Beijer Electronics Frequency Inverter BFI-H3
KI00363D 2021-07
15 (32)
5.4 Transistor outputs 24 VDC or analog output, 0-10 V/4-20 mA
Terminal 8 and 11 can be either analog output 0-10 VDC/4-20 mA or transistor output 24
VDC. Outputs do not need an external power supply. Maximum load is 20 mA.
5.5 Relay outputs
Para-
meter
Name
Default
setting
Function
P2-11
Analog Output 1
Function
8
0:
Drive Enabled or running
1:
Drive Healthy
. Power is applied to the drive and no fault exists
2:
At Target Frequency
. Output frequency matches the set frequency
3:
Output Frequency > 0 Hz
4:
Output Frequency
≥ Limit
. Output frequency > P2-16 (AOUT1) or P2-19(AOUT2)
5:
Output Current
≥ Limit
. Motor current > P2-16 (AOUT1) or P2-19(AOUT2)
6:
Output Frequency < Limit
. Output frequency > P2-17(AOUT1) or P2-20(AOUT2)
7:
Output Current < Limit.
Motor current < P2-17(AOUT1) or P2-20(AOUT2)
8:
Output Frequency 0-10 V
=> 0 Hz to setting in P1-01
9:
Output Motor Current 0-10 V
: 0 to 200% of setting in P1-08
10:
Output (Motor) Torque
. 0
– 165% of motor rated torque
11:
Output (Motor) Power
. 0 to 150% of drive rated power
12:
PID Output
. 0
– 100% represents the output of the internal PID controller
P2-13
Analog Output 2
Function
9
P2-12 Analog Output 1
0
If outputs is to be transistor outputs these parameters do not need to be configured.
0: 0 to 10 VDC; 1: 10 to 0 VDC; 2: 0 to 20 mA;
3: 20 to 0 mA; 4: 4 to 20mA; 5: 20 to 4 mA
P2-14 Analog Output 2
0
Parameter Default
setting
Function
P2-15: Relay
output 1
function
terminal 15
and 16
1
0:
Drive Enabled or running
1
Drive Healthy
. Power is applied and no fault exists
2:
At Target Frequency
. Output frequency= Set
frequency
3:
Output Frequency > 0.0 Hz
4:
Output Frequency
≥ Limit
. Output frequency > P2-
16 (Relay1) or P2-19 (Relay2)
5:
Output Current
≥ Limit
. Motor current > P2-16
(Relay1) or P2-19 (Relay2)
6:
Output Torque ≥ Limit.
Motor torque current > P2-
16 (Relay1) or P2-19 (Relay2)
7:
Analog input 2 > Limit
. Analog input 2 > P2-16
(Relay1) or P2-19(Relay2)
8:
DOL1
Pump staging
– DOL Cascade.
9:
Fire Mode Active
10:
Maintenance Due
11:
Drive available-
Ready to run
12:
Drive Tripped
and in a fault condition
13:
Sate Torque off (STO) status
14:
PID Error ≥ Limit
. The PID Error ≥ Programmed
limit
15:
Low and High Current Warning
P2-18: Relay
output 2
function
terminal 18
0
8
9
AOUT1
: 0-10 V / 4-20 mA / 24 VDC
Default Output Frequency 0-10 V
0 V reference
AOUT2
: 0-10 V / 4-20 mA / 24 VDC
Default Output Motor Current 0-10 V
11
Relay Output 2
Default Drive
Enabled
17
18
Relay Output 1
Default Drive
Healthy
14
15
16