Introduction
The functionalities of the Beckhoff PCI card FC310x (as
TwinCAT (NCI, PTP, PLC and IO) is described below.
TwinCAT 2.7 does not support all the functions described below. TwinCAT 2.8 on the other hand supports all
functions described below, with the exception of redundancy and of the ADS server interface of the FC310x
as a slave (these will both be supported as from TwinCAT 2.9).
The following chapters also apply to the PROFIBUS connection for the CX1000 (CX1500-M310 (master) or
CX1500-B310 (slave)); the name FC310x then also refers to the CX1500-M310 master or CX1500-B310
slave connection.
2.2
FC310x - Technical Data
Technical Data
FC3101
FC3102
Bus system
PROFIBUS DP (standard), PROFIBUS DP-V1 (Cl. 1+2:
acyclic services, alarms), DP-V2, PROFIBUS MC (equidistant)
Number of fieldbus channels
1
2
Data transfer rate
9.6 kbit/s – 12 Mbit/s
Diagnostics
2 LEDs per channel
Interface to the PC
Plug-and-play PCI interface, 32 bit with 4 kbytes DPRAM per
channel
Bus interface
1 x D-Sub socket, 9-pin,
galvanically isolated
2 x D-Sub socket, 9-pin,
galvanically isolated
Communication
Master and slave functionality (also mixed)
Bus devices
per channel: max. 125 slaves with up to 244 bytes input,
output, parameter, configuration or diagnostic data per slave
Process image
Sum max.: 3 kbytes input and output data
Cycle time
differing DP cycle times per slave are possible using the CDL
concept
Standard driver
standard operating system driver for Intel-compatible NIC
Real-time driver
TwinCAT driver for real-time Ethernet
Supply voltage (PCI bus)
5 V
Current consumption (PCI bus, 5 V)
typ. 600 mA
typ. 1000 mA
Power consumption from PCI bus
< 5 W
Weight
approx. 45 g
approx. 75 g
Dimensions (W x H x D, without slot panel)
approx. 14 mm x 106 mm x 175 mm
Permissible ambient temperature range
during operation
0°C ... + 55°C
Permissible ambient temperature range
during storage
-25°C ... + 85°C
Permissible relative air humidity
95 %, no condensation
Vibration / shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27
EMC immunity / emission
conforms to EN 61000-6-2 / EN 61000-6-4
Installation position
variable
Approval
CE