INSTAllATION
� C AUTIOH:
B e f o r e i n s t a l l i n g , v e r i fy that the s e t t i ng s r e q u i r e d f o r the
v a r i o u s f un c t i ons are c o r r e ct by c h e c k i n g the s e t t i n g s s t i c k e r mounted on
the inside surface of the unit.
The PRlDE®Unit can
be
surface mounted or semiflush mounted as shown in Figures 9 and 10. Many small
generator applications will use a weather-proof box containing the PRIDE, manual disconnect and a
contactor for the interconnection relaying. In these systems the relay will
be
surface mounted. other
systens will require semi flush mounting using a rectangular cutout in a relaying r;:a,nel or swinging
door.
Refer to Figure 9 for mOlUlting and outline dimensions and Figure 10 for hole drill
aoo
cutout
dimen.s,ions for semiflush mounting.
Because the semiflush mOWlting nut is located on the inside lip of the relay box and under the front
cover, care should be taken when choosing a mounting screw. These should
be
#10-32 screws; four are
required. Refer to Figure
8
for choosing the length of the mounting screws for semiflush mounting.
The length of the screw should not exceed 1I4n from the back side of the mounting lip. The total
length should
be
1/4" plus the thickness of the panel.
# ' 0-32
PEM N U T
PART O F FLANGE
GASKET
(NOT SHOWN)
COVER �
MOUNTING
MOUNTING PANEL OF
THICKNESS ·T"
" 1 0-32 SCREW
r
(USER SUPPLIED)
SUPPLIED)
ASSUME WASHER T H I C K N E S S
. 0 6 M A X
L == T + 1/4 IN.
( + 1/8 IN . ,
-
0 IN . )
FIGURE 8 Semlflush Mounting Screw
The external wiring connections to the PRIDE unit are made to a 12-position terminal block that is
mounted on the rear of the
PRIDE
when a semiflush mount unit is ordered. If a surface mounted
PRIDE
is
ordered, a 6-inch cable will extend below the unit with the terminal block attached. The terminal
block should then
be
coonected to the panel to which the
PRIDE
Unit is mounted.
Both terminal block
posi tions are shown in Figure 9.
A lug is located in the lower left hand corner for case grounding purposes. Number 6 to 14
AWG
wire
can be
used for this ground strap.