background image

 

Beijer Electronics Frequency Inverter BFI-H3 

                         

KI00363D           2021-07

 

 

 

www.beijerelectronics.com

             

 

4 (32)                                   

 

 

IP66 drives are fitted with a movable gland plate containing two cable entry holes. Please take 
care when drilling to avoid any particles within the BFI.   

Holes and recommended glands are listed in table below. The motor cable does not have to be 
attached to the drive with an EMC-gland.   

        

 

4.2  Physical dimensions IP55 

 

BFI-H3-IP55 

Drive 

size 

A    

Height 

[mm]

 

B

 

Width

 

[mm] 

C

   

Depth

 

[mm] 

D  

[mm] 

E

        

[mm]

 

Weight 

  

[kg] 

3 x 230 V 

3 x 400 V 

0300 

– 0460 [ 7,5-11 kW] 

0300 

– 0460   [ 15-22 kW] 

450 

171 

252 

428 

110 

12 

0610 - 0900 [ 15

–22 kW] 

0610 

– 0900   [ 30–45 kW] 

540 

235 

270 

515 

175 

23 

1100 

– 1500 [ 30–37 kW] 

1100 

– 1800   [ 55–90 kW] 

865 

330 

330 

830 

200 

55 

1800 

– 2480 [ 45–75 kW] 

2020 

– 3020   [110–160 kW] 

1280 

330 

360 

1245 

200 

89 

NOTE 

Mounting bolts 

Size 4 and 5:  4 x M8;               Size 6 and 7: 4 x M10 

Control Terminal, Required Torque 

0.5 Nm. 

Power Terminal, Required Torque 

Size 4: 2 Nm;            Size 5: 4 Nm          Size 6 and 7: 15 Nm. 

IP55 Drives do not have any predrilled gland holes for cable inlet.  

Cable Gland, IP66 Hole Size & recommended glands

 

Frame size 

Hole sizes 

Recommended PG Gland  

Size 1 

2 x 22 mm 

PG16 (correspond to M20) 

Size 2 & 3 

2 x 27 mm 

PG21 (correspond to M25) 

Size 4 

2 x 37 mm 

PG29 

Summary of Contents for BFI-H3

Page 1: ...t disconnect until 10 minutes have elapsed after turning off the supply Ensure correct earthing connections The earth cable must be sufficient to carry the maximum supply fault current which normally...

Page 2: ...22 6 KEYPAD 23 6 1 SELECTING LANGUAGE 23 6 2 DRIVE OPERATING DISPLAY 23 6 3 CHANGING PARAMETER VALUES 24 6 4 PARAMETERS FACTORY RESET USER RESET 25 6 5 SELECTING BETWEEN HAND AND AUTO CONTROL 25 6 6...

Page 3: ...ght kg 1 x 230 V 3 x 230 V 3 x 400 V 0043 0105 0 75 2 2 kW 0043 0105 0 75 2 2 kW 0022 0140 0 75 5 5 kW 2 257 188 186 200 176 172 4 8 None 0180 0240 4 0 5 5 kW 0180 0300 7 5 15 kW 3 310 211 235 252 198...

Page 4: ...00 V 0300 0460 7 5 11 kW 0300 0460 15 22 kW 4 450 171 252 428 110 12 0610 0900 15 22 kW 0610 0900 30 45 kW 5 540 235 270 515 175 23 1100 1500 30 37 kW 1100 1800 55 90 kW 6 865 330 330 830 200 55 1800...

Page 5: ...B 4 x M10 Size 8 4 x M12 Required tightening Torques Control terminals All Sizes 0 5 Nm Required tightening Torques Power terminals Size 2 3 1 0 Nm Size 4 2 Nm Size 5 4 Nm Size 6A 12 Nm Size 6B 15 Nm...

Page 6: ...n hardware limitations and do NOT take into consideration any requirements for compliance to any EMC standards Maximum motor cable length stated applies to using a screened motor cable When using an u...

Page 7: ...pplying Derating Factors A 4kW IP66 drive is to be used at an altitude of 2000 metres above sea level with 16 kHz switching frequency and 45 C ambient temperature Rated current of the drive is 9 5 Amp...

Page 8: ...hould be dimensioned according to any local codes or regulations 400V 230V 690V 400V STAR DELTA Motor cable must be a symmetrical shielded cable where the screen covers at least 85 of the cable surfac...

Page 9: ...he electrical cabinet Separate earth connection might be necessary Motor cable should avoid being installed close to telephone network or signal wiring Minimum distance is 10 cm More detailed descript...

Page 10: ...mally called IT net IT net is normally being used in all types of boats and also some parts of Norway In the rest of Europe TN net is most common were EMC filter can be used The EMC filter on BFI IP20...

Page 11: ...nalog ref 1 10 VDC AOUT1 0 10 V 24 VDC Output frequency 0 10 V 0 VDC 0 V reference Relay Output 2 Drive Enabled 17 18 10 12 13 AIN2 Analog ref 2 STO Safety in STO Safety in AOUT2 0 10 V 24 VDC Output...

Page 12: ...are accessible All other parameters are accessible with this parameter put to 201 P2 24 Switching Frequency Drive depending Keep as low as possible Higher value decreases audible noise in motor but i...

Page 13: ...r Analog setpoint Start in forward or reverse direction by digital signal and set frequency is either a fixed preset speed or analog input signal on terminal 6 Analog input is either 0 10 V or 4 20 mA...

Page 14: ...ed 2 10 Hz Select Select Select P2 03 PresetSpeed 3 25 Hz Not used Select Select P2 04 PresetSpeed 4 50 Hz Select Select P2 05 PresetSpeed 5 0 Not used Select P2 06 PresetSpeed 6 0 Select P2 07 Preset...

Page 15: ...rnal PID controller P2 13 Analog Output 2 Function 9 P2 12 Analog Output 1 0 If outputs is to be transistor outputs these parameters do not need to be configured 0 0 to 10 VDC 1 10 to 0 VDC 2 0 to 20...

Page 16: ...sd P5 01 EtherNet IP Set manually by PC program Modbus TCP CC Link Ver1 Remote device station Exclusive station 2 P5 01 P5 03 9 6 156 kbs 19 2 625 kbs 38 4 2 5 Mbs 57 6 5 Mbs 115 10 Mbs Ethercat Conta...

Page 17: ...DI3 0 What to be written in word 3 0 Not used No function 1 User PID Reference 0 to 1000 0 to 100 0 2 User Register 3 Variable in PLC program or group 9 parameters P5 13 Fieldbus Module PDI4 0 What to...

Page 18: ...mmand Source 0 4 4 Control by Modbus RTU P1 14 Parameter Access 0 201 Get access to all parameter P5 01 Drive Fieldbus Adress 0 Stationnumber 0 63 First Drive should be stationnumber 1 P5 03 Baud Rate...

Page 19: ...t P1 09 Motor Rated Frequency motor rated frequency P4 05 Motor Power Factor normally called cos of the motor P4 01 0 Standard induction motor with variable torque demand like fans 1 Standard inductio...

Page 20: ...1 P9 01 Enable Input source 1 1 Enable on Digital Input1 terminal 2 P9 03 Forward Run Input Source 1 1 Start signal on Digital Input1 terminal 2 P9 07 Reset Input Source 1 1 Alarm Reset on Digital Inp...

Page 21: ...PID Error to Enable Ramp 0 0 Internal ramps are always used 0 1 100 When PID error is less than setting internal ramps are not used and PID controller ramps output frequency Drive can react quickly to...

Page 22: ...ected to BFI through it s RJ45 connector BFI Smartstick also has a memory for parameter settings that can be read or written by it s buttons Choose BFI Stick Smart BLE in Communication Settings Push S...

Page 23: ...Inverter BFI H3 KI00363D 2021 07 www beijerelectronics com 23 32 6 Keypad The drive is configured and its operation monitored via the keypad and display 6 1Selecting language 6 2Drive Operating Displa...

Page 24: ...Beijer Electronics Frequency Inverter BFI H3 KI00363D 2021 07 www beijerelectronics com 24 32 6 3Changing Parameter Values BFI H3 BFI H3 BFI H3 BFI H3 BFI H3 BFI H3 BFI H3 BFI H3 BFI H3 BFI H3...

Page 25: ...1 If required the User Default Parameters may be cleared by setting P6 29 2 If the user wishes to reload Factory Defaults parameters to the drive memory then follow the procedure shown below left If t...

Page 26: ...can be used to speed up selecting and changing parameters when using the keypad When extended or advanced parameter access is enabled additional parameter groups are visible and may be selected quick...

Page 27: ...1 Total Run Time 0 to 99999 hours Displays the total operating time of the drive P0 35 Fan Run Time 0 to 99999 hours Displays total operating time of internal cooling fans P0 36 DC Bus Voltage at Trip...

Page 28: ...p Stop Mode Ramping Fast stop Coasting DC brake Zero speed holding time Motor Overload protect Current limit Input and output loss phase detection Trip level is resistance 2 5 kOhm General Functions P...

Page 29: ...plier for further information For disposal in countries outside of the European Union If you wish to discard this product please contact your local authorities or dealer and ask for the correct method...

Page 30: ...ctions into the drive fuses contactors 08 Over temperature trip Heatsink over temperature The heatsink temperature can be displayed in P0 21 A historical log is stored at 30 sec intervals prior to a t...

Page 31: ...rectly connected and free from faults Measured motor stator resistance varies between phases Check the windings for correct resistance and balance 41 Autotune fail 2 Measured motor stator resistance i...

Page 32: ...Beijer Electronics Frequency Inverter BFI H3 KI00363D 2021 07 www beijerelectronics com 32 32...

Reviews: