4.7 Overview of power supply, grounding and motor cable
•
Power should be connected to the L1/L and L2/N terminals for single phase drives, L1, L2 and
L3 for three phase drives. Phase sequence is not important.
•
For EMC compliance Class C1, a symmetrical shielded cable is recommended.
•
All cables should be dimensioned according to any local codes or regulations.
400V
230V
690V
400V
STAR
DELTA
•
Motor cable must be a symmetrical shielded cable where the screen covers at least 85% of the
cable surface area to fulfil EMC requirements. Example of cables to be used are RKFK, Ölflex
Classic 100 CY, FKKJ-EMC, or similar.
•
Protective grounding of motor is connected to drive
•
Motor cable should be connected to U, V, W.
•
Motor is to either be connected in Star or Delta
➢
Inverter Power supply 3*400 VAC:
-
Rated voltage of motor 230/400, Star connection
-
Rated voltage of motor 400/660, Delta connection