases (1 or 3 phase) correspond to the rating of the BFI as delivered. 
Never connect the mains power supply to the Output terminals U, V, W. 
Do not install any type of automatic switchgear between the drive and the motor 
Wherever control cabling is close to power cabling, maintain a minimum separation of 100 mm and arrange crossings at 90 degrees 
Ensure that all terminals are tightened to the appropriate torque setting 
Do not attempt to carry out any repair of the BFI. In the case of suspected fault or malfunction, contact Beijer Electronics office for further assistance. 

 
 

Summary of Contents for BFI-H3

Page 1: ...t disconnect until 10 minutes have elapsed after turning off the supply Ensure correct earthing connections The earth cable must be sufficient to carry the maximum supply fault current which normally...

Page 2: ...22 6 KEYPAD 23 6 1 SELECTING LANGUAGE 23 6 2 DRIVE OPERATING DISPLAY 23 6 3 CHANGING PARAMETER VALUES 24 6 4 PARAMETERS FACTORY RESET USER RESET 25 6 5 SELECTING BETWEEN HAND AND AUTO CONTROL 25 6 6...

Page 3: ...ght kg 1 x 230 V 3 x 230 V 3 x 400 V 0043 0105 0 75 2 2 kW 0043 0105 0 75 2 2 kW 0022 0140 0 75 5 5 kW 2 257 188 186 200 176 172 4 8 None 0180 0240 4 0 5 5 kW 0180 0300 7 5 15 kW 3 310 211 235 252 198...

Page 4: ...00 V 0300 0460 7 5 11 kW 0300 0460 15 22 kW 4 450 171 252 428 110 12 0610 0900 15 22 kW 0610 0900 30 45 kW 5 540 235 270 515 175 23 1100 1500 30 37 kW 1100 1800 55 90 kW 6 865 330 330 830 200 55 1800...

Page 5: ...B 4 x M10 Size 8 4 x M12 Required tightening Torques Control terminals All Sizes 0 5 Nm Required tightening Torques Power terminals Size 2 3 1 0 Nm Size 4 2 Nm Size 5 4 Nm Size 6A 12 Nm Size 6B 15 Nm...

Page 6: ...n hardware limitations and do NOT take into consideration any requirements for compliance to any EMC standards Maximum motor cable length stated applies to using a screened motor cable When using an u...

Page 7: ...pplying Derating Factors A 4kW IP66 drive is to be used at an altitude of 2000 metres above sea level with 16 kHz switching frequency and 45 C ambient temperature Rated current of the drive is 9 5 Amp...

Page 8: ...hould be dimensioned according to any local codes or regulations 400V 230V 690V 400V STAR DELTA Motor cable must be a symmetrical shielded cable where the screen covers at least 85 of the cable surfac...

Page 9: ...he electrical cabinet Separate earth connection might be necessary Motor cable should avoid being installed close to telephone network or signal wiring Minimum distance is 10 cm More detailed descript...

Page 10: ...mally called IT net IT net is normally being used in all types of boats and also some parts of Norway In the rest of Europe TN net is most common were EMC filter can be used The EMC filter on BFI IP20...

Page 11: ...nalog ref 1 10 VDC AOUT1 0 10 V 24 VDC Output frequency 0 10 V 0 VDC 0 V reference Relay Output 2 Drive Enabled 17 18 10 12 13 AIN2 Analog ref 2 STO Safety in STO Safety in AOUT2 0 10 V 24 VDC Output...

Page 12: ...are accessible All other parameters are accessible with this parameter put to 201 P2 24 Switching Frequency Drive depending Keep as low as possible Higher value decreases audible noise in motor but i...

Page 13: ...r Analog setpoint Start in forward or reverse direction by digital signal and set frequency is either a fixed preset speed or analog input signal on terminal 6 Analog input is either 0 10 V or 4 20 mA...

Page 14: ...ed 2 10 Hz Select Select Select P2 03 PresetSpeed 3 25 Hz Not used Select Select P2 04 PresetSpeed 4 50 Hz Select Select P2 05 PresetSpeed 5 0 Not used Select P2 06 PresetSpeed 6 0 Select P2 07 Preset...

Page 15: ...rnal PID controller P2 13 Analog Output 2 Function 9 P2 12 Analog Output 1 0 If outputs is to be transistor outputs these parameters do not need to be configured 0 0 to 10 VDC 1 10 to 0 VDC 2 0 to 20...

Page 16: ...sd P5 01 EtherNet IP Set manually by PC program Modbus TCP CC Link Ver1 Remote device station Exclusive station 2 P5 01 P5 03 9 6 156 kbs 19 2 625 kbs 38 4 2 5 Mbs 57 6 5 Mbs 115 10 Mbs Ethercat Conta...

Page 17: ...DI3 0 What to be written in word 3 0 Not used No function 1 User PID Reference 0 to 1000 0 to 100 0 2 User Register 3 Variable in PLC program or group 9 parameters P5 13 Fieldbus Module PDI4 0 What to...

Page 18: ...mmand Source 0 4 4 Control by Modbus RTU P1 14 Parameter Access 0 201 Get access to all parameter P5 01 Drive Fieldbus Adress 0 Stationnumber 0 63 First Drive should be stationnumber 1 P5 03 Baud Rate...

Page 19: ...t P1 09 Motor Rated Frequency motor rated frequency P4 05 Motor Power Factor normally called cos of the motor P4 01 0 Standard induction motor with variable torque demand like fans 1 Standard inductio...

Page 20: ...1 P9 01 Enable Input source 1 1 Enable on Digital Input1 terminal 2 P9 03 Forward Run Input Source 1 1 Start signal on Digital Input1 terminal 2 P9 07 Reset Input Source 1 1 Alarm Reset on Digital Inp...

Page 21: ...PID Error to Enable Ramp 0 0 Internal ramps are always used 0 1 100 When PID error is less than setting internal ramps are not used and PID controller ramps output frequency Drive can react quickly to...

Page 22: ...ected to BFI through it s RJ45 connector BFI Smartstick also has a memory for parameter settings that can be read or written by it s buttons Choose BFI Stick Smart BLE in Communication Settings Push S...

Page 23: ...Inverter BFI H3 KI00363D 2021 07 www beijerelectronics com 23 32 6 Keypad The drive is configured and its operation monitored via the keypad and display 6 1Selecting language 6 2Drive Operating Displa...

Page 24: ...Beijer Electronics Frequency Inverter BFI H3 KI00363D 2021 07 www beijerelectronics com 24 32 6 3Changing Parameter Values BFI H3 BFI H3 BFI H3 BFI H3 BFI H3 BFI H3 BFI H3 BFI H3 BFI H3 BFI H3...

Page 25: ...1 If required the User Default Parameters may be cleared by setting P6 29 2 If the user wishes to reload Factory Defaults parameters to the drive memory then follow the procedure shown below left If t...

Page 26: ...can be used to speed up selecting and changing parameters when using the keypad When extended or advanced parameter access is enabled additional parameter groups are visible and may be selected quick...

Page 27: ...1 Total Run Time 0 to 99999 hours Displays the total operating time of the drive P0 35 Fan Run Time 0 to 99999 hours Displays total operating time of internal cooling fans P0 36 DC Bus Voltage at Trip...

Page 28: ...p Stop Mode Ramping Fast stop Coasting DC brake Zero speed holding time Motor Overload protect Current limit Input and output loss phase detection Trip level is resistance 2 5 kOhm General Functions P...

Page 29: ...plier for further information For disposal in countries outside of the European Union If you wish to discard this product please contact your local authorities or dealer and ask for the correct method...

Page 30: ...ctions into the drive fuses contactors 08 Over temperature trip Heatsink over temperature The heatsink temperature can be displayed in P0 21 A historical log is stored at 30 sec intervals prior to a t...

Page 31: ...rectly connected and free from faults Measured motor stator resistance varies between phases Check the windings for correct resistance and balance 41 Autotune fail 2 Measured motor stator resistance i...

Page 32: ...Beijer Electronics Frequency Inverter BFI H3 KI00363D 2021 07 www beijerelectronics com 32 32...

Reviews: